ML15161A176

From kanterella
Revision as of 00:10, 1 July 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Shine Medical Technologies V. 0 - Chapter 08 - Figure 8a2.1-001
ML15161A176
Person / Time
Site: SHINE Medical Technologies
Issue date: 05/21/2015
From: Bynum R V
Shine Medical Technologies
To:
Office of Nuclear Reactor Regulation
Lynch S
References
SHINE, SHINE.SUBMISSION.18, SHN.PSAR.P, SHN.PSAR.P.8
Download: ML15161A176 (1)


Text

Figure 8a2.1 One-Line Diagram - Normal Electrical Power Supply System NOTES:1. BREAKERS DROP OUT (TRIP) ON LOSS OF POWER TO THE BUS AND CAN BE MANUALLY CLOSED SELECTIVELY AFTER SDG RESTORES POWER TO THE BUSES.2. SDG AND AUTOMATIC TRANSFER EQUIPMENT LOCATED IN SEPARATE BUILDING.

3. RESPECTIVE 480V AC SWGR BUS A OR B POWERS THE SDG BUSES DURING NORMAL OPERATION. ON LOSS OF OFF-SITE POWER, BOTH AC SWGR A AND B WILL BE CONNECTED AS NEEDED.4. ON LOSS OF OFF-SITE POWER SDG WILL START. AFTER RATED VOLTAGE AND FREQUENCY ARE ESTABLISHED AT THE SDG BUS, BREAKER FEEDS TO OTHER FACILITY LOADS WILL BE MANUALLY CONNECTED AS NEEDED.5. LOAD BREAKERS EQUIPPED WITH SOFT STARTERS.6. SDG - STANDBY DIESEL GENERATOR7. FIRE PUMP CONTROLLER BOX PER NFPA 20 AND IS LOCATED IN SIGHT OF FIRE PUMP ROOM.480V-208Y/120V75 kVA3PHDISTRIBUTION PANEL FOR TCAP 1, 2, 3 & 4CHILLER 1FACILITY 480V AC PLANT SWGR A208Y/120V 200A3PH, 4W12kV-480Y/277V2000 kVA3PHTRANSFORMER OUTDOOR TYPE12kV UTILITY FEEDER CABLE BUSUTILITY INTERFACEZONE 1 EXHAUSTFAN AZONE 2 EXHAUSTFAN AOUTDOORNCM480V-208Y/120V75 kVA3PHDISTRIBUTION PANEL FOR TCAP 5, 6, 7 & 8CHILLER 3 FACILITY 480V AC PLANT SWGR B208Y/120V 200A 3PH, 4W12kV-480Y/277V 2000 kVA3PHTRANSFORMER OUTDOOR TYPE12kV UTILITY FEEDERCABLE BUSUTILITY INTERFACEZONE 2 EXHAUSTFAN B(STANDBY)OUTDOORNCM480VLATER kW3PH, 4WNCNOBATTERYCHARGER ABATTERYCHARGER BNCNCNONOPLUG-INPORTABLE DG FACILITY 480V AC SDG BUS A AT SWGR ROOM NOTE 3 NOTE 3NCNOTE 4LOCATED INSDG BUILDINGUPS VOLTAGEREGULATINGXFMR ASSEMBLY BUPS VOLTAGEREGULATINGXFMR ASSEMBLY A NCNCNCNCTO 480V AC MCC A1TO 480V ACMCC A2TO 480V AC MCC B1TO 480V ACMCC B2TO 480V ACSDG MCC B125HP200HP100HP200HP100HPSDGCHILLER 4 200HPCHILLER 2200HPEMERGENCYLIGHTINGPANELZONE 1EXHAUST FAN B(STANDBY)125HPNCTO 480V ACSDG MCC A NCEMERGENCYLIGHTINGPANEL FACILITY 480V AC SDG BUS B AT SWGR ROOM NOOUTDOOR LOAD BANKFOR SDGTESTINGNONOFROM 480V AC SUPPLY SDG MCC A FIRE PUMP 200HPFIRE PUMP ROOM(LOCATED OUTSIDE FACILITY)FIRE PUMPCONTROLLER BOX (NOTE 7) Chapter 8 - Electrical Power Systems Normal Electrical Power Systems SHINE Medical Technologies Rev. 0