05000272/FIN-2015007-02
From kanterella
Revision as of 22:23, 29 May 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Finding | |
---|---|
Title | LICENSEE-IDENTIFIED Violation |
Description | Licensee Event Report 05000272/2013-004-00 describes an unanalyzed condition in which PSEG identified their DC ammeter circuits were unfused. Specifically, PSEG did not provide overcurrent protection for wiring associated with DC ammeter indication in the control room to prevent wires from overheating due to fire-induced faults and excessive currents flowing through the cable. With enough current flowing through the cable, the potential exists that the overloaded ammeter wiring could damage system wiring or adjacent safety-related circuits in the cable trays needed for post-fire safe shutdown. This condition could result in a loss of the associated safe shutdown components or a secondary fire in another fire area. The failure to protect safe shutdown cables from the effects of postulated fires was a performance deficiency. This performance deficiency was a violation of Operating License Condition 2.C.(5) for Unit 1 and 2.C.(10) for Unit 2, which requires in part, post-fire safe shutdown cables remain free of the effects of fire-induced cable faults during postulated fires. Contrary to the above, PSEG identified they failed to meet this requirement and the condition existed since initial construction of both units. The issue was more than minor because it was associated with the protection against external events (fire) attribute of the mitigating systems cornerstone and it adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The team determined that the finding was of very low safety significance (Green), based IMC 0609, Appendix F, Fire Protection Significance Determination Process (SDP), Phase 2 screening criteria. The finding screened to Green based upon, task number 2.3.5, because the affected cables were routed in alternate shutdown fire areas that are protected by detection and automatic suppression systems. Additionally, the cable construction is IEEE 383 (thermoset) with a heavy bronze/copper metal shield tied to station ground which decreases the likelihood of inter-cable and intra-cable interactions. Based on a team walkdown, the team determined that the ammeter cable routing was not routed near a credible fire ignition source in the affected fire areas. Because this finding is of very low safety significance and had been entered into PSEGs corrective action program (notification 20630018), this violation is being treated as a Green, licensee identified NCV consistent with the NRCs Enforcement Policy. |
Site: | Salem |
---|---|
Report | IR 05000272/2015007 Section 4OA7 |
Date counted | Mar 31, 2015 (2015Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Licensee-identified |
Inspection Procedure: | |
Inspectors (proximate) | J Rady J Rogge K Young S Galbreath W Cook D Orr |
Violation of: | License Condition License Condition - Fire Protection |
INPO aspect | |
' | |
Finding - Salem - IR 05000272/2015007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Salem) @ 2015Q1
Self-Identified List (Salem)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||