ML17331B325

From kanterella
Revision as of 07:12, 29 June 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Responds to NRC 931103 Request for Rev to Util Previously Proposed Amend Request for TS to Increase Allowable Tolerances for Main Steam Safety Valves.Marked Up of Existing Specs & Proposed Revised Spec Pages Encl
ML17331B325
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 03/29/1994
From: FITZPATRICK E
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML17331B327 List:
References
AEP:NRC:1169B, TAC-M84979, TAC-M84980, NUDOCS 9404040076
Download: ML17331B325 (4)


Text

indianaMichiganPowerCompanyP.O.Box16631Columbus, OH432168AEP:NRC:1169B DonaldC.CookNuclearPlantUnits1and2DocketNos.50-315and50-316LicenseNos.DPR-58andDPR-74UPDATEFORTECHNICAL SPECIFICATIONS CHANGETOINCREASETHEALLOWABLE TOLERANCES FORMAINSTEAMSAFETYVALVES(TACNOS.M84979andM84980)U.S.NuclearRegulatory Commission DocumentControlDeskWashington, D.C.20555Attn:W.T.RussellMarch29,1994

DearMr.Russell:

Thisletterissubmitted inresponsetoMs.BethA.Wetzel'sNovember3,1993letter,requesting arevisiontoourpreviously proposedamendment requestfortechnical specification toincreasetheallowable tolerances formainsteamsafetyvalves.Ouramendment request(AEP:NRC:1169) providesjustification thatasafetyvalveisoperablewithaliftsettingof+3%,andfurtherindicates ourintention toresetanyvaluetestedtothenominalvalueof+1%toprovideassurance thatanysetpointdriftwillnotcontinuesubstantially outsidethe+3%analyzedrange.Inadditiontostatingthisrequirement inthebasesoftherespective specifications, astatement hasbeenplacedinthesurveillance requirements ofSpecification 4.7.1.1ofbothUnit1andUnit2,asrequested.

Oneadministrative changehasbeenmadeintheproposedTechnical Specifications 3.7.1.1and4.7.1.1tomakethemconsistent betweenUnits1and2.Specifically, thereference toTable3.7-4,intheUnit2specification, wasmovedtotheSurveillance Requirements ofSpecification 4.7.1~1afterrenumbering Table3.7-4toTable4.7-1.Renumbering thetableprovidesconsistency betweenUnits1and2.Alsoonthistable,thevalvedesignations havebeenupdatedtomakethemconsistent withplantcomponent numbers.Atypographical errorwascorrected inthesecondsentenceofUnit1Specification 3.7.1.1.a, whichreplacedtheword"many"with"may.",940404007674032'P

~'DR,'ADQCK 05000315P'PDR I~I~

Mr.W.T.Russell2AEP'NRC'1169B Attachment 1tothislettercontainsmarkedupcopiesoftheexistingspecifications.

Attachment 2containstheproposedrevisedspecification pages.Itshouldbenotedthattheseattachments alsocontaincopiesoftherevisedandmarkedupSpecification 3.5.2andBases,whichwerediscussed intheoriginalsubmittal.

Theamendments discussed abovedonotchangetheresultsofouranalysesconcerning significant hazardsconsiderations discussed intheoriginalsubmittal.

Sincethechangesfromouroriginalsubmittal areadministrative innature,itisourbeliefthatpublication ofthechangesintheFederalRegisterisnotrequired.

Therefore, webelievethattheproposedchangeswillnotresultin(1)asignificant changeinthetypesofeffluents orasignificant increaseintheamountofanyeffluentthatmaybereleasedoffsite,or(2)asignificant increaseinindividual orcumulative occupational radiation exposure.

Thisletterissubmitted pursuantto10CFR50.54(f)and,assuchanoathstatement isattached.

Sincerely, PCVicePresident Attachments cc:A.A.BlindG.CharnoffJ.B.Martin-RegionIIINFEMSectionChiefNRCResidentInspector J.R.Padgett STATEOFOHIO)COUNTYOFFRANKLIN)

E.E.Fitzpatrick, beingdulysworn,deposesandsaysthatheistheVicePresident oflicenseeIndianaMichiganPowerCompany,thathehasreadtheforgoingUPDATEFORTECHNICAL SPECIFICATIONS CHANGETOINCREASETHEALLOWABLE TOLERANCES FORMAINSTEAMSAFETYVALVES(TACNOS.M84979andM84980)andknowsthecontentsthereof;andthatsaidcontentsaretruetothebestofhisknowledge andbelief.Subscribed andsworntobeforemethis~dayof19~vNOTARYPUBLICAlTAD.HILLtIOTARYPBBI.IC.STATEOFOHIO