05000382/FIN-2008005-01
From kanterella
Revision as of 20:34, 28 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Finding | |
---|---|
Title | Essential Chiller B Tube Rupture Due to Untimely Corrective Actions |
Description | The inspectors reviewed a self revealing noncited violation of 10 CFR 50,Appendix B, Criterion XVI due to the failure by the licensee to take prompt corrective actions following the identification of an inadequate testing method used for determining the integrity of the Essential Chiller B heat exchanger tubing. Failure to take this timely action resulted in an inadvertent tube rupture and inoperability of Essential Chiller B. The licensee entered this deficiency into their corrective action program as Condition Report CR-WF3-2008-5342.This finding was more than minor because it is associated with the Mitigating Systems attributes for Equipment Performance and would impact the availability and reliability of systems that respond to initiating events. The inspectors evaluated this finding using Manual Chapter 0609, Attachment 4, and determined that it was of very low safety significance (Green) because, assuming worst case degradation of both the B and AB Essential Chillers failing, the redundant A Essential Chiller would still have been available for accident mitigation. This finding had a crosscutting aspect in Problem Identification and Resolution, specifically the Corrective Action Program aspect P.1(d) because the licensee failed to take appropriate corrective actions to address a degrading condition in a timely manner. Specifically, the failure to perform timely tube inspections of Essential Chiller B, following the identification of an inadequate testing methodology used for identifying Essential Chiller heat exchanger tubing degradation (Section 4OA2) |
Site: | Waterford |
---|---|
Report | IR 05000382/2008005 Section 4OA2 |
Date counted | Dec 31, 2008 (2008Q4) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | P Elkmann G Replogle J Clark R Azua D Overland B Correll |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |