Figure 8a2.1 One-Line Diagram - Normal Electrical Power Supply System NOTES:
- 1. BREAKERS DROP OUT (TRIP) ON LOSS OF POWER TO THE BUS AND CAN BE MANUALLY CLOSED SELECTIVELY AFTER SDG RESTORES POWER TO THE BUSES.
- 2. SDG AND AUTOMATIC TRANSFER EQUIPMENT LOCATED IN SEPARATE BUILDING.
- 3. RESPECTIVE 480V AC SWGR BUS A OR B POWERS THE SDG BUSES DURING NORMAL OPERATION. ON LOSS OF OFF-SITE POWER, BOTH AC SWGR A AND B WILL BE CONNECTED AS NEEDED.
- 4. ON LOSS OF OFF-SITE POWER SDG WILL START. AFTER RATED VOLTAGE AND FREQUENCY ARE ESTABLISHED AT THE SDG BUS, BREAKER FEEDS TO OTHER FACILITY LOADS WILL BE MANUALLY CONNECTED AS NEEDED.
- 5. LOAD BREAKERS EQUIPPED WITH SOFT STARTERS.
- 6.
SDG - STANDBY DIESEL GENERATOR
- 7.
FIRE PUMP CONTROLLER BOX PER NFPA 20 AND IS LOCATED IN SIGHT OF FIRE PUMP ROOM.
480V-208Y/120V 75 kVA 3PH DISTRIBUTION PANEL FOR TCAP 1, 2, 3 & 4 CHILLER 1 FACILITY 480V AC PLANT SWGR A 208Y/120V 200A 3PH, 4W 12kV-480Y/277V 2000 kVA 3PH TRANSFORMER OUTDOOR TYPE 12kV UTILITY FEEDER CABLE BUS UTILITY INTERFACE ZONE 1 EXHAUST FAN A ZONE 2 EXHAUST FAN A OUTDOOR NC M
480V-208Y/120V 75 kVA 3PH DISTRIBUTION PANEL FOR TCAP 5, 6, 7 & 8 CHILLER 3 FACILITY 480V AC PLANT SWGR B 208Y/120V 200A 3PH, 4W 12kV-480Y/277V 2000 kVA 3PH TRANSFORMER OUTDOOR TYPE 12kV UTILITY FEEDER CABLE BUS UTILITY INTERFACE ZONE 2 EXHAUST FAN B (STANDBY)
OUTDOOR NC M
480V LATER kW 3PH, 4W NC NO BATTERY CHARGER A BATTERY CHARGER B NC NC NO NO PLUG-IN PORTABLE DG FACILITY 480V AC SDG BUS A AT SWGR ROOM NOTE 3 NOTE 3 NC NOTE 4 LOCATED IN SDG BUILDING UPS VOLTAGE REGULATING XFMR ASSEMBLY B UPS VOLTAGE REGULATING XFMR ASSEMBLY A NC NC NC NC TO 480V AC MCC A1 TO 480V AC MCC A2 TO 480V AC MCC B1 TO 480V AC MCC B2 TO 480V AC SDG MCC B 125 HP 200 HP 100 HP 200 HP 100 HP SDG CHILLER 4 200 HP CHILLER 2 200 HP EMERGENCY LIGHTING PANEL ZONE 1 EXHAUST FAN B (STANDBY) 125 HP NC TO 480V AC SDG MCC A NC EMERGENCY LIGHTING PANEL FACILITY 480V AC SDG BUS B AT SWGR ROOM NO OUTDOOR LOAD BANK FOR SDG TESTING NO NO FROM 480V AC SUPPLY SDG MCC A FIRE PUMP 200 HP FIRE PUMP ROOM (LOCATED OUTSIDE FACILITY)
FIRE PUMP CONTROLLER BOX (NOTE 7)
Chapter 8 - Electrical Power Systems Normal Electrical Power Systems SHINE Medical Technologies Rev. 0