| Title | Essential Chiller AB Component Failure Due to Inadequate Procedural Guidance |
| Description | The inspectors reviewed a self revealing noncited violation of Technical Specification 6.8.1.a for failure to provide documented instructions appropriate to the circumstances as recommended in Appendix A of Regulatory Guide 1.33.The failure by the licensee to provide adequate guidance for the replacement of the Essential Chiller AB compressor motor temperature sensor resulted in there introduction of a failure mechanism that had previously been corrected. This subsequently led to the failure of the temperature sensor wiring and inoperability of Essential Chiller AB. The licensee entered this deficiency into their corrective action program as Condition Report CR-WF3-2008-5471.This finding was more than minor because it is associated with the Mitigating Systems attributes for Equipment Performance and would impact the availability and reliability of systems that respond to initiating events. The inspectors evaluated this finding using Manual Chapter 0609, Attachment 4, and determined that it was of very low safety significance (Green) because the redundant Essential Chillers A and B would still have been available for accident mitigation. Based on the guidance provided in Manual Chapter 0612, Appendix B, Section1-5, Screen for Cross-Cutting Aspects, this finding did not have a crosscutting aspect because it was not considered to be reflective of current licensee performance. Specifically, the licensees failure to update the model work instructions in 2000 was a latent issue, whereby the licensee did not have a reasonable opportunity to identify the problem prior to August, 2008. In addition, the licensee has since instituted programs and processes such that the problem would not reasonably occur today (Section 4OA2) |
| Site: | Waterford |
|---|---|
| Report | IR 05000382/2008005 Section 4OA2 |
| Date counted | Dec 31, 2008 (2008Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | P Elkmann G Replogle J Clark R Azua D Overland B Correll |
| INPO aspect | |
| ' | |
Finding - Waterford - IR 05000382/2008005 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Waterford) @ 2008Q4
Self-Identified List (Waterford)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||