Finding | |
---|---|
Title | Failure to Identify and Correct Faulty NI-36 Channel |
Description | Inspectors identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XVI, for the licensees failure to identify a condition adverse to quality. Specifically, the licensee failed to identify that a faulty logarithmic amplifier was producing inaccurate intermediate range nuclear instrument channel NI-36 indications. This resulted in multiple instances of delays in the change of state of reactor trip instrumentation permissive P-6 when shutting down the reactor. The licensee replaced NI-136s log current amplifier using approved procedures and returned the channel to service. This issue was entered into the corrective action program as Condition Report 16-1227. The licensees failure to identify a condition adverse to quality regarding intermediate range nuclear instrument channel NI-36 was a performance deficiency. Specifically, the licensee failed to identify a faulty log current amplifier in intermediate range nuclear instrument channel NI-36, which led to multiple instances of inaccurate indication and delays in the change of state of reactor trip instrumentation permissive P-6, when shutting down the reactor that required operator action and unplanned technical specification entries. This performance deficiency is more than minor and, therefore, a finding because it impacts the equipment performance attribute of the Mitigating Systems Cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The inspectors screened this finding using Inspection Manual Chapter 0609, Appendix A, The Significance Determination Process (SDP) For Findings At-Power, dated June 19, 2012. The finding screened as Green per Section A of Exhibit 2, Mitigating Systems Screening Questions, because the finding did not affect the design or qualification of a mitigating structure, system, or component; the finding did not represent a loss of the system and/or function; the finding did not represent an actual loss of function of at least a single train for greater than its Technical Specification allowed outage time; and the finding did not represent an actual loss of function of one or more non-technical specification trains of equipment designated as high safety-significant in accordance with the licensees maintenance rule for more than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Inspectors determined the finding had a cross-cutting aspect of conservative bias in the human performance area because leaders did not take a conservative approach to decision making, particularly when information is incomplete or conditions are unusual. Specifically, the licensee made the decision not to enter their procedure for preventing recurring equipment problems process, even though entry criteria to do so was met, because of a false confidence that the correct cause had already been identified [H.14]. |
Site: | South Texas |
---|---|
Report | IR 05000498/2016001 Section 4OA2 |
Date counted | Mar 31, 2016 (2016Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | A Sanchez B Tripathi E Simpson L Brookhart N Hernandez N Taylor |
Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification - Procedures Technical Specification |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |