{{#Wiki_filter:Southern Nuclear Operating Company, Inc.Post Office Box 1295 Birmingham, Alabama 35201-1295 Tel 205.992.5000 SOUTHERN COMPANY July 23, 2008 Energy to Serve Your World" Docket No.: 50-424 NL-08-1166 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Vogtle Electric Generating Plant -Unit 1 Inservice Inspection Summary Report Ladies and Gentlemen: Southern Nuclear Operating Company,(SNC) submits herewith the Vogtle Electric Generating Plant Unit 1, Interval 3, Period 1, Outage 1 (1 R1 4) Inservice Inspection (ISI) Summary Report (Enclosure). This report describes and summarizes the ISI activities performed in the third ISI interval during the spring 2008 maintenance/refueling outage. Paragraph IWA-6230 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section XI, 2001 Edition with the 2003 Addenda (Code) requires submittal of the enclosed report.In addition to examinations credited for the third ISI interval, this report also includes those examinations, tests and Code-applicable repair and/or replacement activities performed in 1 R1 4, which are credited to complete the second ISI interval. Even though the second ISI interval ended May 30, 2007, the Code has provisions for extending, by as much as one year, that portion of an inspection interval, described as an inspection period, to enable an inspection to coincide with a plant outage. 1R14 occurred in March and April of 2008 which is within one year of the end of the second ISI interval. A separate form NIS-1 is included in the report which addresses applicable information to the specific ISI intervals. The supporting ISI documentation, e.g., examination plans and schedules, examination results and reports, examination methods and procedures, evaluation results, and corrective action and repairs, is available for review upon request at Vogtle Electric Generating Plant.XW67 U. S. Nuclear Regulatory Commission NL-08-1166 Page 2 This letter contains no NRC commitments. If you have any questions, please advise.Sincerely, M. J. Ajuni Manager -Nuclear Licensing MJA/DRG/daj

Enclosure:

Vogtle Electric Generating Plant -Unit 1 Inservice Inspection Summary Report Refueling Outage (1 R14)cc: Southern Nuclear Operating Company Mr. J. T. Gasser, Executive Vice President Mr. T. E. Tynan, Vice President -Vogtle Mr. D. H. Jones, Vice President -Engineering RType: CVC7000 U. S. Nuclear Regulatory Commission Mr. L. A. Reyes, Regional Administrator Mr. R. A. Jervey, NRR Project Manager -Vogtle Mr. G. J. McCoy, Senior Resident Inspector -Vogtle Vogtle Electric Generating Plant -Unit 1 Enclosure Inservice Inspection Summary Report SOUTHERNAM SOUTHERNAEN. COMPANY COMPANY Energy to Serve Your World* Energy to Serve Your World'INSERVICE INSPECTION REPORT REFUELING 14 INTERVAL 3 PERIOD I, O UTAG E "I Vogtle Electric Generating UniftI Plant (7821 River Road, P.0. Box, 1600, Waynesboro, Georgia 30830)Soluthlern Nuclelar Operating Corn;40 In~verness Parkway Birlmingham, Alabama 35242)any COMMERCIAL OPERATION DATE:- May 31, 1987 DOCUMENT COMPLETION DATE: June 2008 VOGTLE ELECTRIC GENERATING (VEGP)PLANT 1R14 FINAL REPORT TABLE OF CONTENTS SECTION TAB VOLUME I (OWNER'S REPORT)* INTRODUCTION AND ABBREVIATIONS A" ASME FORM NIS-1 AND ABSTRACT B" INSERVICE INSPECTION (OWNER'S REPORT) EXAMINATION

SUMMARY

CLASS 1 AND 2 WELDS AND SUPPORT EXAMINATIONS C SYSTEM PRESSURE TESTS D REPORTABLE INDICATION

SUMMARY

E* OWNER'S REPORT FOR REPAIRS AND REPLACEMENTS (FORM NIS-2) F VOLUME 2 (ISI EXAMINATION DATA)" EXAMINATION PROGRAM PLAN (TOTAL SCOPE

SUMMARY

) G* ISI EXAMINATION DATA H VOLUME 3 (CERTIFICATIONS)

  • PERSONNEL CERTIFICATIONS I* EXAMINATION PROCEDURES (LISTING)

J" EQUIPMENT CERTIFICATIONS & CALIBRATION BLOCKS (LISTING) K VOLUME 4 (FLOW ACCELERATED CORROSION -FAC)" FAC EXAMINATION

SUMMARY

L* FAC EXAMINATION DATA M VOLUME 1 CONTAINS THE INFORMATION TO MEET THE REQUIREMENTS OF ASME CODE 2001 EDITION w 2003 ADDENDA, SECTION XI, SUBSECTION IWA-6230 FOR SUBMITTAL OF A

SUMMARY

REPORT TO THE NRC FOLLOWING EACH REFUELING OUTAGE.VOLUMES 2 AND 3 CONTAIN THE SUPPORTING DOCUMENTATION FOR THE EXAMINATIONS PERFORMED (RETAINED ON SITE BY VEGP)VOLUME 4 CONTAINS DOCUMENTATION OF THE FLOW ACCELERATED CORROSION (FAC) INSPECTIONS PERFORMED (RETAINED ON SITE BY VEGP) SOUTHERN COMPANY Energy to Serve Your World'SOUTHERN Euk COMPANY Energy to Serve Your World*SOUTHERN NUCLEAR§OPERAVTING C OMPANY MA TERIALS A.ND INSPECTION SER VICES INSERVICE INSPECTIONS PLANT VOGTLE UNIT 1 REFUELING OUTAGE 144 SPRING 2008 Volumes R Owner's Rep'ort, TAB A INTRODUCTION & ABBREVIATIONS INTRODUCTION This report documents the examinations and tests performed at Vogtle Electric Generating Plant, Unit 1 (VEGP-1) between October 27, 2006 (date of last examination performed during the thirteenth (1 3 th)maintenance/refueling outage, 1 R13) and April 24, 2008 (end of the fourteenth (1 4 th)maintenance/refueling outage, 1R14) to meet the requirements of Article IWA-6000 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section XI, 2001 Edition with 2003 Addenda (Code).This report also addresses Code-applicable repairs and/or replacements, which were documented since the last maintenance/refueling outage at VEGP-1 through the completion of the fourteenth maintenance/refueling outage in April 24, 2008. The Owner's Reports for Repairs and Replacements (Form NIS-2) are included herein.In addition to examinations credited for the third inspection interval, this report also includes those examinations, tests and Code-applicable repair and/or replacement activities, which are credited to the second inspection interval. Even though the second inspection interval ended May 30, 2007, the Code has provisions for performing examinations within one year after the end of the inspection interval to coincide with a plant outage. The 1 R14 outage occurred in March and April of 2008 which is within the one year. A separate form NIS-1 is included which addresses applicable information to the specific intervals. The specific exams and NIS-2 forms are itemized and identified in the pressure tests and NIS-2 summary sections.This report does not include Steam Generator Tube Inspections which are required per VEGP Technical' Specification 5.6.10. This information will be provided in a separate report one hundred eighty (180) days after the initial entry into MODE 4 following completion of an inspection performed in accordance with Technical Specification 5.5.9. The ASME Code requirements were met and the separate report will provide the details for these examinations. This report also does not address pressurizer weld overlay application and post overlay examinations. The results of the overlay project have been submitted under a separate cover letter (NL-08-0667 dated May 2, 2008).1-1 LIST OF ABBREVIATIONS ACC Acceptable AD Anchor/Darling AFW Auxiliary Feedwater System Al GPC Action Item (followed by unique no. denoting Action Item number)ANII Authorized Nuclear Inservice Inspector ASME American Society of Mechanical Engineers ASNT American Society for Nondestructive Testing ASTM American Society for Testing and Materials BC Branch Connection CCSS Centrifugally Cast Stainless Steel CCW Component Cooling Water CE Combustion Engineering CH Closure Head CR Condition Report CS Containment Spray CVCS Chemical and Volume Control System DS Downstream ET Eddy Current Examination EVAL Evaluation FAC Flow-Accelerated Corrosion (may also be referred to as"erosion/corrosion") FB Flange Bolting FNF FAC Notification Report FW Feedwater System FSAR VEGP Final Safety Analysis Report (includes updates thereto)GEO Geometric Indications GPC Georgia Power Company HHSI High Head Safety Injection HL Hanger Lug HX Heat Exchanger HYD Hydraulic Snubber IEN NRC Information Notice (may also be shown as "IN" followed by unique no. denoting notice number)IND Indication INF Indication Notification Form ISI Inservice Inspection IST Inservice Testing ITS VEGP Improved Technical Specification ID Inside Diameter IR Inside Radius LB Large Bore LD Longitudinal Seam Weld Extending Downstream LD-I Longitudinal Seam Weld Downstream Inside Radius of Elbow LD-O Longitudinal Seam Weld Downstream Outside Radius of Elbow LMT Lambert, MacGill and Thomas LU Longitudinal Seam Weld Extending Upstream LU-I Longitudinal Seam Weld Upstream Inside Radius of Elbow LU-O Longitudinal Seam Weld Upstream Outside Radius of Elbow MECH Mechanical Snubber MS Main Steam System MT Magnetic Particle Examination NCI Nonconformance Item NDE Nondestructive Examination 1-2 LIST OF ABBREVIATIONS -(continued) NI No Indication NRC United States Nuclear Regulatory Commission NRC-B NRC Bulletin (followed by unique no. denoting Bulletin number)NRI No Recordable Indication NSCW Nuclear Service Cooling Water System OR Outside Radius PL Pipe Lug PM Paul-Munroe ENERTECH PR Pipe Restraint PROF Profile PS Pipe Support PSA Pacific Scientific PSI Preservice Inspection PT Liquid Penetrant Examination RCS Reactor Coolant System RCP Reactor Coolant Pump RHR Residual Heat Removal System RI Recordable Indication RLW Refracted Longitudinal Wave RL Restraint Lug RPV Reactor Pressure Vessel RR Relief Request (followed by unique no. denoting relief request number)RWST Refueling Water Storage Tank SAT Satisfactory Examination Results SB Small Bore SCS Southern Company Services SI Safety Injection System SNC Southern Nuclear Operating Company SUP Supplemental Data T&C Thickness and Contour TDAFW Turbine Driven Auxiliary Feedwater (Pump)UNSAT Unsatisfactory Examination Results US Upstream UT Ultrasonic Examination VEGP Vogtle Electric Generating Plant (common unless followed by "-1" or "-2" to designate a specific plant unit)VT Visual Examination W Westinghouse 1-3 TAB B ASME FORM NIS-1 AND ABSTRACT* Form NIS-1* Abstract FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules 3"3 Interval 1. Owner: Georgia Power Company, 241 Ralph McGill Blvd., N. E.P. 0. Box 4545, Atlanta, Georgia 30308-3374

2. Plant: Vogtle Electric Generating Plant, 7821 River Road P. 0. Box 1600, Waynesboro, Georgia 30830 3.Plant Unit: One 4. Owner Certification of Authorization:

N/A 5. Commercial Service Date: 05/31/87 6. National Board Number for Unit: N/A 7. Components Inspected: Component or Manufacturer or Manufacturer or Installer State or National Board Appurtenance Installer and Serial Number Province Number Address Number Reactor Combustion Eng. 7372 N/A 22004 Pressure Inc., Vessel Chattanooga, TN Steam Westinghouse GAGT 1881, GAGT 1882, N/A NA Generators 1 Elec., GAGT 1883, GAGT 1884, thru 4 Pensacola, FL Residual Heat Ingersoll-Rand 087728 N/A 510 Removal Co., Phillipsburg, Pump, Train NJ"A" Centrifugal Pacific Pumps 52233 N/A 410 Charging Division, Pump, Train Huntington Park,"A" CA Selected Pullman Power System Numbers 1201, N/A N/A Piping, Products, 1204, 1205, 1208.Components, Williamsport, PA and Supports 2-1 FORM NIS-1 (Back)3'd Interval 8. Examination Dates: October 27, 2006 to April 22. 2008 9. Inspection Period Identification: First Period 10. Inspection interval Identification: Third Inspection Interval 11. Applicable Edition of Section XI 2001 Addenda 2003 12. Date/Revision of Inspection Plan: July 21. 2008 / Version 2.0 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. (See Abstract and Examination Summary Listings)14. Abstract of Results of Examinations and Tests. (See Abstract)15. Abstract of Corrective Measures. (See Abstract)We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Pian as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section Xl.Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date: 2-3 J-ý 20 08 Signed: Southern Nuclear By:l ~Operatingq Company, Inc.for a a Georgia Power Company Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Georgia and employed by The Hartford Steam Boiler Insoection and Insurance Company of Connecticut of Hartford, CT have inspected the components described in this Owner's Report during the period October 27, 2006 to April 24. 2008, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report.Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commission: 6-A .Ingpector's ignature National Board, State, Province, and Endorsements Date: fT7LY , ,2 20 cir 2-2 FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules 2 nd Interval Credit 1. Owner: Georgia Power Company, 241 Ralph McGill Blvd., N. E.P. 0. Box 4545, Atlanta, Georgia 30308-3374

2. Plant: Vogtle Electric Generating Plant, 7821 River Road P. 0. Box 1600, Waynesboro, Georgia 30830 3. Plant Unit: One 4. Owner Certification of Authorization:

N/A 5. Commercial Service Date: 05/31/87 6. National Board Number for Unit: N/A 7. Components Inspected: Component or Manufacturer or Manufacturer or Installer State or National Board Appurtenance Installer and Serial Number Province Number Address Number Reactor Combustion Eng. 7372 N/A 22004 Pressure Inc., Vessel Chattanooga, TN Steam Westinghouse GAGT 1881, GAGT 1882, N/A NA Generators 1 Elec., GAGT 1883, GAGT 1884, thru 4 Pensacola, FL Residual Heat Ingersoll-Rand 087728 N/A 510 Removal Co., Phillipsburg, Pump, Train NJ"A" Centrifugal Pacific Pumps 52233 N/A 410 Charging Division, Pump, Train Huntington Park,"A" CA Selected Pullman Power System Numbers 1201, N/A N/A Piping, Products, 1204, 1205, 1208.Components, Williamsport, PA and Supports 2-3 FORM NIS-I (Back)2n Interval Credit 8. Examination Dates: October 27, 2006 to April 22. 2008 9. Inspection Period ldentification: Third Period Credit 10. Inspection Interval Identification: Second Inspection Interval Credit 11. Applicable Edition of Section XI 1989 Addenda N/A 12. Date/Revision of Inspection Plan: May 29, 2007 / Version 1.0 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. (See Abstract and Examination Summary Listings)14. Abstract of Results of Examinations and Tests. (See Abstract)15. Abstract of Corrective Measures. (See Abstract)We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code, Section Xl, and c) corrective measures taken conform to the rules of the ASME Code, Section XI.Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date: JJ 20 Signed: Southern Nuclear By: Operating Company, Inc.for Z Georgia Power Company liat Owner CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Georgia and employed by The Hartford Steam Boiler Inspection and Insurance Company of Connecticut of Hartford, CT have inspected the components described in this Owner's Report during the period October 27, 2006 to Aprl 24, 2008, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required of the ASME Code, Section X1.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report.Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commission: 6A 7e&Irrspecto b National Board, State, Province, and Endorsements Date: 0ZPLr ai 3 20-&2-4 ABSTRACT -ASME CLASS 1 AND 2 Introduction/Status The ASME Boiler and Pressure Vessel Code, Section XI, 2001 Edition (Code), with the 2003 Addenda, is the applicable code for conducting inservice inspection activities during the third ten-year inspection interval at VEGP-1. Examinations and tests required by the Code are scheduled in accordance with"Inspection Program B" as defined in Code paragraphs IWB-2412 and IWC-2412. This "Owner's Report for Inservice Inspection" is for those third inspection period examinations and tests which were performed between October 27, 2006 (date of last examination performed during 1R13) and April 24, 2008 (end of 1R14 maintenance/refueling outage).VEGP has implemented ASME Section XI, Appendix VIII, "Performance Demonstration for Ultrasonic Examination Systems," as required by 1 OCFR 50.55a, amended by the Federal Register Notices 64 FR 51370 dated September 22, 1999, as later modified by 69 FR58804, dated October 1, 2004. The initial Rule specified the 1995 Edition with Addenda through 1996 as the applicable edition of ASME Section XI, Appendix VIII. The 2004 Rule incorporated the 2001 Edition with NRC caveats. VEGP has, except where requests for relief, technical alternatives or exemptions have been approved, complied with the requirements for expedited implementation of the applicable Appendix VIII supplements using the EPRI Performance Demonstration Initiative (PDI).In addition to the summary of inservice inspection activities, this report addresses Code-applicable repairs and replacements documented at VEGP-1 since 1R13 through the end of 1R14. Class 1 and Class 2 Owner's Reports for Repairs or Replacements (Form NIS-2) are provided herein.It should be noted that Authorized Nuclear Inservice Inspector (ANII) inspection services were provided for those examinations and tests required by the Code. ASME Section XI examinations and tests are itemized in the applicable sections by reference to Examination Category. Examinations which do not meet the Code-required coverage either reference request(s) for relief or indicate that additional relief is required.Class 1 Examinations Selected Class 1 components were examined by Southern Nuclear Operating Company (SNC) personnel utilizing ultrasonic testing (UT), magnetic particle testing (MT), liquid penetrant (PT), and visual testing (VT) methods, as applicable. Specific components and examination areas are itemized in the applicable portions of this document.* During the scope of VEGP-1 examinations conducted, no Class 1 components were observed to have UT, PT or MT reportable indications. Six (6) Class 1 piping welds had limited volumetric coverage during UT examinations because of physical limitations due to the geometric configuration of the welded areas. More than ninety percent (90%) of the required volume must be examined as addressed in ASME Section XI Code Case N-460 for adequate ASME Section XI Code-required examination coverage to be attained. As noted herein, the subject code case has been approved by the NRC for use as documented in NRC Regulatory Guide 1.147. It is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the welded areas. These limited examinations will be submitted to the NRC through the relief request process as allowed by 10 CFR 50.55a.2-5 Class 1 Pressure Test This summary report documents the pressure test performed for completion of Second Ten Year Interval requirements for a system hydrostatic test (IWB-5222) as required the 1989 Edition of Section Xl. This summary report also documents the system leakage test performed at the end of the refueling/maintenance outage for the current interval which is the Third Ten Year Interval. The applicable code for the Third Ten Year Interval is the 2001 Edition with Addenda through 2003.For the Second Ten Year Interval, Table IWB-2500-1, Examination Category B-P, of the 1989 Edition of Section Xl requires the performance of a system hydrostatic test (IWB-5222) once at or near the end of each inspection interval. This test is identified as the Class 1 hydrostatic test (HT-1) and it extends to the Class 1 pressure boundary extremity (i.e., second isolation valve) and also includes selected adjacent Class 2 components which are typically isolated from the Class 1 boundary by check valves. As an alternative to ASME Section XI requirements, Code Case N-498-4, which was conditionally accepted for use in Revision 14 of Regulatory Guide 1.147 dated August 2005, was used. Code Case N-498-4 deleted the elevated pressure requirement for the hydrostatic test and reduced the holding time requirement but retained the requirement to extend the boundary subject to test pressurization to include each of the Class 1 pressure-retaining components. To assure that all Class 1 pressure retaining components and selected adjacent Class 2 pressure retaining components are pressurized requires, for some isolated boundaries, that valves be aligned to positions other than their normal alignment and, in some cases, requires the use of a hydrostatic test pump for isolated boundaries. Portions of this test were not completed during the 1 R1 3 maintenance / refueling outage, which was the last maintenance/refueling outage of the Second Ten Year Interval. However, as allowed by IWB-2412, the remaining portions were performed in maintenance / refueling outage 1 R1 4, which was the first maintenance/refueling outage of the Third Ten Year Interval.For the Third Ten Year Interval, Table IWB-2500-1, Examination Category B-P of the 2001 Edition with Addenda through 2003 of ASME Section XI requires the performance of a system leakage test (IWB-5221) each maintenance/refueling outage. This system leakage test (LT-1) was performed prior to plant startup following the refueling outage. These visual examinations revealed minor leakage and boron residue at mechanical connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation. Class 2 Examinations Selected Class 2 Piping welds were examined utilizing UT and PT. Specific components and examination areas are itemized in the applicable portions of this report document.* During the scope of VEGP-1 examinations conducted, no Class 2 components were observed to have reportable indications. Two (2) class 2 piping welds had limited volumetric coverage during UT examinations because of physical limitations due to the geometric configuration of the welded areas. As with the Class 1 examinations, it is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the welded areas. These limited examinations will be submitted to the NRC through the relief request process as allowed by 10 CFR 50.55a.2-6 Class 2 Pressure Tests This summary report documents the system pressure tests performed for completion of the Second Ten Year Interval requirements per the 1989 Edition of Section XI. This summary report also documents the system leakage tests performed for the current interval which is the Third Ten Year Interval. The applicable code for the Third Ten Year Interval is the 2001 Edition with Addenda through 2003.For the Second Ten Year Interval, Table IWC-2500-1, Examination Category C-H, of the 1989 Edition of Section X1 requires system pressure testing. Some of the system pressure tests for the Second Ten Year Interval were not completed during the 1 R1 3 maintenance / refueling outage which was the last maintenance/refueling outage of the Second Ten Year Interval. However, as allowed by IWA-2430, the remaining portions were performed in maintenance / refueling outage 1 R1 4, which was the first maintenance / refueling outage of the Third Ten Year Interval. The specific system pressure tests performed are itemized in the "Pressure Tests" portion of this report document. The visual examinations performed during these system pressure tests found only minor leakage or residue at mechanical joints such as valve stem packing and at flanged connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation. For the Third Ten Year Interval, Table IWC-2500-1, Examination Category C-H of the 2001 Edition with Addenda through 2003 of ASME Section XI requires system leakage tests. The specific system pressure tests performed are itemized in the "Pressure Tests" portion of this report document. The visual examinations performed during these system pressure tests found only minor leakage or residue at mechanical joints, such as valve stem packing and at flanged connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation. Class MC Containment Examinations and Tests (IWE)During the VEGP-1 Spring 2008 maintenance/refueling outage, VT-3 and VT-1 examinations were performed on Class MC Pressure retaining components with their integral attachments and metallic shell and penetration liners of Class CC pressure retaining components with their integral attachments. These examinations were performed in response to the NRC rulemaking to 10 CFR 50.55a that invoked the requirements of Subsections IWE of the 1992 Edition of ASME Section Xl with 1992 Addenda and were performed using VEGP procedure 85053-C, "Visual Examinations for ASME Xl Subsection IWE and IWL and General Visual Examinations". Per procedure 85053-C, the VEGP-1 components were examined for deviations or departures from their normal or common order, form, and rule, with evidence of degradation that may affect either the containment structural integrity or leak tightness. Personnel performing the examinations were qualified in accordance with VEGP procedure NMP-ES-024-100, "Qualification and Certification of Nondestructive Examination and Testing Personnel". Optical aids such as flashlights, mirrors and binoculars were used when performing the examinations that included both direct and remote visual examination methods.Cateaory E-A, Containment Surfaces A VT-3 examination of 100% of the accessible portions of the containment surfaces was performed and documented under Surveillance

  1. 84303-101-1070868801.

All anomalies consisted of surface rust, scratches, discolorations, etc. and were dispositioned as "hardware not affected" since the liner plate's minimum design thickness was maintained at all anomaly locations. The acceptance criteria used to disposition the recorded anomalies was provided in SCS letters SG-1 8218 dated February 28, 2001 and SG-17755 dated September 19, 2000.2-7 Category E-B, Pressure-Retaining Welds The rulemaking (10 CFR 50.55a(b)(2)(ix)(C)) contains a modification that makes examinations of Subsection IWE, Category E-B optional. SNC has chosen to not examine category E-B welds at VEGP.Category E-C, Containment Surfaces Requiring Augmented Examination Identified surface areas likely to experience accelerated degradation and aging require the performance of augmented examinations as defined in Examination Category E-C. There are no existing areas in VEGP-1 requiring Category E-C examination. Category E-D, Seals, Gaskets, and Moisture Barriers A VT-3 examination of 100% of the moisture barrier was performed under Surveillance

  1. 85053-102-1070869101 in which four anomalies were found at the liner plate to moisture barrier interface.

The moisture barrier was removed at the four anomaly locations per MWO 1080525801, and a VT-3 exam was performed on the exposed liner plate per Surveillance

  1. 85053-102-1080604601 (IR# 41568 and IR#41569). All anomalies were dispositioned as "hardware not affected" since the liner plate's minimum design thickness was maintained.

The anomalies were recoated and the moisture barrier was then restored per MWO 1080525801. A satisfactory VT-3 examination was performed per 85053-102-1080604601 (IR# 41601) on the restored moisture barrier.SNC has chosen to implement Request for Relief (RR-E-1) to allow leak tightness of seals and gaskets to be verified by 10 CFR 50, Appendix J Type B testing (LLRT). The NRC approved SNC's use of RR-E-1 in its June 16, 2000 letter to SNC (TAC Nos. MA5314 and MA5315). The Type B test results, along with the Type C test results, are available at the plant site for review upon request in accordance with 10 CFR 50 Appendix J Option B.Category E-F, Pressure-Retaining Dissimilar Metal Welds The rulemaking (10 CFR 50.55a(b)(2)(ix)(C)) contains a modification that makes examinations of Subsection IWE, Category E-F optional. SNC has chosen to not examine category E-F welds at VEGP.Category E-G, Pressure-Retaining Bolting The following VT-1 examinations of the accessible containment pressure-retaining bolting necessary to achieve the 100% required during the interval were performed with no anomalies found as documented on Surveillance

  1. 85053-101-1070869001.

11818H3P01 11818H3P13 11818H3P25 11818H3P40 11818H3P58 11818H3P02 11818H3P14 11818H3P26 11818H3P41 11818H3P59 11818H3P03 11818H3P15 11818H3P27 11818H3P42 11818H3P60 11818H3P04 11818H3P16 11818H3P28 11818H3P43 11818H3P61 11818H3P05 11818H3P17 11818H3P29 11818H3P44 11818H3P62 11818H3P06 11818H3P18 11818H3P30 11818H3P51 11818H3P63 11818H3P07 11818H3P19 11818H3P31 11818H3P52 11818H3P64 11818H3P08 11818H3P20 11818H3P32 11818H3P53 11818H3P65 11818H3P09 11818H3P21 11818H3P33 11818H3P54 12101R2014 11818H3P10 11818H3P22 11818H3P34 11818H3P55 12101R2015 11818H3P11 11818H3P23 21818H3P38 11818H3P56 11818H3P12 11818H3P24 11818H3P39 11818H3P57 A VT-1 examination was also performed on outage penetration 55-M under MWO# 1070814601 since it was disassembled. No anomalies were found.2-8 CLASS CC Containment Examinations (IWL)None performed in 1R14 Status of Examinations Required for the current Interval This 1R14 Outage was the 1 st Outage, 1 st Period of the 3f dInterval. The results from this outage, combined with the "scheduled" examinations for the next refueling outage (1 R1 5, Fall 2009) will represent 100% of the total Class 1 and 2 scope for the current period and interval. VEGP Unit 1 is within ASME Code compliance, pending NRC approval of the volumetric and/or surface examination limitations. Requests for relief will be submitted within the required time frame specified by 10 CFR 50.55a.2-9 TAB C INSERVICE INSPECTION EXAMINATION (OWNER'S REPORT)

SUMMARY

CLASS 1 AND 2 WELDS AND SUPPORT EXAMINATIONS <yogtle Unit 1- Examination SummaryGass1 and 2 hComponents) ASME. , ExaminationlAre-a iExamination -Exam/Cal Sheet Results, Remarks,:Section.Xl -. ; Procedure.,. No(s)." B-D 11201 -B6-002-IR-01 NMP-ES-024-513 S08V1 U028, 029 NRI N/A B3.140 INLET NOZZLE INNER RADIUS & 030 B-D 11201-B6-002-IR-02 NMP-ES-024-513 S08V1U031, 032 NRI N/A B3.140 OUTLET NOZZLE INNER RADIUS & 033 C-A 11201-B6-001-WOI NMP-ES-024-516 S08V1U053, 054, UT RI UT RI -ASME C1.20 UPPER HEAD TO UPPER SHELL BARREL '0' WELD 055 & 056 Code Acceptable C-B 11201-B6-001-W18 NMP-ES-024-401 SO8V1M001, NRI N/A C2.21 32" STEAM OUTLET NOZZLE TO UPPER HEAD WELD NMP-ES-024-516 U057, 058 & 059 C-C 11204-006-51 NMP-ES-024-301 SO8V1P003 NRI N/A C3.20 SUPPORT H006 C-C 11204-007-5 NMP-ES-024-301 SO8V1P007 NRI N/A C3.20 SUPPORT H003 C-C 11205-003-41 NMP-ES-024-301 S08VIP002 NRI N/A C3.20 SUPPORT H019 C-C 11205-007-70 NMP-ES-024-301 SO8V1P004 NRI N/A C3.20 SUPPORT H032 C-C 11205-007-74 NMP-ES-024-301 SO8V1P005 NRI N/A C3.20 SUPPORT H033 C-C 11205-P6-001-WOI NMP-ES-024-301 SO8V1P001 NRI N/A C3.30 INTEGRALLY WELDED SUPPORT ATTACHMENT C-C 11208-P6-002-W03 NMP-ES-024-301 S08V1P006 NRI N/A C3.30 INTEGRALLY WELDED PUMP SUPPORT BRACKET R-A 11201-005-8-RI NMP-ES-024-506 S08V1U042 & 043 NRI UT -Limited exam (58%)R1.11 31" ELBOW TO NOZZLE due to nozzle config.Relief Required R-A 11201-006-1-RI NMP-ES-024-506 S08V1U026 & 027 NRI UT- Limited exam (31%)31" NOZZLE TO ELBOW due to nozzle config.Relief Required R-A 11201-029-1-RI NMP-ES-024-501 S08V1U066 & 067 NRI N/A R1.11 4" BRANCH CONNECTION TO PIPE R-A 11201-053-4-RI NMP-ES-024-501 S08V1U044 & 045 NRI N/A R1.11C 16" PIPE TO REDUCER R-A 11201-053-5-RI NMP-ES-024-501 S08V1 U046 & 047 NRI N/A R1.11C 14" REDUCER TO PIPE 3-1 Vogtle Unit l- Examination Summary (Class I and 2 C6mponents) ASME' " ExaminationlArea f Examination , Exam/Cal Sheet Results'-' Remarksi'-Sectio XI iK~' ~'<~ .-Procedure(s) No(s): ..-R-A 11204-001-9-RI NMP-ES-024-501 S08V1 U001 & 002 NRI UT -Limited exam (50%)R1.11 12" PIPE TO VALVE (Al 87-0131) due to valve config.Relief Required R-A 11204-023-21-RI NMP-ES-024-501 S08V1 U060, 061 NRI UT -Limited exam (50%)R1.11 6" PIPE TO TEE (Al87-0131) & 002 due to tee config.Relief Required R-A 11204-039-1-RI NMP-ES-024-501 S08V1 U068 & 069 NRI UT -Limited exam (50%)R1.11 8" VALVE TO PIPE (Al 87-0131) due to valve config.Relief Required R-A 11204-076-2-RI NMP-ES-024-501 S08V1U005 & 006 RI UT RI -Geometry.R1.11 3" PIPE TO ELBOW R-A 11204-076-42-RI NMP-ES-024-501 S08V1U007 & 008 NRI UT -Limited exam (50%)R1.11 1.5" PIPE TO FLANGE (Al 87-0131) due to flange config.Relief Required R-A 11204-077-9 B-RI NMP-ES-024-501 S08VIU009, 010 NRI N/A R1.11 1.5" ELBOW TO PIPE & 034 R-A 11204-078-10-RI NMP-ES-024-501 S08V1 U01 1, 012 NRI UT -Limited exam (62%)R1.11 1.5" PIPE TO ELBOW & 013 due to support interference. Relief Required R-A 11204-079-10-RI NMP-ES-024-501 SO8V1U014, 015 NRI N/A R1.11 1.5" PIPE TO ELBOW & 016 R-A 11204-243-34-RI NMP-ES-024-501 S08V1 U051 & 052 NRI N/A R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11204-244-28-RI NMP-ES-024-501 S08V1U017 & 018 NRI N/A -R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11204-245-33-RI NMP-ES-024-501 S08V1U024 & 025 NRI N/A R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11204-246-36-RI NMP-ES-024-501 S08V1U040 & 041 NRI N/A R1.11 3" REDUCER TO BRANCH CONNECTION R-A 11205-010-7-RI NMP-ES-024-501 S08V1 U003 & 004 NRI N/A R1.11 12" PIPE TO ELBOW (Al 87-0131)R-A 11208-009-6-RI NMP-ES-024-501 S08VIU063 & 065 NRI N/A R1.11 3" PIPE TO BRANCH CONNECTION 3-2 .........,. ... --. ......... 0g~ unit~l Exam at Sum m ar ( u p rsy,. .,. ..-oi6U~ 1, Etxamination"Smay qS ASME Examinat'ion/Airea ~.~ 7 Examination Exam/Cal Sheet ReutRmakýSection XI, (Sort) -1 Procedure(s) No(s)..F-A 11201-030-H023 NMP-ES-024-203 S08VIV159 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H035 NMP-ES-024-203 S08V1V054 Sat N/A Fl.10S MECH SNUBBER F-A 11201-030-H036 NMP-ES-024-203 S08V1V080 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H037 NMP-ES-024-203 S08V1V084 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H039 NMP-ES-024-203 S08V1V085 Sat N/A F1.10 RIGID STRUT F-A 11201-030-H040 NMP-ES-024-203 S08V1V086 Sat N/A F1.10 LIN RESTRAINT F-A 11201-030-H041 NMP-ES-024-203 S08V1V079 Sat N/A F1.10 CON SPRING F-A 11201-030-H042 NMP-ES-024-203 S08V1V053 Sat N/A FI.10S MECH SNUBBER F-A 11201-030-H043 NMP-ES-024-203 S08V1V087 Sat N/A F1.10 RIGID STRUT F-A 11201-059-H003 NMP-ES-024-203 S08V1V088 Sat N/A F1.10 LIN RESTRAINT F-A 11201-059-H005 NMP-ES-024-203 S08V1V089 Sat N/A F1.10 LIN RESTRAINT F-A 11202-001-H003 NMP-ES-024-203 S08V1V093 Sat N/A F1.20 RIGID STRUT F-A 11202-001-H004 NMP-ES-024-203 S08V1V095 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H006 NMP-ES-024-203 S08V1V096 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H008 NMP-ES-024-203 S08V1V097 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H012 NMP-ES-024-203 S08V1V098 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H021 NMP-ES-024-203 S08V1V099 Sat N/A F1.20 LIN RACK 2-D F-A 11202-001-H024 NMP-ES-024-203 S08VlV100 Sat N/A F1.20 LIN RESTRAINT IIIII 3-3 ~ ~ ~ ~ ~~~- #, .'. uniit,! Exami-ýnation Summary (S6`i r "{ q ..Ui -Examination Exmmr~ASME CExaminationlAre'a ExaInato ~Eam/Cal Sheet Resuilts -Remarks,,' ',Section X(Sr)Poeue) .No(s).2 F-A 11202-001-H025 NMP-ES-024-203 S08V1V11 Sat N/A F1.20 LIN RESTRAINT F-A 11202-001-H602 NMP-ES-024-203 S08V1V094 Sat N/A F1.20 RIGID STRUT F-A 11202-196-H003 NMP-ES-024-203 S08V1V105 Sat N/A F1.20 RIGID STRUT F-A 11202-196-H005 NMP-ES-024-203 S08V1V106 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H007 NMP-ES-024-203 S08V1V107 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-HO10 NMP-ES-024-203 S08V1V108 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H012 NMP-ES-024-203 S08V1V1O9 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H014 NMP-ES-024-203 S08V1V110 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H016 NMP-ES-024-203 SO8VIVIl Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H020 NMP-ES-024-203 S08V1V112 Sat N/A F1.20 LIN RESTRAINT F-A 11202-196-H602 NMP-ES-024-203 S08V1V113 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H001 NMP-ES-024-203 S08V1V102 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H002 NMP-ES-024-203 S08V1V166 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H003 NMP-ES-024-203 S08V1V167 Sat N/A F1.20 LIN RACK 1-D F-A 11202-197-H004 NMP-ES-024-203 S08V1V165 Sat N/A F1.20 LIN RESTRAINT F-A 11202-197-H603 NMP-ES-024-203 S08V1V165 Sat N/A F1.20 RIGID STRUT F-A 11202-197-H604 NMP-ES-024-203 S08VIV168 Sat N/A F1.20 LIN RESTRAINT F-A 11202-223-H002 NMP-ES-024-203 S08V1V141 Sat N/A F1.20 RIGID STRUT 3-4 Vogtle Unit 1 -ý Examinaton Summary (Supports) ýASME ~ 'Exam ination/Area Exaimi'nation-> Exam/Cal Sheet R ASMEc ' .. ....EJ Sti ea -Exa iati xa l S.Results

, Remarks : F-A 11202-223-H004 NMP-ES-024-203 S08V1V142 Sat N/A F1.20 LIN RESTRAINT F-A 11202-223-H010 NMP-ES-024-203 S08V1V143 Sat N/A F1.20 RIGID STRUT F-A 11204-006-H006 NMP-ES-024-203 S08V1V025 Sat N/A F1.20 LIN RACK 2-D F-A 11204-006-H013 NMP-ES-024-203 S08VlV172 Sat N/A F1.20 LIN RESTRAINT F-A 11204-006-H027 NMP-ES-024-203 S08V1V173 Sat N/A F1.20 VAR SPRING F-A 11204-007-H001 NMP-ES-024-203 S08V1VO19 Sat N/A F1.20 LIN RACK 1-D F-A 11204-007-H003 NMP-ES-024-203 S08V1V162 Sat N/A F1.20 LIN RACK 3-D F-A 11204-007-H006 NMP-ES-024-203 S08V1V163 Sat N/A F1.20 LIN RESTRAINT F-A 11204-007-H008 NMP-ES-024-203 S08VlVO18 Sat N/A F1.20 RIGID STRUT F-A 11204-008-H004 NMP-ES-024-203 S08V1V050 Sat N/A F1.20 LIN RESTRAINT F-A 11204-008-HO10 NMP-ES-024-203 S08V1V049 Sat N/A F1.20 LIN RESTRAINT F-A 11204-008-HO0l NMP-ES-024-203 S08VlVO51 Sat N/A F1.20 RIGID STRUT F-A 11204-021-H002 NMP-ES-024-203 S08VlV122

& 175 Unsat Loose jam nut. Acceptable "as-is".F1.10 RIGID STRUT Sat MWO generated to address.F-A 11204-021-H008 NMP-ES-024-203 S08V1V157 Sat N/A F1.10 RIGID STRUT F-A 11204-021-H012 NMP-ES-024-203 S08V1V158 Sat N/A F1.10 RIGID STRUT F-A 11204-021-H014 NMP-ES-024-203 S08VIV137 Sat N/A F1.10S MECH SNUBBER F-A 11204-021-H015 NMP-ES-024-203 S08V1V005 Sat N/A F1.10 RIGID STRUT F-A 11204-021-H021 NMP-ES-024-203 S08V1V138 Sat N/A F1.1S MECH SNUBBER III 3-5 VogtleUnt E m Into Summary (Supports),U >0 ASMEo. ExaminationlArea .,Examination Exam/Cal Sheet Results Remarks ,'Section Xl( Procedure(s) No(s).F-A 11204-021-H022 NMP-ES-024-203 S08V1V139 Sat N/A FI.10S MECH SNUBBER F-A 11204-038-H601 NMP-ES-024-203 S08V1V152 Sat N/A F1.20 LIN RESTRAINT F-A 11204-057-H001 NMP-ES-024-203 S08V1V026 Sat N/A F1.20 LIN RESTRAINT F-A 11204-057-H007 NMP-ES-024-203 S08V1V027 Sat N/A F1.20 ANCHOR F-A 11204-057-H012 NMP-ES-024-203 S08V1V028 Sat N/A F1.20 LIN RESTRAINT F-A 11204-057-H024 NMP-ES-024-203 S08V1V048 Sat N/A F1.20 LIN RACK 2-D F-A 11204-057-H032 NMP-ES-024-203 S08V1V029 Sat N/A F1.20 LIN RESTRAINT F-A 11204-076-H011 NMP-ES-024-203 S08V1V114 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H012 NMP-ES-024-203 S08V1V115 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H013 NMP-ES-024-203 S08V1V116 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H015 NMP-ES-024-203 S08V1V117 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H022 NMP-ES-024-203 S08V1V116 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H023 NMP-ES-024-203 S08V1V119 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H025 NMP-ES-024-203 S08V1V120 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H026 NMP-ES-024-203 S08V1V121 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H028 NMP-ES-024-203 S08V1V122 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H030 NMP-ES-024-203 S08V1V123 Sat N/A Fi11 LIN RESTRAINT F-A 11204-076-H031 NMP-ES-024-203 S08V1V154 Sat N/A F1.10 LIN RESTRAINT 3-6 Vogle) Unhit 1 -~ Examination SummaryJM(upprs >s ASME -ExaminationiArea' Examination ExamICal Sheet -R Remarks Sec-, tion'XI (sort). >Proceclure(s) .,, No(s)F-A 11204-076-H034 NMP-ES-024-203 S08V1V124 Sat N/A F1.10 LIN RESTRAINT F-A 11204-076-H036 NMP-ES-024-203 S08V1V125 Sat N/A FI.10 LIN RESTRAINT F-A 11204-076-H038 NMP-ES-024-203 S08V1V126 Sat N/A F1.10 LIN RESTRAINT F-A 11205-003-H005 NMP-ES-024-203 S08V1V071 Sat N/A F1.20 LIN RESTRAINT F-A 11205-003-H019 NMP-ES-024-203 S08V1V030 Sat N/A F1.20 LIN RESTRAINT F-A 11205-003-H027 NMP-ES-024-203 S08V1V031 Sat N/A F1.20 RIGID STRUT F-A 11205-005-H004 NMP-ES-024-203 S08V1V078 Sat N/A F1.20 VAR SPRING F-A 11205-005-H013 NMP-ES-024-203 S08V1V073 Sat N/A F1.20 LIN RESTRAINT F-A 11205-007-H012 NMP-ES-024-203 S08V1V032 Sat N/A F1.20 RIGID STRUT F-A 11205-007-H032 NMP-ES-024-203 S08V1V075 Sat N/A F1.20 LIN RESTRAINT F-A 11205-007-H033 NMP-ES-024-203 S08V1V076 Sat N/A F1.20 LIN RESTRAINT F-A I 1205-007-H037 NMP-ES-024-203 S08V1V033 Sat N/A F1.20 LIN RESTRAINT F-A 11205-007-H041 NMP-ES-024-203 S08V1V072 Sat N/A F1.20 VAR SPRING F-A 11205-007-H060 NMP-ES-024-203 S08V1V058 Sat N/A F1.20 LIN RACK 2-D F-A 11205-007-H061 NMP-ES-024-203 S08V1V057 Sat N/A F1.20 RIGID STRUT F-A 11206-0011-012 NMP-ES-024-203 S08V1V017 Sat N/A F1.20 VAR SPRING F-A 11206-001-H018 NMP-ES-024-203 S08V1V024 Sat N/A F1.20 LIN RESTRAINT F-A 11206-001-H022 NMP-ES-024-203 S08V1V023 Sat N/A F1.20 LIN RESTRAINT 3-7 -.. Vogtle Unitl I -ExaminationriSumma-ry (Supports)"ASME ExmntolýaExaminaktioný-' Exam/Cal SheetRsut Se'c'tion X I ~(oit) P ,o Pce dudr e(s) No(s). Veak F-A 11206-001-H024 NMP-ES-024-203 S08V1V022 Sat N/A F1.20 LIN RESTRAINT F-A 11206-003-H001 NMP-ES-024-203 S08V1V014 Sat N/A F1.20 LIN RESTRAINT F-A 11206-003-H005 NMP-ES-024-203 S08V1V015 Sat N/A F1.20 VAR SPRING F-A 11206-005-H013 NMP-ES-024-203 S08V1V021 Sat N/A F1.20 LIN RESTRAINT F-A 11206-005-H019 NMP-ES-024-203 S08V1V020 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H014 NMP-ES-024-203 S08V1V034 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H018 NMP-ES-024-203 S08VlV035 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H045 NMP-ES-024-203 S08VlV153 Sat N/A F1.20 LIN RESTRAINT F-A 11208-003-H050 NMP-ES-024-203 S08VlV055 Sat N/A F1.20 LIN RESTRAINT F-A 11208-007-H001 NMP-ES-024-203 S08VIV160 Sat N/A F1.10 LIN RESTRAINT F-A 11208-099-H009 NMP-ES-024-203 S08VlV068 Sat N/A F1.20 LIN RACK 3-D 'F-A 11208-137-H603 NMP-ES-024-203 S08VlV082 Sat N/A F1.20 LIN RESTRAINT F-A 11208-141-H002 NMP-ES-024-203 S08V1V069 Sat N/A F1.20 LIN RACK 2-D F-A 11208-411-H017 NMP-ES-024-203 S08VlV074 Sat N/A F1.20 LIN RACK 2-D F-A 11301-104-H007 NMP-ES-024-203 S08VlV169 Sat N/A F1.20 VAR SPRING F-A 11302-109-H008 NMP-ES-024-203 S08V1V140 Sat N/A F1.20 RIGID STRUT F-A 11302-109-H012 NMP-ES-024-203 S08V1V103 Sat N/A F1.20S MECH SNUBBER F-A 11302-109-H014 NMP-ES-024-203 S08V1V170 Sat N/A F1.20 VAR SPRING 3-8 TAB D INSERVICE INSPECTION EXAMINATION (OWNER'S REPORT)

SUMMARY

SYSTEM PRESSURE TESTS SYSTEM PRESSURE TESTS The following pressure tests on Class 1 and Class 2 components were performed after the last maintenance/refueling outage (1 R1 3) through the completion of the fourteenth maintenance/refueling outage (1R14). As indicated in the pressure test listings some of these tests are for the Second Ten Year Interval and some are for the Third Ten Year Interval. The pressure tests indicated for the Second Ten Year Interval include system functional and system hydrostatic tests. It should be noted that the hydrostatic tests identified were performed to satisfy the "once per ten year" requirements described in ASME Section XI, Code Case N-498-4. The pressure tests indicated for the Third Ten Year Interval include system functional tests, system inservice tests, and system leakage tests. Boundaries for the pressure tests are described in the VEGP-1 Inservice Inspection Plan -Second 10-Year Interval document. Examination results are discussed in the applicable sections of this report document. The examination data for these pressure tests is available at the plant site for review upon request.System Functional Tests (FTs) for Second Ten Year Interval FT Exam. Test Description Number Cat.14 C-H Turbine Driven Auxiliary Feedwater (TDAFW) Pump 1302-P4-001 Functional Test System Functional Tests (FTs) for Third Ten Year Interval IFT Exam. Test Description Number Cat.1 C-H Reactor Head Vent Functional Test 4 C-H Safety Injection Pump 1204-P6-003 Discharge Functional Test 5 C-H Safety Injection Pump 1204-P6-004 Discharge Functional Test 8 C-H Penetration 30 (SI to Cold Legs) Functional Test 12 C-H Containment Spray Train "A" Functional Test 13 C-H Containment Spray Train "B" Functional Test 17 C-H Line 1208-133 (HV-8104 to Valve 185 Flow Test) Functional Test System Hydrostatic Tests for Second Ten Year Interval (HTs)HT Exam. Test Description Number Cat.1 B-P Class 1 Hydrostatic Test (Partially performed in 1R13 -Test completed in 1R14)C-H 3 C-H SI, Normal Charging & CS Pump Suction Hydrostatic Test 5 C-H RHR Train A Suction Hydrostatic Test 6 C-H RHR Train B Suction Hydrostatic Test 4-1 System Inservice Tests for Third Ten Year Interval (ITs)IT Exam. Test Description Number Cat.1 C-H Charging Line Inside Containment Inservice Test 2 C-H Letdown Line Inside Containment Inservice Test 3 C-H Reactor Coolant (RC) Pumps 1, 2, 3, and 4 Seal Leakoff Inside Containment Inservice Test 4 C-H RC Pump 1 Seal Injection from Penetration 54 to Valve 006 Inservice Test 5 C-H RC Pump 2 Seal Injection from Penetration 53 to Valve 359 Inservice Test 6 C-H RC Pump 3 Seal Injection from Penetration 52 to Valve 360 Inservice Test 7 C-H RC Pump 4 Seal Injection from Penetration 51 to Valve 361 Inservice Test 8 C-H Reactor Coolant System (RCS) Hot Leg Sample Lines to Penetration 24 Inservice Test 9 C-H Sample Line from Valve 101 to Valve HV-3514 Inservice Test 10 C-H CVCS Inservice Test with Normal Charging Pump Operating (Outside Containment) 11 C-H Centrifugal Charging Pump 1208-P6-002 (Train "A") Discharge Inservice Test 12 C-H Centrifugal Charging Pump 1208-P6-003 (Train "B") Discharge Inservice Test 14 C-H Accumulator Tank 1 (1204-V6-002) Inservice Test 15 C-H Accumulator Tank 2 (1204-V6-003) Inservice Test 16 C-H Accumulator Tank 3 (1204-V6-004) Inservice Test 17 C-H Accumulator Tank 4 (1204-V6-005) Inservice Test 23 C-H Refueling Water Storage Tank (RWST) Inservice Test 24 C-H Sample Line from Valve 097 to Valve HV-3508 Inservice Test 25 C-H Penetration 24 Outside Containment Inservice Test (Post-Accident Sampling)26 C-H Nuclear Service Cooling Water (NSCW) Train "A" Inservice Test (Outside Containment) 30 C-H NSCW Train "B" Inservice Test (Outside Containment) 34 C-H Containment Coolers 1501-A7-001 and 1501-A7-002 Inservice Test 35 C-H Containment Coolers 1501-A7-003 and 1501-A7-004 Inservice Test 36 C-H Containment Coolers 1501-A7-005 and 1501-A7-006 Inservice Test 37 C-H Containment Coolers 1501-A7-007 and 1501-A7-008 Inservice Test 38 C-H Cooling Coils 1511-E7-001 and 1515-A7-001 Inservice Test 4-2 IT Exam. Test Description Number Cat.39 C-H Cooling Coils 1511-E7-002 and 1515-A7-002 Inservice Test 45 C-H Steam Generator 1201-B6-001 Inservice Test 46 C-H Steam Generator 1201-B6-002 Inservice Test 47 C-H Steam Generator 1201-B6-003 Inservice Test 48 C-H Steam Generator 1201-B6-004 Inservice Test 49 C-H Penetration 7 Inservice Test (Outside Containment Steam Generator 1 Blowdown to Heat Exchanger) 50 C-H Penetration 8 Inservice Test (Outside Containment Steam Generator 2 Blowdown to Heat Exchanger) 51 C-H Penetration 9 Inservice Test (Outside Containment Steam Generator 3 Blowdown to Heat Exchanger) 52 C-H Penetration 10 Inservice Test (Outside Containment Steam Generator 4 Blowdown to Heat Exchanger) 53 C-H Penetration 11 B Inservice Test (Outside Containment Steam Generator 1 Blowdown to Sample)54 C-H Penetration 11C Inservice Test (Outside Containment Steam Generator 2 Blowdown to Sample)55 C-H Penetration 12B Inservice Test (Outside Containment Steam Generator 3 Blowdown to Sample)56 C-H Penetration 12C Inservice Test (Outside Containment Steam Generator 4 Blowdown to Sample)57 C-H Main Steam Loop 1 Inservice Test (Outside Containment) 58 C-H Main Steam Loop 2 Inservice Test (Outside Containment) 59 C-H Main Steam Loop 3 Inservice Test (Outside Containment) 60 C-H Main Steam Loop 4 Inservice Test (Outside Containment) 71 C-H Main Feedwater Loop 1 Inservice Test (Outside Containment) 72 C-H Main Feedwater Loop 2 Inservice Test (Outside Containment) 73 C-H Main Feedwater Loop 3 Inservice Test (Outside Containment) 74 C-H Main Feedwater Loop 4 Inservice Test (Outside Containment) 79 C-H Excess Letdown Heat Exchanger Inservice Test System Leakage Test Schedule (LT)[LT Exam. Test Description Number Cat.1 B-P Class 1 System Leakage Test 4-3 TAB E INSERVICE INSPECTION EXAMINATION (OWNER'S REPORT)

SUMMARY

REPORTABLE INDICATION

SUMMARY

REPORTABLE INDICATION

SUMMARY

The following indication identified on the Condition Report was issued due to reportable indications or conditions being observed during the examination of either Class 1 or 2 components during the fourteenth (1 4 th) maintenance/refueling outage at VEGP-1 (referenced attachments'are available at the VEGP plant site for review upon request): INF No. Affected

  • INF Disposition (108V1) Component/Area 001 11204-021-H002 Loose "jam" nut.(Rigid Strut) Per the disposition of Condition Report 2008103578, the loose jam nut did not prevent the support from performing its intended function.A Work Order was written to correct the condition.

The Indication Notification Form(s) constitute only those reportable indications or conditions observed during the SNC M & IS Department scope of work. Any reportable indications or conditions observed by VEGP Site personnel or outside contractors during their scope of work should be identified by/to the VEGP Site in report document(s) which are referenced herein.5-1 TAB F OWNER'S REPORT FOR REPAIR AND REPLACEMENTS (ASME FORM NIS-2) OWNER'S REPORTS FOR REPAIRS OR REPLACEMENTS (FORM NIS-2)The following Owner's Reports for Repairs or Replacements (Form NIS-2) are provided for work activities documented at VEGP-1 since the last maintenance/refueling outage (1R13) through the completion of the fourteenth maintenance/refueling outage (1R14). Reports are identified by their respective traveler number which is denoted on each of the NIS-2 reports. The originals of the NIS-2 reports are filed with their respective traveler packages at the plant site. Only those NIS-2 reports applicable to VEGP-1 are included in this report document. Any attachments, e.g., code data reports, etc., referenced in the NIS-2 reports will be made available for review upon request at the plant site. This report includes the outstanding NIS-2s from the end of the Second Inspection Interval which ended May 30, 2007 and those NIS-2s which were performed during the Third Inspection Interval which began on May 30, 2007.The NIS-2s listed below were performed during the Second Inspection Interval for the following travelers which are included herein: 01071**01102**04110 04115**05124 06009 06020 06027 06036 06039 06040 06041 06042 06043 06045 06046 06047 06048 06049**06051 06052**06053 06054 06055 06057**06058 06059 06062 06068 06075 06079 06081**06082 06086**06087 06088 06090 06091 07052 The NIS-2s listed below were performed during the Third Inspection Interval for the following travelers which are included herein: 06094**07138 07145 07147 07148**07149**07150 07152 07153 07154 07156 07158 07159 07160 07161 07162 07163 07164 07165 07166 07167 07168 07169**07170 07171 07172 07180 07181 07183 07187 07195 07197 07203 07205 07206 07209 07221 08009 08010 08011 08012 08013 08014 08020 08034 08035 08036 08037 08038 08039 08040 08041 08042 08043**08044 08045 08046 08047 08050**08054 08055 Traveler 01071 is certified on the same NIS-2 report as traveler 06086.Traveler 01102 is certified on the same NIS-2 report as traveler 06057.Traveler 04115 is certified on the same NIS-2 report as traveler 06049.Traveler 06081 is certified on the same NIS-2 report as traveler 06052.Traveler 06094 is certified on the same NIS-2 report as traveler 07169.Traveler 07149 is certified on the same NIS-2 report as traveler 07148.Traveler 08050 is certified on the same NIS-2 report as traveler 08043.6-1 .. .4 ORIGINAL ASME SECTION XI TRAVELER S 9 SECTION XI REPAIRIREPLACEMENT TRAVELER PAGE 1 OF 3 TRAVELER: 01071 REPAIR I] REPLACEMENT [.... ASSOCIATED DOCUMENTS


------- COMPONENT----I MWO: A0100517 CODE CLASS: ASME III Class 1 DC: N/A TAG NO: A2117SnubberQ DCP: N/A DESCRIPTION Snubber PSA-3 OTHER:

SERIAL NO: 269.%9 S5.1 (4.&l DESCRIPTION: Reolace parts of snubber. I I-------- EXAMINATION / TEST REQUIREMENTS .......N/A VT-1 N/A VT-2. N/A VT-3 OTHER N/A N/A NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement I Z No Normal / Expected Wear E ALARA El DCP L EQ Checklist I L] Yes Justification: Intended life of- if less than design life of repaired item: _REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Operatinq Co.-INITIAL @EVIEW -----6 REPATEHOLD POINTS INITIATOR ...00 1 [] YES ZNO E QUALITY CONTROL & 0 1 YES LJNONE ANII ElYES NONE------FINALR _VIEW ----- olo- -"rl tt I " 0,___________________________________ 1 ORIGINAL ASME SECTION Xl TRAVELER INSTRUCTION SHEET ASME SECTION XI TRAVELER INSTRUCTION SHEET TRAVELER NO: 01071 MWO: A0100517 PAGE 2 OF 3 STEPi -TRAVELER WORK, aiP .I Maint P3 ANII*NO..NO RWO' W/H, 'INIT/DATEK W/l14 1INITiD)ATE,.

1. Ensure the serial number, heat Maint. _,-zjp.olI_

and/or trace code number of the _replacement part(s) is entered on _the MER. Ensure ASME code class _of the replacement part(s) is entered _on the MER. _2. Verify the serial number, heat 0C .and/or code number of the _ _ LC; ______replacement part(s) matches what's _recorded on the MER or the applicable documentation.

3. Verify that the ASME code class for the replacement part(s) matches -' _that of the component or piping in which it is being installed.
4. Install replacement part(s). Maint. t __-_4L 9-___-_ 1
  • -** 6 ORIGINAL ASME SECTION XI BILL OF MATERIALS SHEET ASME SECTION Xl BILL OF MATERIALS TRAVELER 01071 MWO -AEeJ4 U iIb/ , PAGE A O0F 3 Telescoping AX4AQ418 26 1977W1977 A:514 101%Cylinder -168\_ ___ _ VIM A -sic__ _ _," ___ _, COMMENTS:

-*1 0.1 Jr~ORIGINAL 0 ASME SECTION Xl TRAVELER SECTION Xl REPAIRIREPLACEMENT TRAVELER PAGE 1 OF 3 1 TRAVELER: 01102 REPAIR Li REPLACEMENT [-ASSOCIATED DOCUMENTS-- -COMPONENT-- MWO: A0000644 CODE CLASS: ASME III CLASS 1 DC: N/A TAG NO: A2117SNUBBERQ DCP: N/A DESCRIPTION SNUBBER PSA-i6 OTHER: N/A SERIAL NO: 15477 WORK DESCRIPTION: SNUBBER BEING REBUILT FOR RETURN TO WAREHOUSE STOCK NEEDS PARTS REPLACED EXAMINATION / TEST REQUIREMENTS -'N VT-1 N VT-2 N VT-3 OTHER N N NOMINAL OPERATING PRESSURE N PNEUMATIC N HYDROSTATIC PRESSURE N TEMPERATURE N HOLD TIME N FAILURE Evaluation for Suitability of Repair or Replacement

  • No Normal I Expected Wear -- ALARA L] DCP [] EQ Checklist El Yes Justification:

Intended life of if less than design life of repaired item: REPAIR/REPLACEMENT ORGANIZATION: SNC MAINT.-IITIAL IfVIEW -fGl E DATE HOLD POINTS INITIATOR .9/1.7101 r] YES__ZNONEl QUALITY CONTROL I 'ZZ Z _[Z YES_1NONEi ANII 1X- .JYESAJONE


F1AL LREVIEW-REMARKS: iirem -o ~i-dec ~a n Snsb&er Sg(5 4 0 R WE~

TRAVELER NO: 01102 MWO: A0000644 ORIGINAL*1 SECTION XI TRAVELER INSTRUCTION SHEET PAGE 2 OF 3i I Il 4 4 *i-I 4 4. 4 4 i: REPLAC)ON THE~~~IMAINTI I~-~~L2 I_______2 VERIFY THE SERIAL NUMBER,HEAT _AND/OR TRACE CODE NUMBER OF _THE REPLACEMENT PART(S) _MATCHES WHAT'S RECORDED ON _THE MER OR THE APPLICABLE _-__DOCUMENT. aC H b NI -3 VERIFY THAT THE ASME CODE CLASS .__FOR THE REPLACEMENT PART(S) _MATCHES THAT OF THE COMPONENT _OR PIPING SYSTEM IN WHICH IT IS _BEING INSTALLED. QC H _____4 INSTALL REPLACEMENT PART(S) MAINT H X- f'-, I FIGURE 2 'I.'. *I r)QIrJN~Al ASME SECTION X I BILL OF MATERIALS TRAVELER 01102 MW O A00006 4 PAGE 3 OF 3.I BALL £CflW ACCY. ~AQ4 0160 ff 1977 wi? 1977 lcq W.q Re~~c-reGUR 3~L~ R 0

  • 1 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler#

04110-3.1. Owner Southern Nuclear Operating Company Date 10/31/06 Name 40 Inverness Center Parkway, Birmingham, AL Sheet I of Address 2. Plant Vogtie Electric Generating Plant Unit Name Waynesboro, GA 30830 wc* 10401oaa.WOO 104010M -Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voatle Address Type Code Symbol Stamp Authorization No.Expiration Date W/A AN/A N/A 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME SEC //1 19 74 Edition, Summer 1975 Addenda, (b)Appilcable Edition of Section Xi Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components.L/A Code Cat e National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stompec" Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)VALVE DRESSER H207ABH AL/A 1-1208-U4-033 1982 REPLACEMENT YES I INDUSTRIES INC. _7. Description of Work Seal welded valve body to bonnet.8. Test Conducted: Hydr ostatic E] Pneumatic[] Nominal Operating Pressure[J NA [] Other 5 Pressure NOP PSI Test Temp. NOT -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No.' N/A Expiration Date N/A Signed A weoOn's Des e Team Leader Date O~wner or Owner's Designee, Title I 4.to p6 CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala and employed by Harilford Steam Boiler Insoection and Insurance Co. of Connecticut I of Hafggrtor o ecticut have Inspected the components described In this Owner's Report during the period 06/14/e4 I to II&XL1190(a .and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with' the requirements of the ASME Code, Section Al By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examlnatlons and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions O;4. 7'SC,'- -M pectc5Sl5gnature National Board, State, Province and Endorsements Date IA 4tezj. ,,fe l a ORIGINAL 3 it SECTION XI REPAIR/REPLACEMENT TRAVELER PAGE 1 OF 3 TRAVELER: 04115 REPAIR LI REPLACEMENT I-ASSOCIATED DOCUMENTS--


COMPONENT-----

WO: A0400541 CODE CLASS: ASME III-Cl. 1 NF CR: N/A TAG NO: A-2117zSNUBBERQ DCP: N/A DESCRIPTION Spare Snubber (AD-151)OTHER: AX4AQ56-10006 SERIAL NO: 588 WORK DESCRIPTION: Replace snubber flanged end sub-assembly. EXAMINATION / TEST REQUIREMENTS -N/A VT-1 N/A VT-2 N/A VT-3 OTHER N/A NIA NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement [] No _M Normal / Expected Wear [] ALARA [] DCP I] EQ Checklist[-] Yes Justification: Intended life if less than design life of repaired item: REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Operating Co.INITIAL REVIEW IGNA U E DA HOLD POINTS AWE lba_4 061/9 El YES 19 NONE ISI ENGINEER , ,- it E] YES .NONE SEC. Xl EXAMINER cipU4I-YS 12NONE ANII []YES NONE-FINAL REVIEW SIGbIATUJRE PATE I GNAT DATE ISI ENGINEER /0,/7 I AWE l/ý Z (, REMARKS: 1.- 6 60119 NI -"v- 2__.'ZS2.M1 rIMM'1INUIAL DATE Qe IfLudo. ORIGINAL TRAVELER NO: 04115 ASME SECTION Xl TRAVELER INSTRUCTION SHEET WO: A0400541 PAGE 2 OF 3 N2-R >~N 1,_ MIT. ___STRUTIOS RO WI INTIDTE. WI -NITIDATE'1. Ensure the serial number, heat Maint. " ... ......... _ ....._.... .and/or trace code number of the _ __ __replacement part(s) is entered on _-_ _ _ _ __the MER. If the part does not have any of these markings, ensure the part is identified with the warehouse label providing PO, MIR and PO line Item numbers. Ensure ASME Code Class of the replacement part(s) is entered on the MER.2. Verify the serial number, heat and/or QC /W trace code number of the replacement _ ___"_"___/ part(s) matches what is recorded on ___. __the MER or the applicable documen- -____tation. If the part has no markings, utilize the PO, MIR and Line Item numbers on the warehouse identifi-cation label.3. Verify that the ASME Code Class QC N A,/for the replacement part(s) matches or ___ _. /exceeds that of the component in f___- ____b which it is being installed.

4. Install replacement part(s) in spare Maint.snubber...

e- Ar fl/ 11 Ad/Q/ 0 O RI(AL ASME SECTION Xl BILL OF MATERIALS TRAVELER 04115 W6 A0400541 PAGE 3 OF 3 MATRILICMPREFE.RENCE IEM RIGINAL&_`:K.`. OIIA ET RCECD -IULEAIE DESRIPION -DA~iG 'O~'-~+RELAEMENT K EPLACEMENT ý REIL#- ~ 'EII I Flanged Fixed AX4AQ56- 81 1977W1 977 SA564 TY 630 1 i y/End 10006 Iq77LWlq77 sA5*1TY6;s3,'- -* Fixed End AX4AQ56- 83 1 977W1 977 SA564 TY 630 Guide Sleeve 10006 Jam Nut AX4AQ56- 84 1977W1 977 SA564 TY 630 -37 ,, .. 10006 1'977L i77 _S4& .-37.COMMENTS:

  • These are parts of the flanged end sub-assembly.

.I/7/ V E/ ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 05124'Y 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Blrmingham, AL Address Vopte ElectrIc Generating Plant Name Waynesboro, GA 30830 Date Sheet Unit 10300 I 1 of L L 1 L 2. Plant WO# 1051668001 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Name Plant Vogte Address Type Code Symbol Stamp Authorizaion No.Expiration Date NAV N/A N/A 1511 / Containment Coalina System is 11 / Containment Cooling Svstsm 5. (a) Applicable Constructlon Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N/A (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19f8 6. Identification Of Components Repaired or Replaced and Replacement Components Code Cade National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)1511 PIPING CWI N/A N/A 1V4-1511-O03-01 1987 REPLACEMENT YES [SYSTEM INCORPORATED 1-1511-E7-001

7. Description of Work Replaced studsand nuts In the 2- II2 Inlet and outlet header flanges to Containment Cooler 1-151 I-E7-001.8. Test Conducted:

WA[1 9. Remarks See Item 7 Hydrostatic [3 Pneumatic Nominal Operating PressureD Other [] Pressure N/A PSI Test Temp. N/A OF Applicable Manufacturer's Date Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Data N/A I Signed Owneo Team Leader Date-fix CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut I of Ha" necticut have Inspected the components described In this Owner's Report during the period 11/28/05 I to a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shaell be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this I1-- D , Commissions C(-A ZrS".Wrspe6(or's Signature Date .1;, =National Board, State, Province and Endorsements

  • ---

ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Traveler# 06009 01/05/07 I of _WO# 1054155901 Address Vontla Electric Generatina Plant 2'. Plant Unit Name Waynesboro, GA 30830 Address-Repair Organization P.O. No., Job No., etc.3. Work Performed by, Maintenance Department Name Plant Voatle Type Code Symbol Stamp Authorization No.Expiration Dafte N/A N/A N/A Address 1205/ Residual Heat Removal Systemn 4.S.Identification of System (a) .Applicable Construction Code ASME SEC Ill 19 71 Edition, Summer 1972 Addenda, N/A (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 198 Code Case 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stomped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)RELIEF VALVE CROSBY VALVE & N56904-00-0037 N/A 1PSV-8708A 1977 REPLACED YES GAGE CO.RELIEF VALVE CROSBY VALVE & N56904-00-0017 N/A IPSV-8708A 1975 REPLACEMENT YES GAGE CO.7. Description of Work Replaced relief valve. The replacement relief valve, serial number N56904-00-0017, Is a rotating spare and was originally Installed as 2PSV-8708B during construction;

8. -Test Conducted:

NA-9. Remarks See Item 7 Hydrostatic [] Pneumatic-- Nominal Operating Pressure[M] Other E] Pressure N/A PSI Test Temp. N/A F o1\Applicable Manufacturer's Data Reports to be attached.CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. -N/A Expiration Date N/A Signed f A J-9 Team Leader Date l z- 0 "\l Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by Hartford Steam Boiler Ins-ection and Insurance Co. of Connecticut of Haifford. Connecticut have Inspected the components described In this Owner's Report during the period 04/0306 to /-,.$ -4007 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ingl 1 .._" ' ,,:_____________________Commissions &ia s , Inspecta e Signature National Board, State, Province and Endorsements Date It I.T^0 MO07 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS 1 As Required By The Provisions Of The ASME Code Section Xi Traveler 0 06020 Southern Nuclear Operating Comoany Date 10/31/06 1. Owner Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Sheet Unit t of t T 1 Name Waynesboro, GA 30830 WO# 1053338301 Address Maintenance Department

3. Work Performed by Repair Organization P.O. No., Job No., etc.Type Code Symbol Stamp N/A Authorization No. N/A Expiration Date N/A Name Plant Vootte Address 4.5.6.Identification of System 1206 / Containment Spray System (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appliceble Edition of Section Xl -Utilized for Repairs or Replacements l98f9i Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Coie Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or Nok PIPE PULLMAN POWER N/A N/A Vl-1206-006-H020 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-1, serial #24337A was replaced with a Lisega Type 30 snubber serial # 305002621043.
8. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] NlA'] Other 5 Pressure N/A PSI Test Temp. .N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement, Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A -Signed L6 Team Leader Data L ( z t\Owner or Owner's Designee, Title 1Q$1".CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connectiut! of Hack% Connecticut have Inspected the components described in this Owner's Report during the period 02/23/06 I to /111 IAQand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning ithe examinationsand corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a lose of any kind arising from or connected with this Insoetlon. 91 " &u Commissions &oinl InpetaftSigntureNational 13oard, State, Province and Endorsements Data .2'9 b~_ *ýfteo ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS 4/As Required By The Provisions Of The ASME Code Section Xi Traveler # 06027 1. Owner Southern Nuclear Operating Company Ntam 40 Inverness Center Parkway. Blrminanha. AL Date Sheet Unit 10/31/06 1 of 1 Address 2. Plant Votjtle Electric Generating Plant Name Waynesboro, GA 30830 Address WO# 1053341101 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1301 /Main Steam System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Coa (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components a National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped, Component Manufacturer Serial No. No. Identification Built or Replacement Ls or N60 PIPE PULLMAN POWER N/A N/A VI-1301-107-HO06 1987 REPLACEMENT YES I SUPPORT PRODUCTS _7. Description of Work Snubber AD-5501, serial #239 was replaced with a snubber AD-5501, seral # 229 to support surveillance testing.S. Test Conducted: Hydrostatic [- Pnaumatic[] Nominal Operating Pressure[] NIA E] Other I] Pressure N/A PSI Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the" statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A -Certificate of Authorization No. N/A Expiration Date N/A I Signed _040%-. Team Leader Date di, A i Owner or Owner's Designee, 11dte CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GGac l and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut ofConectiut have Inspected the components described In this Owner's Report during the period 02'23/06 to I 49=&and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &,A "-----."- pect Signature Data OW &I OL. National Board, State, Province and Endorsements .1 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Travelero 06036 Vt: 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date 11/01/06 Sheet I of 1 Address 2. Plant Voatle Electric Generating Plant Unit 1 Name Wnvn ...... ,~ .......WO# 1053342101 Address.Repair Organization P.O. No., Job No., etc.3.. Work Performed by 4. Identification of System Maintenance Department Name Plant Voatle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1301/Main Steam System 5. (a) Applicable Construction Code ASME SEC Ill 19 77 Edition, Winter 1977 Addenda, (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components 1644-5 Code Case Nationali Repaired, ASME Code Name of Name of Manufacturer Board .Other Year Replaced, StampedI Component Manufacturer Serial No. No. Identification Built or Replacement so or No)PIPE PULLMAN POWER /A IVA V.l-301-139-H004 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-1L, serial #600 was replaced with a snubber PSA-IL, serial # 595 to supportsurveillance testing.8. Test Conducted: Hydrostatic [] Pneumsaticlr Nominal Operating Pressure[] N/A [] Other E Pressure N/A PSI Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached .CERTIFICATE OF COMPLIANCE I We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Aiphorlzation No. N/A Expiration Date N/A Signed Team Ledera Data I , C.]Owner or Owner's Designee. Title ,Iloilo, CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by Hartford Steam Boiler Insoection and Insurance Co. gf Connecticut I of HartfordC Cortcu have Inspected the components described In this Owner's Report during the period 02/23M/06 I to arm y , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor, his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspcinj~42~.Commissions --Ispectors Signature National Board, State, Province and Endorsements Date a/ r - ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI I Traveler # 06039 I 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Voatle Electric Generating Plant Date Sheet 1Gi oa'0 Of oL 1 1 Unit Name Waynesboro, GA 30830 Address WO# 1060055801 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voctle Type Code Symbol Stamp Authorization No.Expiration Date N/A M/A N/A Address 1201 / Reactor Coolant System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Cat (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19-0 6. Identification Of Components Repaired or Replaced and Replacement Components 9 7. Description of Work Snubber AD-501, serial #552 was replaced with a snubberAD-501, serial # 364 to support maintenance on valve 1PVO455B.S. Test Conducted: Hydrostatic Q Pneumatic[] Nominal Operating Pressure[[] N/A FXJ Other I] Pressure N/A PSI Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of ti ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed " f'k --Team Leader Date , f w-ner or Owner's Desinee, Title U-lot CERTIFICATE OF INSERVICE INSPECTION i I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomfa and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harford. neticut have Inspected the components described In this Owner's Report during the period 0=/1/6 to UU&. Ata(A I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section IXi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inp i Commissions Cw. Tg..I8psp-e'or's Signature National Board, State, Province and Endorsements I Date 1& A100. Ab:hf ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler # 06040 11/01/06 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmingham, AL Date Sheet 1 of I 2. Plant Address Vogqte Electric Generating Plant Name Waynesboro, GA 30830'Address Unit I WO# 1060107701 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Deparnment Name Plant Voofle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 198Q 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement aYes or No)PIPE PULLMAN POWER AL/A AN/A V1-1201-031.HOOl 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work -Snubber PSA-1, serial #24106 was replaced with a snubber PSA-1, serial # 21682 to support surveillance testft,.8. Test Conducted: Hydrostatic E] Pneumetic[] Nominai Operating Pressure[] N/A Other Pressure NA PSI Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Date Report. to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed tA).* (Awr w Team Leader Date Titl 0 k .Pwner or Owner's Designee, TitieI I CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geomla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harfd Connecticut have Inspected the components described in this Owner's Report during the period 02/23/06 to 1- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In ton.C31E Commissions C_ Go ;3176lnpectft Signature National Board,-State, Province and Endorsements Date ..9 bao_ AJ,, ..) ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl if Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtie Elect ic'Generating Plant Name Waynesboro, GA 30830 Address 3. Work Performed by ý Maintenance Department Name Plant Vogtle Address Date Sheet Unit I !uVWWla f f I 11/01/06 of I WO# 1060107801 Repair Organization P.O. No., Job No., etc.Type Code Symbol Stamp Authodzation No.Expiration Date N/A N/A N/A 4. Identification of System 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement as or No PIPE PULLMAN POWER N/A N/A VI-1201-036-H010 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-35, sedal #11507 was replaced with a snubber PSA-35, sedal # .11236 to support surveillance testing.8. Test Conducted: Hydrostatic [) PneurcaticQ' Nominal Operating Pressurefl NIA [] Other [] Pressure N/A PSI Test Temp. N/A IF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp Certificate of Authorization No. N/A Expiration Signed Qrkj^ L. ^ Team Leader Date NAV Date N/A~. I Owner at Ownera Dmnlanee. Titli Owner or Owner's Desionse Titid CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boller and Pressure Vessel Inspectors and the State or Province of Georla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Halfor. onncut have Inspected the components described In this Owner's Report during the period 02123/06 to z and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspect~on. ___t__ _.___ ,_ _. _ _ Commissions (G A Signa'ture -National Board, State, Province and Endorsements Date &I.ba?,.. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Y 1. Owner Southern Nuclear Operating Company Name'40 Inverness Center Parkwav, Birmingham, AL Date Sheet Traveler# 06042 11/01/06 of 1 1 WOO 1060107901 Address 2. Plant Vogtle Electric Generating Plant I" I r Unit Name Waynesboro, GA 30830 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System* Maintenance Department Name Plant Voatle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1201 / Reactor Coolant System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, (b)Applicable Edition of Section Xl Utilized for Repaire or Replacements 19,V 6. Identification Of Components Repaired or Replaced and Replacement Components 1644-5 Code Case National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No PIPE PULLMAN POWER N/A N/A VI-1201-049-H002 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-35. serial #11248 was replaced with a snubber PSA-35. serial # 11250 to support surveillance testing.8. Test Conducted: Hydrostatic 5 Pneumatic[] Nominal Operating Pressure[] N/A M] Other 5 Pressure N/A PSI Test Temp. NIA OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct end this r ASME Code, Section Xl. repal Type Code Symbol Stamp N/A Certificate of athorization No. N/A Expiration Data Signed ok,4JJv -Team Leader Date placement r or replacement conforms to the rules of the NWA I "LV I / i) C, 7 1 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by Hartford Steam Boiler Insoecticn and Insurance Co. of Connecticut of Harr Connic have Inspected the components described In this Owner's Report during the period 02/23/06 to 0" and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for.any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions '(In111pectrV¢Sgnature National Board, State, Province and Endorsements Date 2 1 t)0- &*MO(. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl.Traveler# 06043.q 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date 10130105 Sheet I of 1 Address 2. Plant Vogile Electric Generating Plant Name Waynesboro, GA 30830 Unit WO# 1060108301 Repair Organization P.O. No., Job No., etc.Address 3. Work Performed by Maintenance Department Name Plant Vootle Type Code Symbol Stamp Autliarboalofl No.Expiration Data N/A N/A N/A Address 4. Identification of System 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 19.0 6. identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer" Serial No. No. Identification Built or Replacement (Yea or N PIPE PULLMAN POWER N/A N/A VI-1201-097.H601 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-73, serial #435 was replaced with a snubber AD-73, serial # 1202 to support surveillance testing.8. Test Conducted: WAj1 9. Remarks See Item 7 Aydroatatic M Pneumatic[] Nominal Operating Pressureed Other [] Pressure NIA PSI Test Temp. N/A OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Q.,Vj. Team Leader Date / 1!(, Owner or Owner's Designee, TI Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GeoMMl and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut ot Ha" have Inapected the components described In this Owner's Report during the period 02123/06 to ./.ap-7 .fL-, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning, the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In-" --Commissions 6qr. -ýr'&Inilpectoea Signature National Board, State, Province and Endorsements DateA r? si/a. .'ogo. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS .As Required By The Provisions Of The ASME Code Section XI£7'1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham. AL Address 2. Plant Vogte Electric Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit Traveler# 06045 10131106 1 .I 1 WO# 1060108601 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtie Type Code Symbol Slamp Authorizaton No.Expiration Date N/A N/A N/A Address 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition. Winter 1977 Addenda, 1644-5 Code Case (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yea or No)PIPE PULLMAN POWER N/A N/A V1-1204.0214H022 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-10, serial #15478 was replaced with a PSA-tO, serial #14986 to support surveillance testing.S. Test Conducted: Hydrostatic Pneumatic[] Nominal Operating Pre-sure[] NWA[] Other fl Pressure N/A PSI Test Temp. N/A -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ne n') Team Leader Date Et L. (Owner or Owner's Deslgnee, Title%CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GeorOla and employed by Hartford Steam Boiler Inspection and Insurence Co. of Connecticut of-arfo. nnecticut have Inspected the components described In this Owner's Report during the period 02/23/06 to 1, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a lose of any kind arising from or connected-with this Commissions i-, "r'7 Inspettor's Signature National Board, State, Province and Endorsements ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler # 06046 1. Owner Southern Nuclear Operating Company Date Name 40 Inverness Center Parkway, Birmingham, AL Sheet Address 2. Plant Voogle Electric Generating Plant Name Waynesboro GA 30830 Address 10131/06 1 of I WOfE 1060108701 Unit Repair Organization P.O. No., Job No., etc.3. Work Performed by 4, Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1204 /Safety Injection System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Appllcable Edition of Section Xi Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)PIPE PULLMAN POWER N/A N/A Vl1-204-023-H002 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-1603, serial #681 was replaced with a snubber AD-1601, serial # 531 to support surveillance testing.8. Test Conducted: Hydrostatic r Pneumatic'] Nominal Operating Pressure-' WA [f] Other 5 Pressure N/A PSI Test Temp. N/A F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement I C8110 las Type Code Symbol Stamp Certificate of Authorization No. N/A Signed .Team Leader.L I Owner or Owner's Designee, Titfd IVA Expiration Date N/A Deft+/-L CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georiala and employed by Hartford Steam Boiler Insoection and Insurance Co of Connecticut of Hartfor. Cncticu have Inspected the components described In this Owner's Report during the period 02/23106 to 1a nd state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Coda, Section XI.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report.. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions , , -rt.lnespectf's Sgnature National Board, State, Province and Endorsements Date D29b~Q2bist. 9.ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI'7 Traveler# 06047 11/13/06 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Blimingham, AL Address 2. Plant Voglie Electric Generating Plant Date Sheet I of I Unit Name Waynesbomr, GA 30830 Address 1 WON 1060108801 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voptle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME SEC I11 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)PIPE PULLMAN POWER N/A N/A VI-1204-024-H029 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-3, serial #26805 was replaced with a snubber PSA-3, serial # 28341 to support surveillance testing.e. Test Conducted: Hydrostatic Q Pneumatic[-] Nominal Operating Pressure[] N/A Other E Pressure N/A PSI Test Temp. N/A *F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI.. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed -t( Team Leader Date I i / ,/\jOwner or Owner's Designee, Tite ( CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Htfd Con have inspected the components described in this Owner's Report during the period 02/23/06 to 0 Mand state that to the best of my knowledge and beliefi the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this aw-&-0 Commissions (LA PCY47-Dete IS" -Iffspectd-iff Signafure-F National Board, State, Province and Endorsements Date I A .4MI. 'Aobta ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Ll 1. Owner. Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham. AL Address 2. Plant Vogte Electric Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit Traveler I 06048 10/31/06 of I 1 WO# 1060108901 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Votle Address Type Cods Symbol Stamp Authorization No.Expiration Dote N/A N/A N/A 1204 / Safety Injection System, 5. (a) Applicable Construction Code ASME SEC /iI 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 1 9f89 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASM E Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)PIPE PULLMAN POWER N/A N/A VI-1204-047-HO03 1987 REPLACEMENT YES SUPPORT PRODUCTS 7.' Description of Work Snubber PSA. 1/4, serial #26457 was replaced with a PSA-1/4, serial #35110 to support surveillance testing, The transition tube bolting was also replaced.8. Test Conducted: N/A[s]9. Remarks See Item 7ýHydrostatic [] Pneumatlcr] Nominal Operating Pressure[] Other [] Pressure N/A PSI Test Temp. N/A Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 0ad Team Leader Date at ("L. 10 i Owner or Owner's Designee, Title I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued'by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of-aro. Conecticut have Inspected the components described In this Owner's Report during the period 02123106 to IA( and state that to the "best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &19 75e.Insi-etor's Signature National Board, State, Province and Endorsements Date J90 tem 4tnnt ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler # 06049 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant .Vogitle Electric Generating Plant Nome Waynesboro, GA 30830 Date 10/30/06 Sheet I of I Unit 1 WO#A0400541 and 1060109001 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Address Maintenance Department Name Plant Voatle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME SEC ill 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board. Other Year Replaced, Stamped Component. Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)PIPE PULLMAN POWER N/A N/A Vl-1208-488-H021 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Descrlption of Work Snubber AD- 151, serial #416 was replaced with a snubber AD-151, serial # 588 to support surveillance testing.The flanged end sub-assembly was previously replaced in the replacement snubber serial # 588 under Traveler # 04115 and WO# A0400541.8. Test Conducted: Hydrostatic C] Pneumatic[] Nominal Operating Pressure[] N/Ax- Other 5 Pressure N/A PSI Test Temp. N/A F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XL. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _ ( Team Leader Date 1.iLLL/..., 4 Owner or Owner's Designee, TitieO CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia -and employed by Hartford Steam Boiler Insoaction and Insurance Co. of ConnecticA# 'of Hartford onecticut have Inspected the components described In this Owner's Report during the period 06/21/04 to ad and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, conderning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions &if 7;M" " ispecls Signature National Board, State, Province and Endorsements Date j/ _ 'ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler # 06051 1. Owner Southern Nuclear Operating Company Date 11/01/06 y Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Name Waynesbom, GA 30830 Sheet Unit 1 of 1 1 WO# 1060109401

3. Work Performed by Address Maintenance Department Repair Organization P.O. No., Job No., etc.Type Code Symbol Stamp N/A Authorization No. N/A Expiration Date N/A Name Plant Vootle Address 4. Identification of System 1301 / Main Steam System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)App!lcable Edition of Section Xl Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. identification Built or Replacement (Yes or No)PIPE .PULLMAN POWER N/A N/A VI-1301-104-HO06 1987 REPLACEMENT YES SUPPORT RODUCTS 7. Description of Work Snubber PSA-35, serial #1 144a was replaced with a PSA.35 serial #11484 to support surveillance testing.8. Test Conducted:

Hydrostatic 5 Pneumatic[] Nominal Operating Pressure[] NIA' Other 5 Pressure N/A PSI Test Temp. N/A F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date A/A Signed w no Team Leader Data A Owner or Owner's Designee, Titib CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boller and Pressure Vessel inspectors and the State or Province of Georala and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Ha=% nncticut have Inspected the components described in this Owner's Report during the period 02123/06 to Z. and state that to the best of my knowledge and belief, the ,Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspaln -____,________Commissions C-^,. v'.li-fpect~r'8 Signature National Board, State, Province and Endorsements Dote A a t.&~~ I.l-I ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 4/t Traveler# 06052 I0/30/06' 1. Owner Southern Nuclear Operating Company.Date Name 40 Inverness Center Par*WaY, Birmingham. AL _.Sheet 1of Address 2. Plant Voglie Electric Generating Plant Name Waynesboro, GA 30830 Address 3. Work Performed by Maintenance Department Name Plant VogUe Address Unit 1 WO# A051767536 and 1060109501 Repair Organization P.O. No., Job No., etc.Type Code Symbol Stamp Authorztlon No.Explrtion Date N/A N/A N/A 4. Identification of System 1301/Main Steam SYstem 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1§ CodeCas (b)Appllcable Edition of Section XI Utilized for Repairs or Replacements 19§1 6. Identification Of Components Repaired or Replaced and Replacement Components A Nj Nenal Repaired, ASME Cod Name of Name of Manufacturer -Other Year Replaced, Stampedi Component Manufacturer Serial No. No. identification Built or Replacement .(Yes or No PIPEORTN U OL UTPOWER NuAcIe A VI-1301-105-HO03 1987 REPLACEMENT YES SUPPORT P FRODUCTS 7. Description of Work Snubber AD-12501. serial #132 was replaced with a snubberAD-12501, serial # 18 to support surveillance testinqg The planetary standoff flat head screws were previously replaced in the replacement snubber serial # 18 under Traveler # 06081 and I WO# AO5176 7536.8. Test Conducted: Hydrostatic [] Pneumatlc[] Nominal Operating Pressure[] WA [] Other Q Pressure N/A PSI Teat Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Data N/A Signed , , Team Leader Date I I / l/l , Owner or Owner's Designee, TitIel 1=F CERTIFICATE OF INSERVICE INSPECTION i, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the Stste or Province of Geornla and employed by Hartford Steam Boiler Inspectlon and Insurance Co. of Connecticut l ol Hartord..Coninecficut have Inspected the components described in this Owner's Report during the period --02120 to 0 and state that to the beat of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xh.By signing this certificate, neither, the Inspector nor his employer-makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this____________________ Commissions &#* T.45'fI---In6spectofi Signature Datea National Board, State, Province and Endorsements ) ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 4 Traveler # 06053 I 1. Owner 2. Plant Southern Nuclear Operatin Company Name 40 Inverness Center Parkmav. Blrminoham. AL Date Sheet Unit 11/01/06 1 off 1 Address Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address WO 1060109601 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Address Type Code Symbol Stamp Authorizatdon No.Expiration Date 1301 / Main Steam System N/A NAM N/A 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, "N-249-1 Code Cas (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements 19g S. Identification Of Components Repaired or Replaced and Replacement Components D National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampedl Component Manufacturer Serial No. No. Identification Built or Replacement (Ye 0 or NoL PIPE PULLMAN POWER N/A N/A V1-1301-106-H004 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-5501, serial #333 was replaced with a snubber AD-5501, senal# 242 to support surveillance testing..8. Test Conducted: Hydrostatic Q Pneumatic[] Nominal Operating Pressurefl N/A{[ Other El Pressure N/A PSI Test Temp. N/A *F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A -Signed Team Leader Date ln 'Lo ( Owner or Owner's Designee, Tlt14I CERTIFICATE OF INSERVICE INSPECTION -I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Gporala and employed by Hartford Steam Boiler Insoectlon and Insurance Co. of Connecticut 1 of Hartford, C u have Inspected the components described In this Owner's Report during the period 0 120/06 1 to ZQa and state that to the best of my knowledge and belief, the Owner has performed examinations and takten corrective measures described in Athis Owners Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins Commissions C!4. " ."I Inspectors Signat9e National Board, State, Province and Endorsements Date Al: boa. - 4 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06054 y/1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit 11/01/06 I of 1 WO# 1060109701 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department .Name Plant Vogtle Address.Type Code Symbol Stamp AuthorizatIon No.Expiration Date N/A N/A N/A 1301 /Main Steam System 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1

  • Code Cas (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19f8 6. Identification Of Components Repaired or Replaced and Replacement Components 9 National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampeds Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or NO)PIPE PULLMAN POWER N/A N/A VI-1301-110-H004 1987 REPLACEMENT YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-151L, serial #700 was replaced with a snubber AD-151L, serial # 486 to support surveillance I testing.5. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating PresaureQ NIA Other Pressure N/A PSI Test Temp. N/A -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE V We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of A~thorization No. N/A Expiration Date N/A -Signed )4oj.vý( U -s A Team Leader Date it__________ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of -Georala and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut Iof Hartford Qonnectlcut have Inspected the components described In this Owner's Report during the period 020 to and state that to the 'best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this CM ts1a ACommissions (go ?Jrtf, In~boectorrg Signature National Board, State, Province and Endorsements IDate ,,29 J .o_. . I.ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler #06055 e 1. Owner Southern Nuclear Operating Company Name 40 inverness Center Parkway, Blrmlngham, AL Address Vogtle Electric Generatino Plant Name Waynesboro, GA 30830 Address Date Sheet Unit 10/3/6 I 1 of L I'2.Plant WO# 1060109901 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voctle Address Type Code Symbol Stamp Authorization No.Expiration Data W/A N/A W/A 1302/Auxiliary Feedwater System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, " N-249-1 Code Cas (b)Appllcable Edition of Section XI Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components a National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or Nol PIPE PULLMAN POWER N/A N/A VI-1302-107-H01 1 1987 REPLACEMENT YES SUPPORT PRODUCTS.7. Description of Work Snubber AD-503, serial #313 was replaced with a snubber AD-503, serial # 201 to support surveillance & Test Conducted: Hydrostatic [ Pneumatic[] Nominal Operating Pressure[] NIAE] Other I Pressure N/A PSI Test Temp. N/A -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xh repair or replacement I Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A I P Signed STeneador Date #I k or Owner's Designeb, Tide CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georcia and employed by Hartford Steam Boiler Insoection and Insurance Co. af Connecticut of-lafo. Coe have Inspected the components described in this Owner's Report during the period 02-20/06 tond stats that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinatIons and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this=Commissions &A. National Board, State, Province and Endorsements >e te 7 ,L.~ ' tl, K ORIGINAL FORM NIS-2 OWNER'S REPORT-FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 06057 ,-1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit Address 2. Plant Vootle Electric Generating Plant 11/07/06 1 of I WO# 1060110101 and A0000644 Name Waynesboro, GA 30830 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogte Type Code Symbol Stamp Authorization No.Exopilron Date N/A N/A NALI Address tqn~ IA. .viIInr.j nwtu~ntnr ~utt4n1 1302IAuxilia Feedwater-q-tem S. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Case (b)Applilcable Edition of Section Xl Utilized for Repairs or Replacements 19.6 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampsed Component Manufacturer Serial No. No. Identification Built or Replacement aYes or No)PIPE PULLMAN POWER N/A N/A VI-1302-109-HOO9 1987 REPLACEM&ENT YES SUPPORT PRODUCTS _I.7. Description of Work Snubber PSA-lO, serial #15950 was replaced with a snubber PSA-1O, serial # 15477 to support surveillance 1 testing. The telescoping cylinder In the replacement snubber serial # 15477 was also replaced under Traveler# 01102 and I WO# A0000644.6. Teat Conducted: NAI 9. Remarks See Item 7 Hydrostatic [] Pneumatic[] Nominal 'Operating Pressure[] Other [] Pressure N/A PSI Test Temp. N/A F?I Applicable Manufacturer's Data Reports to be attached I CERTIFICATE OF COMPLIANCE We certify that the atements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Learneader Date 0I JjOwner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boller and Pressure Vessel Inspectors and the Slate or Province of GeoR7ia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford. Conneccut have Inspected the components described In this Owner's Report during the period 09/10/01 I to M -and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section 1Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins Commissions Goi 7T5 IribpectWSlgnature National Board, State, Province and Endorsements Date .AM&=AID& ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electic Generating Plant Date Sheet Unit Traveler # 06058 10/31/06_ _ _ of WO# 1060110201 Name Waynesboro, GA 30830 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voctle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A 1302/Aux~liary Feedwater System _5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Cas (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components Descriptlon of Work SnubberAD-501, serial #574 was replaced with a snubber AD-501, serial # 567 to support surveillance testing.8. Test Conducted: NIA1 9. Remarks See Item 7 Hydrostatic [] Pneumatic[:] Nominal Operating Pressure[Other [] Pressure N/A PSI Test Temp. A/A OF Applicable Manufacturer's Data Reports to be attached 1111,1101 CERTIFICATE OF COMPLIANCE i We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/AI Signed a L Team Leader Date loc. *Owe r Owner's Dein e, ttl CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ge0o1ia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartord. Connect have inspected the components described In this Owner's Report during the period 020/to. a= and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section!Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning .the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with ihis in eoon.Ida- -Commissions (&4 -7:TtA'MarpecteA Signature National Board, State, Province and Endorsements Date L _.. Anate ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06059-1/1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogie Electric Generating Plant Date 11/01/06 Sheet 1 of 1 1 Unit 1 Name WaynisboWo GA 30830 WO# 1060110301 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by Me P1 4. Identification of System intenance Department Name ent Vootle Type Code Symbol Stamp Authorizatlon No.Expiration Date N/A N/A AVA -Address/ I~n~rnt,}nh, 1305 / Feedwa for Q-tem 5. (a) Applicable Construction Code " ASME SEC III 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Cat (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 19A2 6. Identification Of Components Repaired or Replaced and Replacement Components a National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampem Component Manufacturer Serial No. No. Identification Built or Replacement as or No)PIPE PULLMAN POWER N/A N/A VI-1305-058-HO03 1987 REPLACEMENT YES I SUPPORT PRODUCTS _7. Description of Work Snubber PSA-100, serial #2505 was replaced with a snubber PSA-100, serial # 2402 to support surveillance testing.8. Test Conducted: NfA[9. Remarks See Item 7 Hydrostatic Q] Pneumatic[ Nominal Operating PressureD Other [] Pressure N/A PSI Test Temp. N/A'Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. AVA Expiration Date N/A -CL.. \ .I Signed Team Leader Date %I _ k Owne or Oner's Designee, TilteI CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of -Geomia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hardon c have Inspected the components described in this Owner's Report during the period 02/20/06 1 to / 2 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section fXl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ithe examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Ig on. of~ect ,gnatu "-Commissions "SSt c d 11setf intr National Board, State, Province and Endorsements Date AS t b;_ae b

  • -- -FORM NIS-2 OWNER'S RQ W M 6TC~4 TS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler#06O62L1 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL.Address 2. Plant Vogte Electric Generating Plant Name Waynesboro, GA 30830 Date Sheet 11102/06 of WO# 1060321601 Unit Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voatle Type Code Symbol Stamp Authorizatlon No.Expiration Date N/A N/A W/A -Address I 1302 / Auxiliary Feedwater System i a. (a) Applicable Construction Code ASME SEC III 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b)Appllcable Edition of Section XI Utilized for Repairs or Replacements 1989 6. .Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stomped Component Manufacturer Serial No. No. Identification Built or Replacement (Yea or NO'PIPE PULLMAN POWER N/A N/A VI-1302-107-H014 1987 REPLACEMENT YES I SUPPORT PRODUCTS _7. Description of Work Snubber AD.501, serial #166 was replaced with a snubber AD-501. serial N 689 to support surveillance testirl.[. Test Conducted:
9. Remarks See Item 7 Hydrosatic

[] Pneumatic[] Nominal Operating PresaureQ-Other [] Pressure N/A PSI Test Temp. N/A OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp V/A Certificate of Authorization No. N/A Expiration Date MIA -Signed or Date &CERTIFICATE OF INSERVICE INSPECTION i I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala -and employed'by Hartford Steam Boiler 'Inspection and Insurance Co of Connecticut I of Harford, Connecticut have inspected the components described In this Owner's Report during the period 02/23/06 to *a and state that to the best of my knowledge and belief, the Owner has performed examinations and tsaken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section 1XI.~I/By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer laill be liable.in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions LA .1&1 r npedis Signature National Board, State, Province and Endorsements Date At bi. O ,,(a L ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi I/Traveler# 06068 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit 11/15/06 1 of 1L Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 WO# 1060344801

3. Work Performed by 4. Identification of System Address Maintenance bepartment Name Plant Vootfe Repair Organization P.O. No., Job No., etc.Type Code Symbol Stamp Authorhadon No.Expiration Datm N/A W/A N/A Address Sr., /.d~~ 0 ,D.uf ý ~ a% UM=111 exe.1-1111 I S. (a) Applicable Construction Cede ASME SEC III 19 77 Edition, Winter 1977 Addenda, (b)Appllcable Edition of Section Xl Utilized for Repairs or Replacements l98f 6. Identification Of Components Repaired or Replaced and Replacement Components 1644-5 Code Case National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement aYes or NP4 PIPE PULLMAN POWER N/A N/A Vl-1204-023-HO10 1987 REPLACEMENT YES SUPPORT PRODUCTS -7. Description of Work Snubber PSA-1O, serial #15827 was replaced with a snubber PSA-1O, seratl# 16100 to support surveillance testing, 8. Test Conducted:

Hydrostatic [ Pneumatic[] Nominal Operating Pressure[J WAE'J Other ] Pressure N/A PSI Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement I Type Code Symbol Stamp N/A L Certificate of Authorization No. N/A Expiration Date N/A Signed ........Team Leader Date k I..r ~ & n~L WTFfA &eiF INPRI -IJPIT d3F INSBRVICF I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Hartford Steam Boiler Ins"ection and Insurance Co. of Connecticut I of Hartfd n have Inspected the components described In this Owner's Report during the period 03/16M6 I to a( and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of. any kind arising from or connected with this~P~M~a-.~AL 4..eO-~Commissions irv v"- i InspeDt -r's Signature -National Board, State, Province and Endorsements Date A10V~. 7006 FORM NIS-2 OWNER'S REQ 91 Q 4JRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler# 06075 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL oDat Sheet Unit 11/O8/08 of I Address 2. Plant Voglie Electric Generating Plant Name Waynesboro, GA 30830 WO# 1049001003 and PO# 7063483 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtie Address Type Code Symbol Stamp Authorization No.Expiration Data N/A A/A N/A 1201 / Reactor Coolant System 5. (a) Applicable Constuction Code ASME SEC III 19 71 Edition, Summer 1972 Addenda, N/A (b)Applilcable Edition of Section Xl Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components Code Cas 0 National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped, Component Manufacturer Serial No. No. Identification 1u3it or Replacement e REACTOR COMBUSTION 8971 21668 1-1201-V6-001 1076 REPLACEMENT YES VESSEL INC. ___________ ____ __________ _____.7. Description of Work The male flange assembly on the Instrument port column was replaced by a new design core exit thermocouple Iassembly (CE7NA). The CETNA assembly was Installed on vessel penetrations 75, 77, and 78 in accordance with DCP -1049001001.

8. Test Conducted:

NIA['9. Remarks See Item 7 Hydrostatic [] Pneumatlc[] Nominal Operating Preasure['] Other [] Pressure N/A PSI Test Temp. N/A Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _~ 1 " i~o WA. )A.L 4 Team Leader Date LL 1 i kX.. .Owner or Owner's Designee, Titt 1_I S. -CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel inspectors and the State or Province of Georgila and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut I of Hatrdn have Inspected the components described In this Owner's Report during the period 05/09/06 I to d and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer s~hal be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with Ihis In/LLI44iA,9 Commissions e-*. 7..-6'--1urfpectoft Signature Date -7 7 AV ja., National Board, State, Province and Endorsements ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 9 Traveler#- 06079 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Par*way, Birmingham, AL Address 2. Plant Vogile Electric Generating Plant Name Waynesboro, GA 30830 Address Date Shest 1013/015 I of I Unit WO# 1053519701 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. identification of System Maintenance Department Name Plant Vogtle Address Type Code Symbol Stamp Authoriation No.Expiration Date N/A N/A N/A 1201 / Reactor Coolant System 5. (a) Applilcable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N-249-1 Code Cal (b)Appticable Edition of Section XI Utilized for Repairs or Replacements 19&9 S. Identification Of Components Repaired or Replaced and Replacement Components a National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No PIPE PULLMAN POWER N/A N/A VI-1201-030-H601 1987 REPLACEMENT YES SUPPORT P RODUCTS/ 1-7. Description of Work Snubber AD-151, serial #482 was replaced with a snubber AD-151, serial # 133 to facilitate removal and installation of the Pressurizer code safety valves. I 8. Test Conducted: N/A[9. Remarks See Item 7 Hydrostetlic Q Pneumatic[- Nominal Operating Presaure-- Other [] Pressure N/A PSI Teat Temp. N/A OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A L Certificate of A thorization No. N/A Expiration Date N/A Signed ,ATmLeader Datea Owner or Owner's Designee, Thse Ie.CEiTIFICATE OF INSEHVI;E INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boilor and Pressure Vessel Inspectors and the S or Province of Gearola .and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut Hartfrd Connecticut have inspected the components described In this Owner's Report during the period 05/WW to L and state that to the best of my knowledge and belief, the Owner has performed examinations and ta corrective nmeasures described in this Owners Report in accordance with the requirements of the ASME Code, Section ken SXl.r By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning It examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer sh be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with ti In _________________ Commissions &0 ZX&.he all tis-t~apector's~ignature Date It4 Aoi.Ae1 National Board, State, Province and Endorsements 1 ORIGINAL 5 SECTION Xl REPAIR/REPLACEMENT TRAVELER PAGE 1 OF 3 TRAVELER: 06081 REPAIR E5 REPLACEMENT I---- ASSOCIATED DOCUMENTS--


COMPONENT


WO: A051767. 36 s"V% -g CODE CLASS: ASME III Ci. 1 NF CR: 2006105749 TAG NO: A-2117-SNUBBERQ O DCP: N/A DESCRIPTION Spare Snubber 1411-"6THER: AX4AQ56-10006 SERIAL NO: 18 WORK DESCRIPTION:

Install replacement Planetary standoff flat head screws.------- EXAMINATION / TEST REQUIREMENTS


N/A VT-1 N/A VT-2 N/A VT-3 OTHER N/A N/A NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement No [ Normal / Expected Wear [JALARA LI DCP N EQ Checklist 5 Yes Justification:

Intended life if less than design life of repaired item: REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Operatina Co.----- INITIAL REVIEW-EGN DATE, HOLD POINTS AWE E051,W66 -YES Z NONE ISI ENGINEER E YES NONE I UqMCNN(MMNER YES NONE ANII []j j YES NONE----- FINAL REVIEW -----SIGNATURE DATE "NT R D DkTE4 ISI ENGINEE AWE 4 REMARKS: _See. .-Tr..,,eerd -c'or ,'-.S-.rANI-- E [- i rIll nn!HOLD PO LDATEur ORIGINAL Il I 1 t TRAVELER NO: 06081 ASME SECTION Xl TRAVELER INSTRUCTION SHEET I-WO: A051767536 PAGE 2 OF 3 SEC. XI:*:STEP TRAVELER.WORK EXAMINERI ANI.....I.. MAINY ,, ,_,., NO.. '...INSTRUCTIONS. RWO W/Hi INIT/DATE W/l. INIT/DATE, 1. Ensure the serial number, heat Maint.and/or trace code number of the __-__replacement part(s) is entered on _the JML. If the part does not have any of these markings, ensure the part is identified with the warehouse label providing PO, MIR and PO line Item numbers. Ensure ASME Code Class of the replacement part(s) is entered on the JML. _2. Verify the serial number, heat and/or COC H , __ trace code number of the replacement / _ __part(s) matches what is recorded on M ______-, the JML or the applicable documen- S '.1, 5 _tation. If the part has no markings, _utilize the PO, MIR and Une Item _numbers on the warehouse identifi- _cation label. _3. Verify that the ASME Code Class CQC H _for the replacement part(s) matches or ___exceeds that of the component in _which it is being installed. .4. Install replacement part(s) in spare Maint. ",_,_ ' _'__snubber per procedure 27362-C. CQC , _/-__ -__________O O ORIGINAL 0 ASME SECTION XI BILL OF MATERIALS TRAVELER 06081 WO A051767536 PAGE 3 OF 3 REPLACEMENT.- CODE ED., ADD. &CASES MATERIAL SPEC REPLACEMENT ITEM. ASME SECTION XI -t.MATERIALICOMP REFERENCE ITEM ORIGINAL OG .INL-- HEAT, TRACE CODE. VISUAL EXAMINER DESCRIPTION -DRAWING NO. REPLACEMENT REPLACEMENT OR SERIAL# VERIFIC# 110 3 ea. Flat Head AX4AQ56- 136 1977W1977 SA564 TY 630 v-. ao.t,/t, Screws 10006 ___T7 W _ [q77 SA T5 &- W, 6W/J COMMENTS: -)o,,e_ ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler#06082 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Date Sheet 03/05/07 of 3 1 WO# 1061048701 Unit Address Repair Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Name Plant VogUe Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A 4. Identification of System 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME SEC I11 19 74 Edition, N/A (b)Aopllcable Edition of Section Xi Utilized for Repairs or Replacements 198L9 6. Identification Of Components Repaired or Replaced and Replacement Components Addenda, N/A Code Case National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampeod Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)VALVE FISHER 6499458 4704 IFV0121 1979 REPLACEMENT YES I CONTROLS CO.7. Description of Work Valve plug was replaced. A copy of Form N-2 for the replacement plug Is attached.8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] NIA] Other Q Pressure N/A PSI Test Temp. W/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date Signed Ownr D ln .Ti Team Leader Date -I Owner or Owner's Dasianee. Title I conforms to the rules of the'~OA N/A CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the St'ate or Province of Geomla a and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connectwlcu of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 07/31/06 to 7 -o -e and state that to the best of my knowledge and belief, .the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section !Xl.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning ihe examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this__,,-__ _ _ _ _ Commissions. 7s.4 l rpector'sgnature -National Board, State, Province and Endorsements Date 2,w 9~ 6 STr"e~eA4'X-2.4 FORM N-2 CERTIFICATE HOLDERS DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by tie Providous of the ASME Code, Section m Not to exceed One Day's Production Pg. 1 of I 25-N230123557 I. Manuikctured and cetfled by wrutle~ rVI?,?,a C hW'l mir. 1564 anirr TTU rrc PbiC 1 CfEACA IWU A tAB CO (nunu and addres afNFT Cartificate Holder)2. Mamadhctred for muckor 3850 1 -if eld QA ww"4 (namne and address of puihas)3. Location oftsimtllation V-#U Electric Gamatin PIS 7921 Rim Road w .. POD- GA 30RIn a Q2 (name an address)W/A 2ont 4. Type i2A657£ mov. r nA47O []I6tf 75 12A6S76 Rev. C w1k 2001 (drawin3 no.)QnwIr spee no.)(tesie -mmo)lr- A ,, J-(CMN (yearbuill)

5. ASME Code. Section III: I,.,. "mS~ fflE I (afition)(addenda date)(Cio)6. Fabrlcated in accordance with Cust. Spec. (Div. 2 only) N/A Revision H/A (no.)(Code Cue no.)Dole N/WA 7. Rwemb: Des:.l ASME BYFC. SEC. MI 1974 Ed iton. No Addatded C=a 2 Other: ASM. B-Vc, SEC. 0 1919 Edid, No dde!d, Clau 2 8. Noa. thicknme (in.) N/A Min. deslI Odtcla (n.) N/A Dia. ID (ft &in.) N/A Length ovewall (ft & in.) N/A 9. What applicabte.

Cerifcate Holders' Dat Reportsre us eahied for each item of this report: ha or Apputenancc Serial Number Heat Number 721402-1 Part or Appurtfnance Salal Number Heat Number I (1)(2)(3)(4)(5)(6)(V)(0)(9)(10)(13)(12)(13)(14)(15)(20)(21)(22)(23)(24)(25)A17258-1 4.5 (26)(27)(2C)(29)(30)(31)(32)(33)(34)(35)(36)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(48)(49)(5O)________________ I___________________ 1 _____________________ 4 --10. Design Pmeum 2735 Psi.Temp. 200 OF. Hydra. test pressure N/A at temp. 'P (when applicable)

  • Supplenmional hioromtiom in the form of M, sketches.

or drawnns may be ucd provided (1) siue is ! 112 x Ii, (2) Infom idon In ttent 2 and 3 on this Data Report included on MaC sheek ()mech sheet Is numced and the number ofsheets is recorded at the top ofthis fann.a See+ 3oQ3 FORM N-2 (back)Mft. Serial No. A17258-I CERTIFCATION OF DESIGN Design specificatito certified by Heavy P. Leonard P.A. State PA PC& no. 23938-B (when almicab"e) Deaign remt* certified by WA P.E. State NA Re. no. MIA (,wm applicable) CERTIFICATE OF SHOP COMP'IANCE We einuify dug the statamets mnde in ths rempoare aem et and "han this (these) Plug/Sten canrmn to the rules of tnsus ion ofdOe ASME Code. Section M.NPT Certfiate of Autlmrinon No. -1930 Uste 11-11-2001 Dafte oM301 Name FISHER 0 ONTROLS INT'L INC Sg WP Cutifleata Holder)CERIIFICATE OF SHOP INSPECTION I. the und -gilndI holding a valid osmsoaiason Ismued by the National Board of Boller and Pressure Vessel Iuspectors and the statc or Province of JOWAI mud egleyed by HARTFORD S.A.L & L CO I of HARTFORD.C ONN have inspected theme ier. descrbed in this Data Report an P-7an-Wste-- -5 a E dim to the best of nW kmwedgn end belief, the Cutifie Holder has fWbricsted these parse or apputenaness In accordance-with the ASME Code. Section Ill. Each parlisted has bern atorimed for atuulng on the date shown above.By signpin this eollficaWe neither the Inmpect nor his employer wakes any vamnty. expressed or implied, concaning the equipment desm'bed in this Data Repm t Fwtammoe neither dt inspector nor his eunplor shall be liable in my mnaner for any pesonal injury or pmiroty damage or imo ofany kind arising frn or connected'Jith this inspection.(Authiorized Inspector) (Nal. Bd. and. endorsements) state or peav. uud no.)!2-36-6.doc ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 06086.'1 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit 11/07/06 I of , 2. Plant Address Vogde Electric Generating Plant Name Waynesboro, GA 30830 Address WO# 1061721901 and A0100517 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voatole Type Code Symbol Stamp Authoriation No.Expiration Data WAL N/A N/A Address 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME SEC Ill 19 77 Edition, Winter 1977 Addenda, 1644-5 Code Cat (b)Applicable Edition of Section Xi Utilized for Repairs or Replacelments 1989 6. Identification Of Components Repaired or Replaced and Replacement Components D I-National Repaired, ASME Code Name-of Name of Manufacturer .Board Other Year Replaced, Stamps Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)PIPE PULLMAN POWER N/A AL/A VI-1201-030-H020 1987 YES I SUPPORT PRODUCTS 7. Description of Work Snubber PSA-3. 129749 was replaced with a snubber PSA-3, serial # 26939 to support survellance testing. The telescoping cylinder in the replacement snubber serial # 26939 was also replaced under Traveler# 01071 and WO# A0100517.8. Test Conducted: Hydrostatic 5 Pneumatic[] Nominal Operating Pressure[] N/A [x] Other 5 Pressure N/A PSI Test -Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE -We certify that the statements made In the report are correct and this replacement conforms to the rules of t e ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp WA Certificate of Authorization No. N/A Expiration Date N/A " Signed Teem Leader Date .: 4A~CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors: and the Ste or Province of Georole end employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut Hartford. Connecticut have Inspected the components described In this Owner's Report during the period 06I06/01 to state that to the best of my knowledge and belief, the Owner has performed examinations and talEon corrective measures -described In this Owners Report In accordance with the requirements of the ASME Code,.- -"Section -Xl" By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inslne~ton ...p Commissions-o B t nt It4 11-ý ectot% ignaureNational Board, State, Province and Endorsements ante "A sy. eof. .I ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REP4IRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 06087 9 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date 10123/06 Sheet 1 of 1 Address 2. Plant Vogtle Electric Generating Plant Unit I I Name Waynesboro, GA 30830 Address WO# 1061761501 Repair Organization P.O. No. Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtile Address Type Code Symbol Stamp Authorization No.Expiraton Date N/A N/A N/A 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME SEC Ill 19 77 Edition, Winter 1977 Addenda, N/A (b)Applicable Edition of Section Xi Utilized for Repairs or Repiacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components Code Case I National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, StampeZ Component Manufacturer Serial No. No. Identification Built or Replacement or N)PIPE PULLMAN POWER N/A N/A V1-1208-001-HO28 1987 REPLACEMENT YES I SUPPORT RODUCTS I 7. Description of Work Snubber PSA-3, serial #20228 was replaced with a PSA-3 serial #25504 to facilitate maintenance on valve 1LV0460.S. Test Conducted: Hydrostatic [] Pneumatic[- Nominal Operating Pressurefl N/A Other [] Pressure N/A PSI Test Temp. N/A F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A I Signed 0j.A-S-u Team Leader Date\J Owner or Owner's Designee, Tile CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of GeorIa and employed by Hartford Steam Boiler Inspection and insurance Co. of Connecticut I of-etfo. Connecticut have Inspected the components described In this Owner's Report during the period 09128/06 .to state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, SectionI X.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ithe examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a losq of any kind arising from dr connected with this In .WA# J Commissions .Ah (_ 7&'AI IThspe~PsSlgnitu'i -National Board,-9tote, Province and Endorsements Date Jo ,JI. ,,oof. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Cede Section XI Traveier# 06088 1. Owner 2. Plant Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmincham, AL Date Sheet Unit Address Vogte Electric Generating Plant-Name Waynesboro. GA 30830 Address 12/13(06 of 1 WO# 1054157401 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Addresis *Type Code Symbol Stamp Authorization No.Expiration Date 1202 / Nuclear Service Cooling Water System N/A N/A N/A 5.1516-2, 1567, 163541, 1649, (a) Applicable Construction Code ASME SEC III 19 74 Edition, Summer 1975 Addenda, 1677& 1712 Code Case*(b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stampesd Component Manufacturer Serial No. No. Identification Built or Replacement (Yea or No)VALVE ANCHORIDARLING E9001-133-4 N/A 1-1202-U4-471 1984 REPLACEMENT YES VALVE CO.7. Description of Work A valve bonnet stud was replaced.8. Test Conducted: Hydrostatic j] Pneumatic[] Nominal Operating Pressure[] N/A (K Other E] Pressure N/A PSI Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A'Certificate of Authorization No. N/A Expiration Date N/A Signed Owner o rl r Team Leader Data Owner or Own er's Designed, Title V-qi* OF INSERHVICE INSPIECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georal " and employed by Hartford Steam Boiler Insoectlon and Insurince Co. of Connecticut of Hartford. Connecticut have Inspected .the components described In this Owner's Report during the period 09/28/06 to ' /-I -_n-r. , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer slal be liable In any manner for any personal Inlury or property damage or a loss of any kind arising from or connected with this Commissions &*. ?'"&--' i~speo&r's Signature National Board, State, Province and Endorsements Onts as MAt 2.OD' ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Tra velar # 06090 5 1. Owner Southern Nuclear Operatinr Company Name 40 Inverness Center Parkway. Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant.Date 1/2/7 Sheet 1 of 1 Unit Name Waynesboro, GA 30830.Address 1 WO# 106176"01 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voctle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1201/Reactor Coolant System 5. (a) Applicable Construction Code ASME SEC III. 19 71 Edition, Summer 1972 Addenda, (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1982 1484-1, 1484-2 1528-3 Code Case 6. identification Of Components Repaired or Replaced end Replacement Components National Repaired, ASME-Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No)STEAM WESTINGHOUSE GAGT 1881 11 1-1201-B6-002 1981 REPLACEMENT YES GENERATOR ELECTRIC CORP.7. Description of Work Steam generator

  1. 2 hot leg primary manway stud numbers 9, 10, and 14 were replaced.0. Test Conducted:
9. Remarks See Item 7 Hydrostatic

[] Pneumatic[] Nominal Operating PressureX' Other C] Pressure N/A PSI Test Temp. N/A "F Cse 0IT-I07 0 Applicable Manufacturer's Dats Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed l Team Leader Date I SOwner or Owner's Designee, Tfle " CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of Hartford. Connecticut have Inspected the components described in this Owner's Report during the period 10/03/06 to i -,l --aob1, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins _______--____________Commissions fir4. 2!,V4 MIspec 'a Signature National Board, State, Province and Endorsements Date ",.f-bb'7 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl (A)Traveler# 06091 11/06/06 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet I Of 4-e3 01 2.Address Vogtle Electric Generating Plant Plant Unit Name Waynesboro. GA 30830 WON 1051821701 Address Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voqtle Address Type Code Symbol Stamp Authorization No.Expiration Date NWA W/A NI/A 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME SEC III 19 71 Edition, Summer 1972 Addenda, 1501, N-3-10 Code Ca.(b)Appllcable Edition of Section XI Utilized for Repairs or Rplacements 19&9'6. Identification Of Components. Repaired or Replaced and Replacement Components I National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped Component Manufacturer Serial No. No. Identification Built or Replacement (Yeas or No)VALVE FISHER 5909459 3253 1PV0455B 1981 REPLACEMENT YES CONTROLS CO.. __" 7. Description of Work Valve vee-ball was replaced. A copy of Form N-2 for the replacement yea-ball is attached.8. Test Conducted: NIA [X]9. Remarks See Item 7 Hydrostatic [ Pneumatic[] Nominal Operating Pressurel] Other Q] Pressure N/A PSI Test Temp. N/A Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed kJ Owner Team Leader Date it 'Le T.t\,I Owner or Owner's Designee, TitfibU.CERTIFICATE OF INSERVICE INSPECTION I 1, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessei Inspectors and the State or Province of Geor&Al and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut.Harr Conctut have Inspected the components described In this Owner's Report during the period 10/05/06 ..to X I vi and state that to the best of my knowledge .and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.'By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his.employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with Wehl I ne --.-, .Commissions u , -e". " Iýý Signature vNational Board, State, Province and Endorsements Date .9 'AM Jo jc " FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the Provisions of the ASME Code, Section III Not to exceed One Day's Production Pg. I 1AMme5I Cr 0609 1 S teet 2-4 f3 of I.025-N230173824 I. Manufisacred and certified by 2. for 3. Locationofinstallation FISHER CONTROLS INT'L LLC. 205 SOUTH CENTER STREET, MARSHALLTOWN. IA. 50158 (name ed address ofNPT Certificate Holder)Control Southern Nuclear Plants, 3850 Lakefield Dr. Strwmni, GA 30024 (name and address of purchase)Voldc Electric Gen. Plant. 7821 Rivet Rd. Wayneboro. GA 30330 (name and address)4. Type I V9098 Rev. H SA351 CF8M 70 KSl N/A 2005 (drawing no.)(mat'l. spec. no.)'97'7 (tensile Strength)Summer 1972 (CRN)(year built)N/A 5. ASME Code, Section I1: 1971 Sumiaw 1977 (edition)6. Fabricated in accordance with Consl. Spec. (Div. 2 only)(addenda due)(class)N/A (Code Case no.)Date N/A N/A (no.)Revision 7. Remarks: Design: ASME BPVC Sec 111. 1971 Edition, Summer 1972 Addenda, Class I Othe.: ASME BPVC Sec 011 1989 Edition, No Addenda, Class I 8. Nomr. thickness (in.) N/A Min. design thickmess (in.) NIA Dia. ID (ft &un.) N/A Length overall (ft &.in.) N/A I 9. When applicable. Certficate Holders' Date Reports re atarched for each item of this report-Y --Part or Appurtenance Serial Number A!H6399-1 Heal Number Par or Appurtenance Serial Number He Number (I)(2)(3)(4)(5)(6)(7)(8)(9)(10)(11)(12)(13)(14)(IS)(16)(17)(I8)(19)(20)(21)(22)(23)(24)(25)MXIO SN W35" (26)(27)(28)(29)(30)(31)02)(33)(34)(35)(36)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(48)(49)(50)4 --_ _ _ _ _ _ _ _ _ _ _ _ _ _10. Design Pressure 2485 psi.Temp. 650 OF.Hydro, test pressure N/A at temp. OF (when applicable1 OSupplenental information in the form of lists. sketches, or drawings may be used provided (1) size is 8 1/2 x II, (2) information in items 2 and 3 an this Data Report is included on each sheet, (3) each sheet is numbered end the number of'sheets is recorded at the top of'this form. -rave Ier,# 06091~ISVer+ 3 ."FORM N-2 (back)(S Mfi. Serial No. AH6389-! I CERTIFICATION OF DESIGN Design specifications certified by Henry P. Leonard P.E. State PA: Reg, no. 23938-E (who applicable) Design repone cenified by N/A. PL, State N/A R .no. N/A (when applicable) CERTIFICATE OF SHOP COMPIdANCE We certify tht dhe statements made in this report are correct and.tdat this (then) Ven-Ball Sub Aýy contiomua to dle rule of construction of dte ASME Code, Section M.NPT Certificate of Authorizaion No. 193.0 Expires tO-27-20Q7 Date 12/7/05 Name FTSHERCONTROLSfl0("L LLC Sim tN" Cra.iscaft Holder) (aut(a ,orized meprts9swe W CERTIFICATE OP SHOP INSPECTION I, the undesigwed, holding a valid conmmission isued by the National Baoad ofBoilae.and Pressure Vessel ispec'tof and the state or Province of Iow and employed by Haitffrd Steam Boiler of CT .I of Hartfrd, CT ban inspected dine items decribed in this Data Report on --and statmme liato the be of my knowledbe and belief, Cenfloaw Holder has &hricated these pts or appurtlnances in accordance with the ASME.Code, Section IlL r liHted has bee authomrizd far stmping on the date shown above.Dyslptigng dibi catifimle, neither the ihtpector nor his employer makes any warrany. expreased or implied. concerningithe equipmemn described in.dths Data R:po -.Furthenrmore neither the inspector nor his employer ah be liable in any manner for any peisonal injury or Property damage or loss of any kind aising frm or cornncted with this inspection. DameP D Signed ~ s t 'Commissfions X'(Authorized I (Nat'l. Rd. (incl. endorsements) state or proy. and no,)I 2-36-6.do< ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl 07052 i Traveler #09/17/07 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Voatle Electric Generating Plant Date Sheet I of 3 Unit 1 Name Waynesboro, GA 30830 Address WO# 1070278101 Repair Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voage Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1301/Main Steam Svstem 5. (a) Applicable Construction Code ASME SEC III 19 77 Edition, Winter 1977 Addenda, N/A (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 6. Identification Of Components Repaired or Replaced and Replacement Components Code Ca'se National Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced, Stamped, Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or Noj VALVE CONTROL 23468-1.4 N/A IPV3030 1982 REPLACEMENT YES COMPONENTS INC.& & .1 7. Description of Work Valve plug was replaced. A copy of Form N-2 for the replacement plug (S/V 154041-2) is attached.I 8. Test Conducted: WA[K 9. Remarks See Item 7 Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] Other [] Pressure N/A PSI Test Temp. N/A F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Aut Irzation No. N/A Expiration Date N/A 1 Signed .= Team Leader Date nher or Owner's Designee, Itie WI#16ýCERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by Hartford Steam Boiler Inspection and Insurance Co. oI Connecticut ol Hartord. Co c have Inspected the components described In this Owner's Report during the period 02/26/07 I to .0 .and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section IXI.I ,Br lng this certifie, npither the inspector nor his employer makes any warranty, expressed or Implied, concerning fthe m o nd corrqt saures described in thE Owners Report. Furthermore, neither the Inspector nor his employer shall liable a an rror= personal lnlu property damage or a loss of any kind arising from or connected with this~jaa(Commissions (4- o0 o1I. -liispecfor's Signiture Data -a`O 0 National Board, State, Province and Endorsements Trueterw 01OS5-skeeti 20431-.2 Form 1)FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the Provisions of th ASME Code, Section I1.Not to Exceed One Dav's Production Pa.1 of 2-1. Manufactured and certfied by Control Components Inc. (CCI)22591 Avenida Ernymsa. Rancho Santa MaMarfia, CA 92688 t (nana and address of Crtificate Holder)2. Manufactured for GEORGIA POWER COMPANY, ALVIN VOG7LE PLANTAAUGUSTA. GEORGIA (name and address of purchaser)

3. Location of Installaton ALVIN VOGTLE PLANT, AUGUSTA, GEORGIA (name and address)4. Type 320601696 SA-182-F11 70 K.S.I. N/A 2002 (drawing no.) (mall Spec. no.) (tensile strngth) (CRN) (year built)S. ASME Code. Section III. Division 1: .1977 WINTER 1977 2 N/IA (edition) (addends date) (class) (Code Case no.)6. Fabiricated In accordance with ConAt Spec. (dliv. 2 only) N/A Revision N/A Date NWA (no.)7. Remdrils FOR ATMOSPHERIC DUMP VALVE CCI PROJECT 100456 8.Nom. thickness (in.) 3.2 Min. design lulchness 1.8 D. ID((R&In.)

1.5 9. When applicable. Certificate Holders' Daa Reports are atched for each item of the this report Length overatll(ft A n.) 11.1'1 I Part or Appurtenance Serial Number National Board NO.i Numerical Orter N/A Part or Appurtanm, Serial Number National Boarnd No.in Numerical Order (1.)(2.)(3.)(4.)(5.)(6.)(7.)(8.)(9.)(10.)(11.)(12.)(13.)(14.)(15.)(16.)(21.)(18.)(19.)(20.)(23.)(22.)(23.)(24.)(25.)1!i 1~.1 154041-2 N/A 15404143 N/A 154041-4 N/A i l I I 4 I.(26.)(27.)(28.)(29.)(30.)(31.)(32.)(33.)(34.)(35.)(36.)(37.)(38.)(39.)(40.)(41.)(42.)(43.)(44.)(45.)(40.)(47.)(46.)(49.)(50.)4. -I 1* --4. --I --4. --i I --4 --4.I i.i--4 4 4 4.-4. --4 I 4.4 4 4.4.4 4 4._________ ________ I,~1*10. Design pressure 1640 psi Temp. 600 Deg. F Hydra test pressure N/A at temp. 0 3g. I*Supplemental information in the form of r ists. sketches. or drswings may be used provided (t) sze is 112 x 11. (2) information in items I Ihrough 4 on this Dea Report is inluded on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the too of this form. I This farm (E00037) may be obtained from the Orer Oept., ASME, U Law Drive. Boa Z=30. Fairlield. NJ 07007-2300. r -S~neet 3oP3 Form N-2 S FORM N-2 (Back -Pg. 2 of .2)CeiMcate HaIslet'a Serial No.154041-1 though thru 154041-4 N/A CERTIFICATE OF DESIGN Design Specification certified by MARK Z. JEIRC P.E. State CA Reg. no. 12217 Design Rapo"

  • cerlified by N/A P.E. State N/A Reg. no. N/A (when applicable)

CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this (these) PLUG conforms to the rules of construction of the ASME Code, Section III, Division 1.NPT Certificate of Authorization N-2696 Expires JUNE 7. 2003 No.Date Name Control Components Inc. (CCI) Signed (NPT Cetificate Holder) (Auf*lrfel n-tve)CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Provinc of CALIFORNIA and employed by HSBCT of HARTFORD-CONNECTICUT have Inspected these Items described in this Data Report on 4t- 1 -X',c -, and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with ASME Section III, Division 1. Each part listed has been authorized for stamping on the date shown above. I By signing this certificate, neither the inspector nor his employer makes warranty. expressed or implied, concerning the equipment describe in this Data Report. Furthennore. neither the inspector nor his employer shall be liable In any manner for any personail injury or property damage orof any kind arising from or connected with this Inspection. Date A -OL Signed = t "'7 / -,--, Commlsslons 4 14"-4-, (Authoruized Inpecixr) (Nati 6d. (Including and Mst or pmv.. rnd no.) I ORIGINAL 40 SECTION XI REPAIR/REPLACEMENT TRAVELER PAGE 1 0F3 TRAVELER: 06094 REPAIR E5 REPLACEMENT Z , ---- ASSOCIATED DOCUMENTS----


COMPONENT


WO: A061951201 CODE CLASS: ASME III CI. 1 NF CR: N/A TAG NO: A-21 17-SNUBBERQ DCP: N/A DESCRIPTION Spare Snubber (PSA-1I)-OTHER:. AX4AQ18-168 SERIAL NO: 12859 WORK DESCRIPTION:

Install replacement telescopina sleeve.-EXAMINATION/TEST REQUIREMENTS


N/A VT-i N/A VT-2 N/A VT-3 OTHER N/A N/A NOMINAL OPERATING PRESSURE N/A PNEUMATIC N/A HYDROSTATIC PRESSURE N/A ý TEMPERATURE N/A HOLD TIME N/A FAILURE Evaluation for Suitability of Repair or Replacement

.No. Normal / Expected Wear E ALARA DCP Z EQ Checklist Yes Justification: Intended life if less than design life of repaired item: REPAIR/REPLACEMENT ORGANIZATION: Southern Nuclear Ooeratinq Co.------ INITIAL REVIEW-.-- GNADAT ~ HOLD POINTS A .WE 1 176A~ ElYES- 0 NONE ISI ENGINEER IEl YES AW NONE fl#MEPXAMINER __________ .YES 5NONE ANI I 5YES FINAL REVIEW---~S IcATU RE DATE SLGNA1IUR.E DATE 181 ENGINEEW'-7l' .s4-16 -2do a AWE ~ ~ 2t R EMARKS: &e I~iS4-~ K)-TS-z HOLD POIl S.ORIGINAL TRAVELER NO: 06094 ASME SECTION Xl TRAVELER INSTRUCTION SHEET WO: A061951201 PAGE 2 OF 3 and/or trace code number of the replacement part(s) is entered on 4 4 4 +the JML. If the Dart does not have any of these markings, ensure the part is identified with the warehouse label providing PO, MIR and PO line Item numbers. Ensure ASME Code Class of the replacement part(s) is entered on the JML.:2. Verify the serial number, heat and/or COC .£i fL/k trace code number-of the replacement part(s) matches what is recorded on the JML or the applicable documen-tation. If the part has no markings,_ utilize the PO, MIR'and Line Item__ numbers on the warehouse identifi-cation label.3. Verify that the ASME Code Class. CQC , b __________ for the replacement part(s) matches or .....exceeds that of the component in which it is being installed.

4. Install replacement part(s) in spare Maint. "5"CT JhiF,_,_snubber. CaC 1 U -ASME SECTION Xl BILL OF MATERIALS TRAVELER 06094 WO A061951201 PAGE 3 OF 3.,.N, " w XSE § E~~TIE Telescoping AX4AQ18- 26 1977W1977 wo- A-519 Gr. 1018 Sleeve. ..... 168 .. .. 44-)~q 7v, .,IO COMMENTS: .( 7 So) kA t'o TERI 2- I 0 5 z ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRPREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler#

07138 06/19/08 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet I of 1 Address 2. Plant Vogtle Electdric Generating Plant Unit 1 Name Waynesboro, GA 30830 Address 1062002601 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtle Type Code Symbol Stamp Authorization No.Expiration Date NAV NIA N/A Address 1201 /Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. I/i, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thr2063 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No PIPE PULLMAN POWER N/A N/A V1-1201-030-H601 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work SnubberADo-151, serial #133 was replaced with a snubber AD-151, serial #482.8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] ExemptnX Other [] Pressure psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Au~ IN/A Expiration DateNA Signed T eam Leader Date Z& (o Owne'r Owntr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford Coecticut have inspected the components described In this Owner's Report during the period 08/06107 to / and state that to the beat of my knowledge and belief, the Owner has performed examinations and taken correclve measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions C.A 7_r%4 fInspec s Signature National Board, State, Province and Endorsements Date E!ýw."' ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkwav. Birminiham, AL Date Sheet Traveler# 07145 07/02/08.1 Of 7 1 1060178403 Address 2. Plant Vogtlie Electric Generating Plant Unit Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vot/le Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for RepairlReplacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)1204 PIPING PULLMAN POWER N/A N/A 1K3-1204-015-01 1987 INSTALLED YES SYSTEM PRODUCTS I F09651 7. Description of Work Flow orifice assembly 1F09651 was installed. Installation required welding to the existing piping system. Installation of this orifice was in accordance with DCP 10601784. Copies of the data reports for the orifice assembly are attached.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic E] Pneumatic[]

Nominal Operating Pressure['J Other [] Pressure _ psi Test Temp.Exempt[]Dlii,'Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of n No. ,NA Expiration Date N/A Signed ~ Team Leader Date " 7-Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Ins.oction and Insurance Co. of Connecticut of .ar Ord, QCnnecticut have Inspected the components described in this Owner's Report during the period 07/16/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions &.4 Z"- Signature National Board, State, Province and Endorsements Date -.Tut-Y 4Q:. acc& Tr.,'e I e r -07(4 +FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production pg. I of 2 1. Manufactured and cert~ied by tonics. Incorporated, Bridgeville Division, 30 Curry Avenue, Cononsburq, Pennsylvania, 15137 (name and dnm of NPT Car~cAs Holde)2. Manufactured for West nghouse Electric Co.. 4350 Northern Pike, Monroeville, PA. 15146 (Ware Wr4 adiur d-pWue)3. Location of Installation -Vtle Electric Generating Plant -Unit 1, 7821 River Road. Waynesboro, GA 30830 (raw and adrml SA-312 TP 316 75.00 4. Type I0N25E50 Rev. 3 SA 182 TP 316 75-O.D N/A 2007 (dravt~lnumber) (min. 19Mc no.) (es $n"(CF"(yarbol

5. ASME Code, Section IlI, Division 1: 1974 Summer 1975 2 N/A (eodsmb (aldarda 4) (du-I (Cd.o u no.)6. Fabricated in accordance with Const. Spec. (Div. 2 only) N/A Revision N/A Date N/A (no.)7. Remarks IHS( Multi-Stage 8reakdown Orifice consisting of two weld neck flanoes welded to two pipe sections and two orifice odoaters.Manufactured on tonics Contract 1665. Supolied on Westinahouse Contract 4500208455.

The WestinChouse controct removes from Ionics ony Design Renort resDonsibilites for the Apourtenances.

8. Norn. Thickness (in.)_.337 in. design thickhess (in.) ---- Dia. ID (ft & In.) 0'- 83.22" 9. When applicable.

Certificate Holders! Data Reports are attached for each Item of this report Length overall ( ft & In.) W-3.8 Pari or Appurten'ance National Part or Appurionance Natitonbt Serial Number Board No. Serial Number Board No.in Nlumertcal order la, Nwriedfal Order (1 I-FO-9651 (26)(2) (27M______________ (3) (28) __________ (4) (29) ___________ (5) ________________________ (30) __________ (6) ________________________ (31)(7) __________________________ (32)(8) __________________________ (33) ___________ (9) ___________(34) (10) ___________ (35) ____________ ________________ (11) ___________________________ (36) ______________ (12) ____________(37) ___________ (13) ___________ (38) ____________ (14) ________________________ (39)(15) (40)(18) (A1) _________(17) ______________ (42) _______________ (18) _____________ (43)(19) (44) ___________ (20) (45) ___________ (21) __________ (46) ___________ (22) (47) ___________ (23) ________________________ (48) __________ _______________ (24) __________ _____________ (49) __________ _______________ (25) ________________________ (50) _________________________

10. Design pressure.

Iw psi. Temp. 250 *-F. Hydro. Test pr'essure 2800 at temnp. .,.L F teMM swcba*Supplemnental infonrmation in the form of llsts, sethesoe. or drawinrgs may be uaed Prdovdd (1) size Is 8 'A xl1i. (2) Informnationr in Itoens2asnd 3 on Wei Dats Report is inctluded on each sheet. (3) eachi sheet is numbered and the number of sheeta Ia recorded at ttu top of this foirm.(?~9fJ This form (E00040) may bie obtained froms the Order dept.. AS$4E. 22 Law Drtve. Sax 2300, Fairftlod. NJ 07007,2300. Page 10 of 177 5'ee'e 3o-C 7 FORM N-2 (Back -Pg 2 of 2)Certificate Holders Serial Nos. I-FO-9651 through CERTIFICATION OF DESIGN Design specifcations certified by John L. Robinson P.E. State PA _Reg. No. 072588 (when applicble) Design report' certified by NIA P.E. State N/A Reg, No. N/A (When applcable) CERTIFICATE OF COMPUANCE We certify that the statements made In this report are correct and thal this (these) IHSI Mull-Stace Breakdown Orifce conforms to the rules of consbuction of the ASME Code, Section I11, Division 1.NPT Certificate of Authorization No. N-2974 Expires March 2e. 2008 Date 2 -2 Name Ionics. Incorporated -Bridgeville Division Signed (NPT Critflcate Makler) taullbornzd repreeantaove) CERTIFICATE OF INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One Beacon America Insurance Co.of Boston. MA have inspected these Items described in this Date Report on 6 2.- Z- .-",AA7 , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated thse parts or appurtenances In accordance with the ASME Code, Section 1li, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or imptled, concerning the equtpment described In this Data Report. Furthermore, neither the Inspector nor lls employer shalt be liable In any manner for any personal njury or property damage or loss of any kind arising from or connected with this Inspection. Date OZ-_2-2c"7 Sign7ý Commissios -,lzed lud.lnape f (Nail. Od. (inri. andorsemente) and sMe or prow. and nol Page 11 of 177 T~vI~r~/0714 S S6,eei 4ofi 7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production P9. i of 2 1.2.3.Manufactured and certiid by Ionics, Incorporated, 8ridgeyfile Divison.. 30 Curry Avenue. Canonsburg, Pennsylvania, 1513 7 (Pnm adS sWida a NPT C*Vtw H*i Manufactured for Westinqh0-se Electric Co., 4350 Northern Pike, Monroeville, PA. 15146 (ra* KW afum d pwchaW)~vnrtle FI,,trie (Senerrttinf PRant -Unit 1. 7821 RIver Road. Wavnesboro. GA 30830 Location ot In IdUaLlun Vonde Elettric Gpneratina Plant -Unit 1 7821 Piver Rood Wavilesboro GA 30630 4. Type 10025E50 Rev. 3 SA-312 TP 316 75,000 N/A 2007 ( drming Srunte) fin'I. Spec no.) (lantsla ngtr) ICRNI) (e bIall 5. ASME Code. Section III. Division 1: 1974 Summer 1975 2 N/A (Wall) IE 1Ira dab) Was,) iamr 6. Fabricated in accordance with Const, Spec. (Div. 2 only) N/A Revision N/A Date N/A Inc.)7. Remarks IHSI multi-Stage Breakdown Orifice Extension Adapters consistinr of a oioe welded to o weld neck flange, Monufactured on lonics Contract 166S. Suootied on Wesrinahouse Contract 4500208455, The Westinghouse controct removes from Ionics any Design 1 RePOrt resoC; for I.5.8. Nom. Thickness (In.)_,21.fln. design thilcitwes (in.) -Dia. ID (It & in.) 0'- 3.822= Length overall (&in.) 0'-17.12'9. When applicable, Certificate Holders' Data Reports are attached for each Rtem of this report: Part or Appurtenance National Senal Number Board No.In Nurnerical order () 1-F0-9651-A (2) _____________ _(3)(4)(5) ___________ _____________ _(6) __________________________ (7) ____________ ______________ (11) ________________ (12) ___________ (13) ___________ _____________ (14) ___________ (17) __________ (17) __________ ____________ (218) __________ (19) ___________ (25)i (26)(27)(28)(29)(30)(31)(32)(33)(34)(35)(36)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(40)(49)(50)+'I.4-Part or APPWUntance National Seral Number Board No.in N"Wricarl order I 10. Design pressure 1860 psi. Temp. 250 *F. Hydro. Test pressure 2800 at tamp. .5i* F-wa appale"Supplemental Infaormation in the farm of lists. sketches, or drawings may be used provided (1) size IsA x 11, (2) Innftmon In items 2 and 3 on til Date Report is included an each 0 1heel. 13) each sheet is numbered and ft number of slheaelI rcorded o " top of thlls form.iistT his form (E00040) may be oblalned romn the Order dept. ASME. 22 Law Drive, Bax 2300. Fairfeld, NJ 07007-2300. Page 12 of 177 Tr&,e~r$'07145 c3kefA 5 o-( 7 FORM N-2 (Back -P9 2 of 2)Certificate Holdees Serial Nos. 1-FO-96S1-A through_CERTIFICATION OF DESIGN Oesign specifications centifled by John L Robinson P.E. State PA Reg. No. 072588 (when appliable) Design report certified by .N/A P.E. State N/A Reg. No. N/A (when appilabua) CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) IHSI Multi-Staoe Breakdown Odlfce Extension Adapter conforms to the rules of construction of the ASME Code, Section Ill, Division 1.NPT Certificate of Authorization No. N-2974 Expires March 265 2008 Date Z, gi'O- Name 1onics. Incorporated-Brid eville Division SIgned (NPT Cerdficate Holder) (authorized reprm ntadve)CERTIFICATE OF INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One Beacon America Insurance Co.of Boston, MA have Inspected these Items described In this Data Report on , Z -2 0 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section ill, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipmlent described In this Data Report. Furthermore, neither the inspector nor his employer shalh be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection. Date 02 2 .00-7 Signea Commissions PA 44'e- -zed Nuclear inspeemrI lNatl. 8d. (incl. endorsermnts) and state or prov. end not Page 13 of 177.==50i 07145 S~tee4+ 4of 7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production Pg. 1 of 2 1.2.Manufactured and certified by lnics. Incorporoted. Bri.dgeviile Division. 30 Curry Avenue. Cononsbua .Pennsylvanio. 15137 (unit and asis of NPT C *tlr. I Hakd}Manufactured for Westinghovuse Electric Co./4350 Northern Pike, Monroeville. PA, 15146 (infrm mr amd adisa wipivf , ... , .,..,u,.,; WUrntlo I~,rnfrir Connrntinn Plrrnt -Unit 1. 7821 River Road. Wovnesboro. GA 30830 4.5.6.7.Mc] UI -11 41 t' El-tric Ganerobrin Plmnt -Linit 1 7821 River Road WovnL-sborci GA 30830-a on-)Type 10025E50 Rev. 3 SA-31Z TP 316 75,000 N/A ?007 I diiAnt; ruirdiat (fW1. SPIC 110.) lfmsif fbsntlr (CRN) (yesrnbig ASME Code. Section Ill, Division 1: 1974 Summer 1975 ? N/A (eadith) (adda dab) (des) (Cod. Cal M)Fabricated in accordance wilh Const. Spoc. (Div. 2 only) N/A Revision N/A Oata N/A (no.)Rema cIi;l MltihStnrne Breaikdown Orifice Extension Adooters consisting ofo Dioe welded to o weld neck flrnce.inufacturt II ContrOCt 1665. Supplied on Westinghouse Con r the Appurtenonces. ,500208455. The Westinnhouse contract removes from Ionics any Design Report reso S. Nomn.Thickness(i.l .37Iln. deslgn thicnessOn.j-_--_ Dla.ID(ft&InM) Y'.3.827 Length overall(fM&mn.) 0'-17.12'9. When applicable, Certificate Hoders' Data Reports are attached for each teom of thi report, Serial Number I-FO-965 1-8 National Doard NO.in Numerecal order (1)(2)(3)(4)(5)(6)(7)(8)(9)(12)(13)(14)(15)(17)(18)(20)(21)(22)(23)(24)(25)Pad t o Appurteanances National Serial Number Boased No.In Numerical Order (26) _ _ _ _ _ _ _ _ _ _ _ _ _ _(27)(28)(32) _ _ _ _ _ _ _ _ _ _ _ _ _ _(33) _______________ (34)__ _ _ _ _ _ _ _(35)__ _ _ _ _ _ _ _(35) _ _ _ _ _ _(37)(38) ___________ (39) ______________ __________________ (40)__ _ _ _ _ _ _(41)_______ _____ ________ __ __ __ _(42) ______________________________ (43) ____________ _______________ _(44)__ _ _ _ _ _ _ _ _ _ _ _ _ _(45) _ _ _ _ _ _ _ _ _ _ _ _ _(40) _ _ _ _ _ _ _ _ _ _ _ _ _(47) ____________ _______________ _(48) _ _ _ _ _ _ _ _ _ _ _ _ _(49) _ _ _ _ _ _ _ _ _ _ _ _ _(50)_______________________ I ___10. Design pressure 1860 psi. Temp. 260 'F. Hydro. Test pressure 2800 at temp. _5" F'Suppdemental information in (he form of IsmI sketches, or drawings may be used prvided (1) ize Is 8A x 11, (2) informnatlon in items 2 and 3 on tils Data Report Is inculued on each sheet. (3) each sheet Is numbered and tie number of sheeft is recorded at eth lop of is form.l9fi8 This form OE00040) may be obitined from the OrdardeptL, ASME. 22 Law Drive, Box 2300. Fafriteld, NJ 07007-2300. Page 14 of 177 TrmoedIer e- 07/4-:5 he 707 FORM N-2 (Back -Pg 2 of 2)Certificate Holder's Serial Nos. FO-9651-B through-CERTIFICATION OF DESIGN Design specifications certified by John L Robinson P.E. State PA Reg. No. 072588 (when applicable )Design report' certified by NIA P.E. State N/A Reg. No. NIA (when applicale )CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this (these) IHSI Mul-Staoe Breakdowm Orifice Extension Adapter conforms to the rules of construction of the ASME Code. Section III, DIvision 1.NPT Certificate of Authorization No. JH-2974 Expires March 26. 2008 Date z. ' Name Ionics. Inconmorated -Bridgeville Division Signed _ ._______,_(NPT Certificate Holder) Cauthorized repreentlative) CERTIFICATE OF INSPECTION I, the undersigned, holding a vatld commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pgennsylvania and employed by One Beacon America Insurance Co.of Boston. MA have Inspected these Items described In this Data Report on QZ-Z- -r0'7 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code. Section Il, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this Data Report. Furthermore, neither the Inspector nor his employer shah be liable In any manner for any personal injury or property damage or loss of any kind adsing from or connected with this inspection, Date Q?2&b 7 Signed Commlssion P,24-( '-r horized Nuclear inspetor) (Nell. Bd. (nci. ridorsernenla)and astrate or prov. aMd nol Page 15 of 177 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler# 07147 07/02108 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birminnham. AL Date Sheet Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address 1_ _ _ _ Of 1 Unit 1060178403 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A Address 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME Sec. I11. 1977 Edition, Winter 1977 Addenda, N/A (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2O03 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components Code Case National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)1204 PIPE PULLMAN POWER N/A N/A V1-1204-015-H006 1987 CORRECTED YES SUPPORT PRODUCTS _7. Description of Work Pipe support was modified par DCP 1060178401.

8. Test Conducted:

Hydrostatic F] Pneumatic[] Nominal Operating Pressurejj Exempt[K Other [] Pressure psi Test Temp. -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Auth 1 ation No. N/A Expiration Date N/A Signed .. Team Leader Date Owner-of"Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Oeorala and employed by Hartford Steam Boiler Ins.ectlon and Insurance Co. of Connecticut of H o Cnnecticut have inspected the components described In this Owner's Report during the period 07/16/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.-Inpoc9A igntur Commissions G 4 .)Z" -lnspect Signature National Board, State, Province and Endorsements Date 7ZALY gf .10CR FORM NIS-2 OWNER'S FC 'ILACEMENT ACTIVITY As Required EIr~f I Section XI 48 lravelerw 7i1, July 22. 2008 1. Owner 2. Plant Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birnmingham, AL Date Sheet Unit I *__ _ _ _ _ _ Of 7__eat,"_Address Vogtle Electric Generating Plant Waynesboro, GA 30830 WO 1060178402 Address RepairlReplacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Name Plant Vogtle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A 4. Identification of System 1214 / Safety Iniection System 1204 / Safetv Ini lion Svstern 6. (a) Applicable Construction Code ASME Sec. III 1977 Edition, Winter 1977 Addenda, n/a (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 d. 2003 add.(c) Applicable Section Xi Code Case(a)6. Identification Of Components Code Case 6 TIz4Ge I National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped'Comeonent Manufacturer Serial No. No. identification Built Installed Yes or No)1204 PIPING PULLMAN POWER N/A N/A 1K3-1204-057-01 1987 INSTALLED YES SYSTEM PRODUCTS 1F09650)I 7. Description of Work A flow orifice IF09650 was Installed. Installation required welding to the existing piping system and the additioln of spacers. One of the spacers was replaced by an orifice plate due to flow test results under Traveler #07149.Installation of this orifice was In accordance with DCP 1060178401. Copies of the data reports for the orifice assembly are attached. I 8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] Pneumatic[] Nominal Operating Other [] Pressure _pal Test Temp.Exempt[]Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANC 'I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbo Stamp N/A Certif icate I oriz ~n 9 NIA Expiration Date W/A of 4~~Signed oJ Cvinr'sDesignee, Title Team.Leader Oat CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Bolier and Pressure Vessel Inspectors I and the state or Province of Geaoria and employed by Hartford Steam Boiler Insoecfion and Insurance Co. of Connecticut of o ctit have Inspected the components described in this Owner's Report during the period 7/16007 " to 4ad. _ -and state that to the best of my knowledge and belief, the Owner has performed examinations and 6ken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer ihall be liable In any manner for any personai Injury or property damage or a lose of any kind arising from or connected withl this Inspection. .. ..__ _ _ _ .. .. _ _ _ _ _ _ Commissions ."lnspectoW'Signature* '- National Board, State, Province and Endorsements Date ,, .zL'_. I $~ea~L 2a47 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production P9. I of 2 1. Manufactured and certifled by Ionics, Incorporated, Bridgeville Division, 30 Curry Avenue. Cononsburo. Pennsylvarna. 15137 (nme arid ade of NPT Cwtflicale Holdel 2. Manufactured for Westinghouse Electric Co., 4350 Northern Pike, Monroeville, PA, 15146 (Who4 W id udrees or puilmeoor 3. Location of installation Voctde Electric Generatina Plant -Unit 1. 7821 River Road Woynesboro, GA 30830 (hwor and ddremi)SA-312 TP 316 75,000 4. Type 10025E50 Rev. 3 SA 182 TP 316 75.0 N/A 2007 Idtamfsi number Irsaf spec; sa.) (leasi. Masgdl( (CRN) 6-e buI 5. ASME Code. Section III. Division 1: 1974 Summer 1975 2 N/A (aftil) (aderedeleJ (dma) (Ced c" no.)e. Fabricated in accordance wlh Const. Spec. (DIv. 2 only) N/A Revislon N/A Date N/A (noj 7. Remar(s HHSI Multi-Stoge Breakdlown Orifice consistina of twq weld neck flanges welded to two pipe sections and two orifice adopters.Mnnufnctured on Ionics Contract 1665, Supplied on Westinghouse Contract 4500208455. The Westinahouse contract removes from Ionics ony Design Report I r the Appurtenances. B.Norn. Thickness (in.)_.5M1jn. design thicknes (Itn.) --- DIa. ID (ft & In.) 09- 3.438 When applicable. Certificate Holders' Data Reports are attached for each Item of this report: Aat or Nalursoian Length overall (ft &in.) 4'-3.80 Serial Number 1-FO-9650 Board No.in Numerkoat order Foet or Serial Number National Board No.In Numerical Order (1)(2)(3)(4)(5)(6)(7)(8)(9)(10)(11)(12)(13)(14)(17)(16)(20)(21)(22)(23)(24)(25)(26)(27)(28)(29)(30)(31)(32)(33)(34)(35)(36)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(48)(49)(50)I+4-10. Design pressure 3100 psi. Temp. 250 "F. Hydro. Test pressure 4700 at temp. _5" F heMa Spcble)'Supplemental information in Ibhe form of lIts. Slelctles, or drawings may be used provided (1) is 8 A x 11. (2) information in Item 2 and 3 on this Data Report Is Incmucleo on each sheet. (3) each aheet is numbered and the number of shedls 1A recorded at the top of aft form.(7198) This form (E00040) may be obtained f(Mm the Order deptl, ASME. 22 Law Orte. Box 2300. Fairfield, NJ 07007.2300. Page 4 of 177 -rwiele(2il 0148 Sheet 34 1 FORM N-2 (Back -Pg 2 of 2)CertIficate Holder's Serial Nos. 1.F0-96gS through.CERTIFICATION OF DESIGN Design speciications certified by John L. Robinson P.E. Slate PA Reg. No. 0725B8 (wher applicable) Design report' certified by NIA PE. State N/A Reg. No. N/A (when applicable) CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this (these) HHSI Multi-Stage Breakdown Orifice conforms to the rules of construction of the ASME Code. Section III, Division 1.NPT Certificate of Authorization No. N-2974 Expires Match 26- 2008 Date 2 -Z If- 7 Name Ionics. Incorprted -Bridfevjlle Division Signed -f ..Z , (NPT CeIllftCat Holder) (authortzed represenlatve) CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of PcnnsiYlvania and employed by Onc Beacon America Insurancc Co.of Bopton. MA have Inspected these Items described in tis Data Report on 60-Z tl .Cb -.. and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code, Section IlI, Division 1. Each part listed has been authorized for stamping on the date Mown above.By signing this certificate, neither the Inspector nor his employer makes any varranty, expressed or Implied, concerning the equipment described in this Data Report Furthermore, neither the inspector nor his employer shall be table In any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection. oate OZZ 2(-0-7 Sine Commissions P~~,/~54A"hodld Nuclear Inspector) (NtlN, 8d. (Ind. endorwments) end state or prIy. and no)' Page5 of 177 ,Shee 4,(7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III.Not to Exceed One day's production Pg. i of 2 1. Manufactured and certified by Ionics, Incorporated, Bridgeville Division, 30 Curry Avenue. Canonsburg, Pennsylvania, 15137 (wren 4 oird esa d NPT Cerika.e Holder)2. Manufactured for Westinghouse Electric Co., 4350 Northern Pike, Monroeville, PA, 1S14§oarnei alrd am of uriaser 3. Location of Installation Voqtle Electric Generatino Plant -Unit 1. 7821 River Rood, Woynesboro, GA 30830 (nafie a adreen)4. Type 10025E50 Rev. 3 SA-312 TP 316 75.0 .MIA 2007 (idre",n nuber) (marl spec na. (lensils siremptlij (CN) (yea bull)5. ASM. Code, section III, Division 1: 1974 Summer 1975 2 N/A (ad"ton (aiiG8G8W) (Ciacss (Gods cue no)6. Fabricated in accordance with Const Spec. (Dlv. 2 only) N/A Revision N/A Date NIA rno.)7. Remarks HH1S Mult-Stocme Breakdown Orifice Extension Adopter consisting of a pive welded to a weld neck flange.Monufactur.ed on Ionics Contract 1665. Supplied on Westinghouse Contract 4500208455. The Westinghouse controct removes from Ionics Ony Design Report resoonsibilities for the Aoourtenances.

8. Nom. Thickness(tn.)

ji.5 tn. design thlicneas (in.)_ Dia.IO(ftiln.) 0'-3.43r Length overafl(ft&ln.) 0'-17.38" 9. When applicable, Certificate Holders Data Reports are attached for each item of this report Part or Appurtenance National Serial Number Board No, Serial Number Board No.in Numernicl order in Numeninc Order (1) (-FO-9650-A (26)(2) (27)(3) 1 (28)(4) (29)(5) (30)(6) (31)(7) (32)(8) (33)(9) (34)(10) (35)(11) (36)(12) (37)(13) (38)(14) (39)(15) -_(40)(16) (41)(17) (42)(18) (43)(19) ,, (44)(20) (45)(21) (48)(22) (47)(23) (48)(24) (49)(25) (50)10. Design pressure 3100_ psi. Temp. 250 "F. Hydro. Test pressure -47.0 at temp. 6 , F'Supplemental Inlormation In l/a form to raisi. sketch-es. or drawings may be used proirded (1) is a V. X 11. (2) information in temsr 2 and 3on thits Oats Reor ts included on each helel. (3) each sheet is numbered and the number of sheoets i recorded at toelop of this form, 7/95) This form (EO0040) may be obtelned from the Order dept., ASME, 22 Law Drive, Box 2300. Fakiteld. NJ 07007.2300. Page 6 of 177 --rriv ter W 0 O7i4-Slhert 5e47 FORM N-2 (Back -Pg 2 of 2)Carnlfl'cate Holder's Sergal Nos. I-FO-9650-A through CERTMFICATION OF DESIGN Design specJficallons certified by John L. Robinson P.E. State PA Reg. No. 072588 (Ywhen applicable) Design report' certifed by NIA P.E. State N/A Reg. No. N/A (when applicable) CERTIFICATE OF COMPLIANCE We certiif that the statements made In this report are correct and that this (these) HHSI Multi-Stame Breakdown Orifice Extensiorn Adapter conforms to the rules of construction of the ASME Code. Section iII, Division 1.NPT Certificate of Authorization No. N-2974 Expires March 28. 2008 Date 2'2-o" Name Ionics. Incorporated -Bndaevilce Division Signed <---(NPT Cerfricate Holder) (authorized represtaUve) CERTIFICATE OF INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One BaacoD Am-bica Insurance Co.of Boston- MA have inspected these items described kI this Data Report on 0 Z-?"2- "7 , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code. Section ifi. Division I. Each part listed has been authorized for stamping an the date shown above.By signing this ceritficata, neither the Inspector nor his employer makes any warrranty. expressed or Implied, concerning the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection. Date or N rpor Commissions -PAZ(n4t (ý~ oie Nula Iselr Nall. ad. Oncl. endorsements) arnd state or pov. and rio]Page 7 of 177 l-rAve c-r 0*£714-8 5reet d 7 FORM N-2 CERTIFICATE HOLDERS' DATA REI'ORT FOR NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production Pg.l of 2 1. Manufactured am certified by lonics. Incorporoted. Bridgeville Division., 30 Curry Avenue. Cononsbura. Pennsylvonior 15137 (mae wid aftrag of NPT Curiltcab hktr)2. Manufactured for Westinghouse Electric Co., 4350 Northern Pike, Monroeville, PA. 15146 Iname and rrAvM of purdmwa)3. Location of installation Vogtle Electric Generoting Plant -Unit 1. 7821 River Road Woynesboro, GA 30830 aImes aid adfrtos 4. Type 1002SESORev. 3 SA-312 TP 316 750MO -N/A 2W07 ( dreaoig numbee) (mail. 1ws Me.) taballl luirgir) (CRNI I (ebut)5. ASME Code, Section Ill. Division 1: 1974 Summer 1975 2 N/A (adika) igdftxbdatei) Melas) (Code cue nyo 6. Fabricated in accordance with Coast. Spec. (Div. 2 only) N/A Revision N/A Date NIA (ra)7. Remarks .HHSI Multi-Stoae Breakdown Orifice Extension Adopter consisting of a lpie welded to a weld neck flanQe, Manufactured on Ionics Contract 1665. Supplied on Westinghouse Contract 4500208455. The Westinghouse contract removes from Ionics any Design Reoort responsibilities for the Appurtenonces, 8. Nom. Thickness (in.)531i.n. design thickness (In.) ---. Dia. ID (t &a In.) 0- 3.43r Length overall (ft &in,) a-17.38.9. When applicable, Certificate Holders' Data Reports are attached for each item of this raport: Part Or Appurtenance Serial Number National Board No.tn Numarical order (1)(2)(3)(4)(5)(6)(7)(8)(9)(10)(11)(12)(13)114)(IT)(16)(17)(18)(19)(20)(21)(22)(23)(24)(25)4.4.10. Design pressure -100 psi. Temp. 250 *F. Hydro. Test pressure 4700 at temp... 'LF Supplemental ninformation in the form of iisis. sketches. or dmrwings may be used prOvided (1) sl2b Is a A x 11, (2) information in Items 2 end 3 on this Date Report is inOuded on each sheel, (3) each sheet is numbered and fe numberer 'iseets i recorded ati U elop of pia form.171%) This form (E00040) may be obtained trom the Order dept., ASME. 22 Law Drive. BoX 2300, Faitld. NJ 07007-2300. Page 8 of 177 S heet 7o4 7 FORM N-2 (Back -Pg 2 of 2)Certiicate Holder's Serial Nos. 1-FO-9650-B through.CERTIFICATION OF DESIGN Design specifications certified by John L. Robinson P.E. State PA Reg. No. 07258M (when applicable) Design reporr certified by NIA , P.E. State N/A -Reg. No. NWA CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) _ HHSI Multi-Staoe-Breakdown Oriflce Extension Adapter conforms to the rules of construction of the ASME Code. Section III, Diviston 1.NPT Certificate Of Authorizatnon NO. N-2974 Expires March 26 200W Date Name Ionics. Incormorated -Bridgevflle DLvision Signed (NPT Certificate Holder) (authoriz red osentatiwe) C1RN'FICATE OF INSPECTION i, the undersigned, holding a valid Commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania -and employed by One Beacon AmericA Insurance Co.of Boston. MA have Inspected these items described in this Data Report on -0 Z .2 b- and state that to the oest of my knowledge and belief, the Certfilcate Holder has fabriceted these parts or appurtenances In accordance with the ASME Code, Section Ili, DIvision 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the Inspector nor his employer makes any vrranty. expressed or Implied, concerning the 'equipment described In this Data Report. Furthermore. neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or loss of any kind arising from or connected with this Inspection. Date o -.o-. _7 Signed :7-- ---Commissions PA'2-f;,*,9 inzed Nuclear Inspector) WNatl. 8d. (ind. endomecents) and state or prov. and riol Page 9 of 177 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 07150 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Address 2. Plant Vogtle Electrc Generating Plant Sheet Unit 07/02/08 Of 7 1 1060178404 Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance DeDartment Name Plant VoglielType Code Symbol Stamp Authorization No.Expiration Oate NIA N/IA N/A Address 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME Sec. 11i, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A S. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Ytes or No)1204 PIPING PULLMAN POWER N/A N/A IK3-1204-014-01 1987 INSTALLED YES SYSTEM PRODUCTS IIF09652 7. Description of Work Flow orifice assembly 1F09652 was Installed. Installation required welding to the existing piping system. Copies of the data reports for the orifice assembly are attached.8. Test Conducted: Hydrostatic [] PneumaticE Nominal Operating Pressure'x] ExemptE]Other [] Pressure _psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASM E Code, Section XI.Type Code Symbol Stamp N/A Certificate of n No ..NaA Expiration Date N/A Signed "Q J Team Leader Date Owner oJr Ownei's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by Hartford Steam Boiler Inspection and Insurance Go. of Connecticut of Hjatord, C.nnecticut have Inspected the components described in this Owner's Report during the period 08/06/07 to r a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions &4. 756.linspeca-s Signature National Board, State, Province and Endorsements Date 2;t ~;ý" s~reest ~2oa FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production Pg. 1 of z 1. Manufactured and cerlfled by Ionics, Incorpqrnted. Bridgeville Divj~ion, 30 Curry Avenue. Cononsburg. Pennsylvania, 15137 (arne and xun ol NPT C40cals HOW 2. Manufactured for Westinghouse Electric Co.,/4350 Northiern Pike, Monroeville. PA. 15146 Ina" ad edmf of wcilwwa)3. Location of Installation Voqtie Electric Generatinq Plant -Unit 1.7821 River Rood, Waynesboro, GA 30830 ren and addrss)SAo312 TP 316 75,000 4. Type 100Z5E90 Rev. 3 SA 182 TP 316 75.000 N/A ;g07 I daoirgrrluber (me spec roi (lmntifrn1"01h ICRNI (Yom kd 5. ASME Code, Section Ill. Division 1: 1974 -Summer 1975. 2 N/A (dmon) (adcrdedaat (darl (Code Ca no.)6. Fabricated in accordance Wth Const. Spec. (Div. 2 only) N/IA Revision N/A Date N/A 7. Remarks IHSI Multi-Stoge areakdown Orifice consisting of twA weld neck flanqes welded to two pi0e sections and two orifice adopters.M,,n,,fnrtured on Ionics Contract 1665. SuoDqied on Westinghouse Contract 450028455. The Westinghouse contract removes from lonics any Design Report resp[or I Length overall (ft & in.) V'-3.80", 8. Noam, Thickness (in.)_.3jUn. design thickness (in.) ---- Dia. ID (ft & In.) 0- 3.82g " 9. When applicable, Certicate Holders' Data Reports are attached far each Item of this report: Part or Appurtanairm Serial Number 1-FO-9652 National Beoar No.in Nu-mrical order Pad or Appurtenance Sedal Number National Board No.In Numerical Order (1)(2)(3)(4)(5)(8)(7)(8)(9)(10)(11)(12)(13)(14)(15)(17)(18)(20)(21)(22)(23)(24)(25)(26)(27)(28)(29)(30)(31)(32)(33)(34)(3-5)(36)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(48)(49)(50)++10. Design pressure 1060 1 psi. Temp. 250 'F. Hydro. Test pressure 2800 at temp. jj " F t" aw)catl)'Supplemental in the form of lsts. sketches, or drawivgs may be used prvided (1) sIze Is 8a xi11, (2) nfonrmalion in iftoms2 and 30n IhS Matn Report Is included on each sheet. (3) each sheet is numbered and the number of sheets Is recorded at the lop of this "orm.a7/9B) This form (EO0040) may be obtained from the Order dept., ASME, 22 Law Drive. Box 2300. Failield, NJ 07007.2300. Page 16 of 177 6ee-t 3,47 FORM N -2 (Back -Pg 2 of 2)Certtficate Holdefs Serial Nos. 1-FO-9652 through..CERTIFICATION OF DESIGN Design specifications cartified by John L. Roblnson P.E. State PA Reg. No. 072588 (wtmn appllcaGe )Design report! certified by N/A P.E. State N/A Reg. No. N/A (when CERTIFICATE OF COMPLIANCE We certify that the statements made in this report ate correct and that this (these) IHSI Muli-S iae Breakdown Orifice conforms to the ru)es of construction of the ASME Code, Section III, DivWon 1.NPT Certificate or Authorization No. N-2974 Expires March 28. 2008 Date Z-2T-o) Name tonics, Incomorated-Brideeville Division Signed _ ----____,__(NPT Certfcate Holder) (authorized (epTeseat5MUV) CERTIFICATE OF INSPECTION I. the undersigned. holding a valid commission Issued by the National Board of and Pressure Vessel Inspector$ and the Stale and Province of PennsylvaniA and employed by One Beacon America Insurance Co-of Boston. MA have Inspected these Items descrbed in this Data Report on end state that to the best of my knowledge and belief, the CertIriate Holder has fabricated these parts or appurtenances In accordance with the ASME Code, Section ill, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or loss of any kind arising from or connected with this inspection. Date 6 2-2~j- ?.'ZOO1 Sins commissions 'Z6(5hylrisd Nuclehr Inspector) (Nail.. So. (md. endontements) and slt.t or prov. andi nol Page 17 of 177

  1. / 09160 Skeet A-r l FORM N-2 CERTIFICATE HOLDERS' DATA RETORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production -.Pg.lIof 1. Manufactured and cserfied by Ionics. Incorooroted. Bridgeville Oivislon. 30 Curry Avenue. Canonsbura. Pennsylvania. 15137 (rame wb didress Of NPT Carfia Holder)2. Manufactured for Westinghouse Electric Co.. 4350 Northern Pike. Monroeville, PA. 15146 3. Location of Installation Voqtle Electric Generotin Plont -Unit 1. 7821 River Roaod. Woyesboro GA 30830 (noam and addres)4. Type 10025E50-Rev. 3 SA-312 TP 316 75,000 N/A 2007 (&aw-ig nwbi) (imaftl S roe.) (itithsfhogi JCRNI) /arkl 5. ASME Code, Section III, Division 1. _ 1974 Summer 1975 2 N/A (ediloa) (Addends dos) (d-) (Cwd cme no.)6. Fabricated in accordance with Conat Spec. (Div. 2 only) N/A -Revislon _NA Oato N/A 7. Remarcs iHSI MuWti-Stoae Breakdown Orifice Extension Adodters consi stinoof a-pile welded to oweWd neck fion-g.Manufactured on Ionics Controct 1665. Supplied on Westinqhoqe Contra.t 4500208455. The Westinahouse controct removes from Ionics any Desion Report responsibi.ities for the Anourtenonces.

8. Non. Thickness(in.)

.337,In. design thickness (In.)=--- Dfa. i(ftAln.) 0'-3.82,2 Lengthoveralli(ft8ln.)0Q"o.2" 9. When applicable, Certificate Holders' Data Reports are attached for each em of this report P eart o ubr Boardeanc Na o. Part OrAppurtemance National InalNffa Noardte No. Sadal Number Bowd Nm In Nuerica orde Nwnewlcs Oqdii ()(27) ____________ __________ (6) ___________ (31) ________ ___ ___________ (7) ___________ ______________ (32)____ ___ ____ _ ___ __ ____(8) ___ ________ ___ __________ (33)____ ___ ____ __ _____ ___(9) ___________ _____________ (34) _ _________ __________ (10) ___________ _____________ (35) ___________ (13) ___________ ____________ _ (38)___ __ __ __ ___ ___ _____ __ _(14) (39)____ ___ ____ _(15) (0 (16) (41) __________ _________(17) 142) ___________ __________ (18) ~~~~~~(43) _____________ (20) _________ _ (45) ___________ (21) 4_________ 46)(22) (47)(23) _________ _ (48)____ ___ ____ _(24) ___________ (49)(25) E M___________ (50)Design pressure .... I AD pal. Temp. 260 -'F. Hydro. Teat pressure 2800 at temp. _Ljj F totes ipm*10."Supplervn ntal information in the form of tlle. skletches. or drawings mns be Used Provided (1) sin is 8a. x11. (2) In items2and 3on Ot Data Report is included on each Sheet. 131 each sheet is nwubered and the nunber of is oroded at the top of this form.17M) Thil form (E00040) may be obai-ed fron the Order dept. ASAAE, 22 Law Drtve. Box 2300, Fairinaid, NJ 07007-2300 Page 18 of 177 0760Q Sbee L 5o-C 7 FORM N -2 (Back -Pg 2 of 2)Certificate Holder`s Serial Noe. 1-FO-9652-A through..CERTIFICATION OF DESIGN Design spelacications certified by John L. Robinson P.E. State PA _Reg. No. 072588 (when applIcaible) Design reporr certified by NAh e P.E. State N/A Rag. No. WA (wtlen appl~cable )CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are corrictand that this (these) IHSI Muil-Staos Breakdown Orifice Extension Adaoter.conforms to the rules of construction of the ASME Code, Section III, Division 1.NPT Certificate of Authorization No. N-2974 Expires March 26. 2008 Date F- 0 -11 Name lonics. Incorporated -Birideville Division Signed Z -(NPT Cerlflicale Holder ) (,utihorizad represertav) CERTlFICATE OF INSPECnTON I, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State and Provinrc of Pennsylvania and employed by One Beacon America Insurance Co.of Boston. MA have inspected these Items descibed In this Date Report on ) c -fm -ZC07 and state that to the best of my knowledge and belief, the Certificate Holder lhas fabricated these parts or appurtenances In accordance with dhe ASME Code. Section Ill, Division 1. Each part liled has been authorized for stamping on the date shown above.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this Data Report. Furthermore. neither the Inspector nor his employer shali be liable In any manner for any personal injury or property damage or loss of any kind arising ftm or connected with this Inspection. Date 02-~ Z -2Ax- Sign Commissions AG~(L' fllýlzd IudeZ Inspector) (Nat'l. Rd. (Ind. eridorserresnits and stile or pray. arid riol Page 19 of 177 -Tr~eler W6#760O ( .ed f 7 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the provisions of the ASME Code, Section III Not to Exceed One day's production Pg. I of 2 1. Manufactured and certified by tonics, Incorporated, Bridaevifle pIvision. 30 Curry Avenue. Cqnorlburcl. Pennsylvania. 1513 7 (name and ~addai of NPT Cari11 Holder)2. Man,,facluredlot Westinghouse Electric Co, 4350 Northern Pike. Monroeville. PA. 15146 3. Location of installatlon Voatle Elecric Generating Plant- Unit 1. 7821 River Rood, Woynesboro, GA 30830~rare and drssa)4. Type 10025ESORev.3 I "Wing evmbe SA-312 TP 316 (mall, tpec no.)NLA IM)~2007 b 1A~5. ASME Code, Section III. Division 1: 1W74 w-Summer 1975 (addenal dab)2 NIA Mdiss) ICed. cute no.)6. Fabricated if) accordance weit Const. Spec. (Div. 2 only) NIA Revision N/A Date N/A 7. Remarks 1HSI Multi-Slope Breakdown Orifice Extension AdoPters consistino of a pipe weLded to a weld neck flonQe.M.nufactured on Ionics Contract 1665. Supolied on Westinghouse Contract 4500208455_ The Westinghouse contract removes from Ioni;s any feninn rkdbeu rs--Km MFd -kimmurn.-gg.

8. Nom. Thickness (in.)-.Ljl.n design thickness On.) -- Dil. 10 (ft & in.) 0-- 3.822- Length overall(ft&In.)

U-1 9. When applcable, Certificate Holdars' Data Reports are attached for each Itarn of this report Part or Appurtearlnce National Serial Number Board No.in Numerical order 1-FO-9652-B (2) ___________ (3)(4) ___________ (5)_____________________________ (6) ___________ ______________ (7) ____________________________ 0(8) _____________ ______________ (114) __________ _(17)(21)(22) ____________ (23)(24) __________________________ (25)10. Design pressure____ 11§Q psi. Temp.20 Pat or Appi~rtesnance Nadoanal Serial Nurnber Board No.In Numeriall order (28)(29) ___________ _(31) ___________ (32)__ _ _ _ _ _ _ _ _ _ _ _ _ _(33)__ _ _ _ _ _ _ _(34) _ _ _ _ _ _(35) _____________ (36)__ _ _ _ _ _ _ _ _ _ _ _ _ _(37) ____________ (38) _____________ _________________ (39) _____________ _________________ (40) ____________ (41) ____________ (42) ____________ (43)(44)__ _ _ _ _ _(45) _____________ (48) _____________ (47) _____________ (48)(49)(50)F-.. Hydrol. Test pressure 2800 at lamp. -IL P*Supplarenlaw information in the form of lists, sketches. or may be used provided (1) aima is a X x I1. (2) Informatl, In items 2 and 3On this Date Report is included on each sheet. (3) each sheet is numbered and the numbern f shoeelsisrecordedat the opof this formi (71981 This form (EO0040) may be obtained from the Order ftpL, ASME. 22 Law Drive. Box 2300. Fairfiedl. NJ 07007-2300 I Page 20 of 177 Trce ler // 0'I TSO FORM N -2 (Back -Pg 2 of 2)Certificate Holder's Serial Nos. 1-FO.9652-8 through CERTIFICATION OF DESIGN Design specifications certified by .John L Robinson P.E. State PA _Rog. No. Q02568 (when spplIcaile) Design repor" certified by NIA , P.E. State N/A tReg. No. NIA (when applicoble) CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) IHSI Muki-Staoe Breakdown Orifice Extension Adaoter conforms to the rules of construction of the ASME Code. Section itl, Division 1.NPT Certificate of Authonzation No. N-2974 Expires March 28. 2008 Date L -Name Ionics. Incopormted -Bridgeville Division Signed _---"_ _ _INPT Certifcate Holder) (authoriza: 'epdeentetve) CERTIFICATE OF INSPECTION

f. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State and Province of Pennsylvania and employed by One Beacon America Insurance Co.of Boston. MA have Itspected theme Items described in this Data Report on e7-,2 ,- Z<A>? and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code. Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or conceming the equipment descibed In this Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or loss of any kind arising from or conn" th this inspection.

Date 62-7 3,2(-Vx'7 Signed Commissions udNuclar Inspectr) (Nul. 8d. (Incl. edorseemanlt) and state or prov. and no)Poge 21 of 177 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birnincham, AL Date Sheet Unit Traveler# 07152 07/02108 Of 1 1060178404 Address 2. Plant Voajte Electric Generating Plant Name Wavnesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtfe Type Code Symbol Stamp Aulthorization No.Expiration Date N/A N/A N/A Address 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components Code Case National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Comronent Manufacturer Serial No. No. Identification Built Installed (Yes or No)1204 PIPE PULLMAN POWER N/A N/A VI-1204-014-H005 1987 CORRECTED YES SUPPORT PRODUCTS 7. Description of Work Pipe support was modified per DCP 1060178401.

8. Test Conducted:

Hydrostatic [] Pneumatie[] Nominal Operating Pressure[] Exempt[o Other [ Pressure psi Test Temp. -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Autho 5 iatlon No... N/A Expiration Date N/A Signed Team Leader Date , Owner or Ownertl DesigneeTitle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia , and employed by. Harfford-Steam Boiler Inspection and Insurance Co. of Connecticut ,of _HsrflordL Conecitfcut.. have Inspected the components described in this Owner's Report during the period 8/06/07 to 7 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ilnspection. Commissions e;4 *,o -.npec"-s Signature National Board, State, Province and Endorsements Date "7 :T-,., NA. ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07153 L/1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Blrmingham, AL Address 2. Plant Vogtle Electric Generating Plant Date Sheet Unit 04/18/08 of _ __, I1.Name Wavnesboro, GA 30830 1070954401 Address Maintenance DeDarlnent Repair/Replacement Organization P.O. No., Job No., etc.I Code Symbol Stamp NIA 3. Work Performed by 4. Identification of System Type Name Plant Vootle I Authorization No.Expiration Date N/A NIA Address 120A / Chemh~al nnd Va/urns tanimi .~v.tsm 1208 / Chemical and Volume Control S-tern I S. (a) Applicable Construction Code ASME Sec. Il, 1977 Edition, Winter 1977. Addenda, 1644-5 Code Cas (b) Applicable Edition of Section Xl Used for Repalr/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xi Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year -Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (es or No)PIPE PULLMAN POWER N/A N/A V1-1208-009-HOO1 1987 INSTALLED YES SUPPORT PRODUCTS 7.Description of Work Snubber PSA-3, serial #29037 was replaced with a snubber PSA-3, serial #28344. A replacement load stud wasl also installed.

  • I 8. Test Conducted:-
9. Remarks See Item 7 Hydrostatic E] Pneumatic[]

Nominal Operating Pressurej] Exempt[X Other [] Pressure -psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the-requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of Aut"Izatl an No. NWA Expiration Date.N/A , Signed Owner or Titi Team Leader Date CERTIFICATE OF INSERVICE INSPECTION -I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Geoorola and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartfor.g ConncticuL have Inspected the components described In this Owner's Report during the period 07/1/07 I to " and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section lXi.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ithe examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. " I__________________Commissions &A .firspector'-51lnature National Board, State, Province and Endorsements 0 Date S- Miay' 2=w - ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl I 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 T Date 0;Sheet 1-Unit raveler# 07154 V15/08 of I I 1070956301 Repalr/Replacement Organization P.O. No., Job No., etc.Address Maintenance Deoartment

3. Work Performed by 4. Identification of System Name Plant Voctle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A 1301/Main Steam Address 1301/ Main Steam SystemL 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped.Component Manufacturer Serial No. No. Identification Built Installed ( Yes or No)PIPE PULLMAN POWER NA/A AI VI-1301-109-HO02 1987 INSTALLED YES SUPPORT PRODUCTS _7. Description of Work Snubber AD-73, serial # 1197 was replaced with a snubber AD-73, serial #472.8. Test Conducted:
9. Remarks See Item 7 Hydrostatic

[] PneumaticQ Nominal Operating Pressure[] Exemptrxo Other [] Pressure -psi Test Temp. _ OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the r'eport are coriect and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of Au rIzation No N/A Expiration Date N/A Signed Team Leader Date' 4i-t/,o 2-crF$i"-OwneFor'lwher's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of ConnectictA of arffrd Lonn ectdcut have inspected the components described In this Owner's Report during the period 07/16/07 to V..t -k=& and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Sectionl Xi.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerningi the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer s'hall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with 'this Ins action.I __ ___ __ ___ __ Commissions 6^. 7-Se" Inspectofet Signature National Board, State, Province and Endorsements Date /_ , S-- .~1 J.*1'ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07156 I/1. Owner Southern Nuclear.Operating Company 2. Plant Name 40 Inverness Center Parkway, Birmingham, AL Address Vogtle Electuic Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit 04/17/08 1 of 1070955901 Repair/Replacement Organization P.O. No., Job No., etc.I 3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1208 / Chemical and Volume Control System S. (a) Applicable Construction Code ASME Sec. I11, 1977 Edition, Winter 1977 Addenda; N-249-1 Code Ca.(b) Applicable Edition of Section Xt Used for Repair/Replacement Activity 2001 Ed, thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components 0 National Corrected, ASME Coale Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or N6L PIPE PULLMAN POWER N/A N/A V1-1208-001-H032 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-503, serial #241 was replaced with a snubber AO-503, serial #658.I 8. Test Conducted:

9. Remarks See Item 7 Hydrostatic E] Pneumatic[]

Nominal Operating Pressure-] Exemptfx'Other [] Pressure _psi Test Temp. OF'Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE .1 certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of AIlorization O,, N/A Expiration Date N/A Signed 71 Team Leader Date __ _ _"rwne'ir or OneAis Designee, Title CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors. and the state or Province of Georia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harflorgd, ut have inspected the components described In this Owner's Report during the period 07/16/07 I to &- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerningI the examinations end corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any'personal injury or property damage or a loss of any kind arising from or connected with !this Inspection., ..Commissions 64," I-' Inspecor's Signature National Board, State, Province and Endorsements Date 9 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY'As Required By The Provisions Of The ASME Code Section XI-~Traveler

  1. 07158 1. Owner Southem Nuclear Operating Company Date 04/14/08 Name 40 Inverness Center Parkway, Birmingham, AL Sheet 1 of 1 Address 2. Plant Vogtle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1070956701 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant VoQtie Expiration Date N/A Address 4. identification of System 1204 /Safety Injection System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A V1-1204-025-H012.

1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-1601, serial #50 was replaced with a snubber AD-1601, serfal #112.B." Test Conducted: Hydrostatic F1 Pneumatic[] Nominal Operating PressureE Exempt9 Other [] Pressure _psi Test Temp.' _F 9. Remarks See Item 7 S , Applicable Manufacturer'e Data Reports to be attached CERTIFICATE OF COMPLIANCE certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A# CefllfIbete of A. oriz tiN N/ Expiration Date NAV Signed: 'Team Leader Date ___ -______Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by Hartford Steam Roller Inspection and Insurance Co. of Connecticut of Hartfor onnecticut have Inspected the components described In this Owner's Report during the period 07/161/07 to V and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section, XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concernlngi the examinations and corrective measures described in this Owner's Report Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions 7,r6 S I nspabr's Signature National Board, State, Province and Endorsements Date: /"S I I ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07159 1. Owner Southern Nuclear ODeratina Comranv Date 04/10/08 Name 40 Inverness Center Parkway, Birmingham, AL Sheet Address 2. Plant Voatle Electric Generating Plant Unit Name Iof Waynesboro, GA 30830 1070956901 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address 4. Identification of System 1301/Main Steam System 5. (a) Applicable Construction Code ASME Sac. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped!: Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A A/A V1-1301-107-H004 1987 INSTALLED YES I SUPPORT PRODUCTS _7. Description of Work Snubber AD-5501, seanal #488 was replaced with a snubber AD-5501, serial #239. I@ 8. Test Conducted: Hydrostatic ] Pneumatic[] Nominal Operating Pressure[] Exempto]Other [] Pressure psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of Autorization No N/A Expiration Date NI/A Team Leader Date.SOwn lrnor1Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Geornia and employed by Hartford Steam Boiler Insoectlon and Insurance Co. of ConnectIcut of Haford, Connecticut have inspected the components described In this Owner's Report during the period 07/16/07 I to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shell be liable In any manner for any personal Injury or property damage or a lose of any kind arising from or connected with til.s Inspection. ___Commissions &-,4 75sr,-" inspectfs Signature National Board, State, Province and Endorsements @ Date BanA~.,& -' ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI V1 Traveler# 07160 04116/08.1.Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date 2. Plant Address Voglie Electric Generatina Plant Sheet 1 Unit of I Name Waynesboro, GA 30830 Address 1070956801 Repair/Replacement Organization P.O. No., Job No., etc..3. Work Performed by 4.. Identification of System Maintenance Department .Name Plant Vogtle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1301/Main Steam System 5.(a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Ca., (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A a 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No'PIPE PULLMAN POWER N/A N/A Vl-1301-104-H003 1987 INSTALLED YES SUPPORT PRODUCTS 7." Description of Work Snubber AD-12501, serial #41 was replaced with a snubber AD-12501, serial #132.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] PneumaticE] Nominal Operating Pressure[] ExemptfZ]Other [] Pressure _ psi Test Temp. 7F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.Type Code Symbol Stamp N/A Certificate of A hoatio No. N/A Expiration Date /NA-/A Signed 1"".' Team Leader Date ______'______ Owner oi Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission-issued by the National BoArd of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of arf Caon elcut have Inspected the components described in this Owner's Report during the period 07/16/07 V to s Q Mx. and state that to the best of my knowledge and belief, the Owner has performed examinations and talken corrective measures" described in this Owner's Report In accordance with the requirements of the ASME Code, Section :Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning ihe examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer sh~all be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions &A~.75(SSgnature Board, State, Province and Endorsements Date :5'-A W ,nX 0 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi TravelerN 07161 1. Owner Southern Nuclear Operating Company Date 04113/08 Name 40 Inverness Center Parkway, Bininigham, AL Sheet Address 2. Plant Vogtle Electric Generating Plant Unit Name 1 of 1 Waynesboro, GA 30830 1070956001 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtie Expiration Date N/A Address 4. Identification of System 1208/Chemical and Volume Control System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Cas i (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 203 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped!" Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A Vl-1208-012-HO11 1987 INSTALLED YES -SUPPORT PRODUCTS _7. Description of Work Snubber AD- 153L, serial #250 was replaced with a snubber AD- 153L, serial #702.8. Test Conducted: Hydrostatic [] Pneumatlc[] Nominal Operating Pressure[] Exempt'X Other ] Pressure _ psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.Type Code Symbol Stamp N/A Certificate of z N/A Expiration Date N/A Signed Team Leader Date " Owner or Own~er'l Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georaia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut: of Harr. CQonncticut have inspected the components described in this Owner's Report during the period .07/16/07 to 0,. and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section IXI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. I Commissions GC,^. W'&Inspeffor's Signature National.Board, State, Province and Endorsements Date ze, 4,-tfP CORRECTED_ ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler # 07162 C 1. Owner Southern Nuclear Operating Company Date 06116108 Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Sheet I of 1 Unit 1 Name Waynesboro, GA 30830 Address 1070955601 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance DeDartment Name Plant Voglie Type Code Symbol Stamp Authorization No.Expirtion Date NAV NAV N/A Address 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components r National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed aYes or No)PIPE PULLMAN POWER N/A N/A Vl-1201-030-H055 1987 INSTALLED YES SUPPORT PRODUCTS 7, Description of Work SnubberAD-151, serial #427 was replaced with a snubberAD-151, serial #424. The removed snubberAD-151, Serial #427 failed functional testing as documented by CR# 2008103664. The verification of acceptability was not completed until after the pipe support was returned to service as documented by CR# 2008106722.

8. Test Conducted:
9. Remarks See Item 7 Hydrostatic

[] Pneumatic"] Nominal Operating Pressure[] Exempt[N]Other Q] Pressure _____ psi Test Temp. __ _ F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of " Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harrd. have inspected the components described In this Owner's Report during the period 07/16/07 to state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this in on.Commissions (,, 7" ff~spectir4ignature National Board, State, Province and Endorsements Date ; ", , C ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI A Traveler# 07163 1. Owner Southern Nuclear Operating Company Name 40 inverness Center Parkway, Birmingham, AL Date Sheet Unit 04/17/08 1 off 1 2. Plant Address Vogtle Electric Generating Plant Name Waynesboro, GA 30830 1070954201 Address Repair/Replacement Organization P.O. No;, Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1204 / Safetv Injection System 5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section X.1 Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Codie Name of Name of Manufacturer Board Other Year Removed, or Stamped Cmoent Manufacturer Serial No. No. Identification Built Installed (Yes or NIo)PIPE PULLMAN POWER N/A N/A VI-1204-043-H013 1987 INSTALLED YES I SUPPORT PRODUCTS 7. Description of Work Snubber PSA-3, serial #28741 was replaced with a snubber PSA-3, serial #28740.0 8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] Pneumatic[] Nominal Operating. PressureW ExemptL]OtherE] Pressure _____ psi Test Temp. -_OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.Type Code Symbol Stamp N/A Certificate of Autorization No. N/A Expiration Date N/A Signed W' Team Leader Date Owner or Owher's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Roiler Insoection and Insurance Co. of Connecticut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period 07/16/07 1 to and state that to the best of my knowledge and belief, the Owner has performed examinations and tdken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Sectionj Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or 'connected with this inspection. Z:- ý ý ýft'a .iCommissions C-34. Lo fnspe&6r'sSignature -National Board, State, Province and Endorsements 0 Date A3 k .A ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler# 07164 1. Owner Southern "Nuclear Operatihg Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet 04/10/08 of 1'2. Plant Address Voptle Electric Generating Plant Unit Name Waynesboro, GA 30830 Address 1070954001 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenahce Department Name Plant Votfle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A NIA NIA 1204 / Safety Inlaction System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, WInter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section XI Used for RepairlReplacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A VI-1204-025-HO07 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-1, serial #24583 was replaced with a snubber PSA-1, serial #24326.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic f] Pneumatic-Nominal Operating Pressure[

Exemptf]Other [] Pressure pal Test Temp, OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify. that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Auftrization No. NIA Expiration Date NIA Signed, 0 t<." \ or Team Leader Date--Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford.n2 n icut have Inspected the components described In this Owner's Report during the period 07/16/07 to Y and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correct ve measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section XI.: By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning; the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. __L________________--___-__, ____ Commissions 6p. ., lnspehuffSignaturs National Board, State, Province end Endorsements Date /5 ,o.L _( cocm ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07165 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet 06/16108 2 Plant Address Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address I of I I Unit 1070955501 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1305 / Condensate and Feedwater System 5. (a) Applicable Construction Code ASME Sec. iIl, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xi Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A V1-1305-064-H005 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-35, serial #40271 was replaced with a snubber PSA-35, seral #12261. The removed snubber PSA-35r senal #40271 failed functional testing as documented by CR# 2008103698. The verification of acce tability was not completed unhiA affar iha nina ~,,nnnt w~a rainmari in ~~an4i~a n~ dn,,nmnntaA hu (~a 9f~,A1fl~7OO III after the -ail-f was retumed to servke as documented b CR#2008106722 r-8, Test Conducted:

9. Remarks See Item 7 Hydrostatic

[J Pneumaticfl Nominal Operating Pressurer] Other n Pressure psi Test Temp. _Exempt]Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Criiaeo A1 _ Expiration Data NIA Signed TeamnLeader Date L./-ki or Ower's Designee, Tite CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georafa and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartord Connticut have Inspected the components described in this Owner's Report during the period 07/16/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. Snscs Sgntut B S P ndtCommissionss insp s ignaureNational Board, State, Province and Endorsements Date c2 a Zrjm #¶'&O C i ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASM E Code Section XI'Traveler# 07166 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmingham, AL Date Address 2. Plant Vogtle Electric Generating Plant Sheet Unit 04/10/08 I of I Name Waynesboro, GA 30830 Address 1070955401 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtle Address Type Code Symbol Stamp Authorization No.Expiration Date NIA NIA WA 1305 / Condensate and Feedwater System 5. (a) Applicable Construction-Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components Code Case National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built installed (Yes or NoL PIPE PULLMAN POWER N/A N/A V1-1305-060-H003 1987 INSTALLED YES SUPPORT PRODUCTS _J 7. Description of Work Snubber PSA-100, serial #2219 was replaced with a snubber PSA-100, serial #2188.* J 8. Test Conducted: 9 Ramarks Sea Item 7 Hydrostatic 5 Pneumaticf] Nominal OperatingPressuref[] Exempt[i]Other [] Pressure _psi Test Temp. _ _OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of A5 t zati n No. N/A Expiration Date N/A Signed Team Leader Date I L .--oner* o)P (5wrer'Jo esignee, Title" CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors I and the state or Province of Georqla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of 6ardConnecticut have Inspected the components described In this Owner's Report during the period 07/16/07 1 to /2& nand state that. to the best of my knowledge and belief; the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Sectionl XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning, the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shell be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions t AnspeciEr Signature~ National Board, State, Province and Endorsements Date AZ. APfA. ZM!B ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By.The, Provisions Of The ASME Code Section XI Traveler# 07167.1.Owner Southern Nuclear Operatlng Company Name 40 Inverness Center Parkway, Birmingham. AL Date Sheet 04/17/08 1 1 of I Address 2. Plant Vogte Electric Generating Plant Name Waynesboro, GA 30830 Address Unit 1070955101 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voctle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A.N/A NIA 1301 1 Main Steam System 5. (a) Applicable Construction Code ASME Sec. I11, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca., (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components a National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed aes or No)L PIPE PULLMAN POWER N/A N/A Vl-1301-104-H004 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-35, serial #12253 was replaced with a snubber PSA-35, serial #12262. 1 a. Test Conducted:

9. Remarks See Item 7 Hydrostatic

] Pneumatic[] Nominal Operating Pressure[] Exempt[Z]Other ] Pressure -psi Test Temp. __IF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp NIA Certificate of Au^rzation No N/A Expiration Date N/A Signed <rA:;w.s Team Leader Date OwneFr or nr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of. Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Lart! Connecticut have Inspected the components described In this Owner's Report during the period 07/16/07 1 to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions &AL Inspelblor's Signature National Board, State, Province and Endorsements a Date R,3 AftPR. alexnal WI ORIGINAL .FORM NIS-2 OWNER'S REPORT FOR REPAIRPREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07168 1. Owner Southern Nuclear Operating Company Date 04/17/08 Name 40 Inverness Center Pakway, Birmingham, AL Sheet I of I Address 2. Plant Vogtle Electric Generating Plant Unit I Name Waynesboro, GA 30830 1070954801 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A I Name Authorization No. N/A Plant Vootla Expiration Date N/A Address 4. Identification of System 1204/Safety Injection System 5. (a) Applicable Construction Code ASME Sec. 111, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xi Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or Nol PIPE PULLMAN POWER N/A N/A V1-1204-127-HO15 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-35, serial #12252 was replaced with a snubber PSA-35, serial #11248.8. Test Conducted: Hydrostatic E] Pneumatic[] Nominal Operating Pressure[] Exempt[OJ Other U Pressure _ psi Test Temp. OF_ _9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached -CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Au oirizatlon No Nl/A Expiration Date N/A -Signed Team Leader Date 12..li 2r 16nOwnr or Ower's Designee, Title CERTIFICATE OF INSERVICE INSPECTION -I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georcia and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of Hartfnrd, Connecticut have inspected the components described in this Owner's Report during the period 07/16/07 I to ....d/ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Sectioni. X..By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. C_ _Inspe_-_ _ _ _'s Signature National Board, State, Province and Endorsements Date d5 AAA. A~e' ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI.2 Iraveler# 07169 04/21/08 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address.2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830.Address 3. Work Performed by Maintenance Department Name* Plant Vogtle Address 4. Identification of System Date Sheet Unit I of 1 A061951201 and 1070953901 Repair/Replacement Organization P.O. No., Job No., etc.Type Code Symbol Stamp W/A Authorization No. AN/A Expiration Date N/A 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME Sec. I1/, 1977 Edition, Winter 1977 Addenda, 1644-5. Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001.Ed. thru 2003Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (es or No)PIPE PULLMAN POWER N/A N/A VW-1204-023-H007 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA.10; serial #15976 was replaced with a snubber PSA-10, serial #12859. The telescoping cylinder was previously replaced in the Installed snubber sernal #12859 under Traveler-06094 and WO# A061951201.

8. Test Conducted:
9. Remarks See Item 7 Hydrostatic

[] Pneumatlc[] Nominal Operating Pressure[] Exempt(']Other [ Pressure .psi Test Temp. __OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A C f ofAtorlzation No. ' N/A Expiration Date N/A Signed TeamLeader Date Owher or'Oner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by' Hartford Steam Boiler InsPaction and Insurance Co. of Connecticut of _Har.frd, Connecticut have Inspected the components described in this Owner's Report during the period 11/01/06 to a e2g=&, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl..By signing this certificate neither the. Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. _______________________Commissions CY4. M i nspaor's Signature National Board, State, Province and Endorsements Date : j AA. e'Otr 6 I ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI'170 Traveler # 07)4/10/08 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet of 1 1070953701 Address 2. Plant Vootle Electric Generating Plant Unit I of 1070953701 Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.a Code Symbol Stamp N/A 3. Work Performed by 4. Identification of System Maintenance Department Type Name Plant Vogqle Authorization No.Expiration Date N/A N/A Address 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed, thru 2003 Add.(c) Applicable Section Xl Code Case(s) MIA 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A VI-1201-042-HOOI 1987 INSTALLED YES SUPP5ORT PRODUCTS _7. Description of Work Snubber PSA-1, serial #12207 was replaced with a snubber PSA-1, serial #24315.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic'[

PneumatlcE Nominal Operating Pressure[ Exempt[IX Other F] P Pressure _ psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp. NIA Certificate of AutjbdIzatoon No,. N/A Expiration Date N/A Signed X' Team Leader Date .-Owner or Ownet's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of rf Connecticut have Inspected the components described In this Owner's Report during the period 07/16/07 i to W and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any persohal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions 6h 7-M n nspec.i"ris Signature " National Board, State, Province and Endorsements [Date /tK, ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07171 i 1. Owner Southem Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet 04/17/08 1 of 1 Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Unit 1070953401 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voole Type Code Symbol Stamp Authorization No.Expiration Data Nl/A N/A N/A Address 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca!(b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components SNational Corrected, ASME Coae Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A V1-1208-024-H005 1987 INSTALLED YES SUPPORT PRODUCTS _7. Description of Work Snubber PSA-1/4, serial #34217 was replaced with a snubber PSA-1/4, sedal #34205.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] PneumaticE1 Nominal Operating Pressure[] Exempt(X]Other [] Pressure psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Au r n N/A Expiration Date N/A Signed Team Leader Date.- -rc)ýner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticul of HV Cnn uecticut have inspected the components described In this Owner's Report during the period 07/16/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, SectionI XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerningithe examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising' from or connected with this Ins ecton.__CCommissions 11.'nspecto,6 Signature National Board, State, Province and Endorsements Date 240 AHit.,oA' ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section X1 1. Owner Southern Nuclear Operatinq Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit Traveler# 07172 07/02/08 1__ _ _ Of 1 1 1060178404 Address 2. Plant Vogfle Electric Generating Plant Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtle Address Type Code Symbol Stamp Authorization No.Expiration Date W/A WA/WAb 1204 / Safety Injection System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)1204 PIPING PULLMAN POWER N/A N/A 1K3-1204-014-01 1987 INSTALLED YES SYSTEM PRODUCTS 7. Description of Work A I" drain line connection was welded to line 1204-014-4. per DCP 1060178404.

8. Test Conducted:

Hydrostatic F1 Pneumatic[] Nominal Operating PressureX] Exemptrl Other [] Pressure _ psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of Aj ýtion N/A Expiration Date N/A Signed O 'a.JTl Team Leader Date Owner oOwersesignee, Title"--, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georlai and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of rtford cnneciut have Inspected the components described In this Owner's Report during the period 08/06/07 to -- i. f-, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions 15IA 74, r Inspqldr's Signature National Board, State, Province and Endorsements Date 4 ;3"-11-y W " 4) ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1, Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit Traveler# 07180 06/18/08 of 1 1 1071004001 Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A NIA WAV Address 1208/ Chemical and Volume Control System 5. (a) Applicable Construction Code ASME Sec. ill, 1971 Edition, Winter 1972 Addenda, N/A (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thu 2003 Add, (c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components Code Case 7. Description of Work installed replacement relief valve. Relief valve SNN N56900-00-0074 has been previously installed and is utilized as a rotating spare; originally purchased under PO# 7029205 and received under MIR# 970901.B. Test Conducted-

9. Remarks See Item 7 Hydrostatic

(] PneumatlicF-Nominal Operating PressureE] Exempt[]Other I[] Pressure _ psi Test Temp. ?F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of (thrizatiorlo. N/A Expiration Date N/A Signed V X ý,ý Team Leader Date-Ow-neor'Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georaia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of 194d Clne tcut have inspected the components described In this Owner's Report during the period 08&23W7 to a$446 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XIL By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspectionl. Commissions 6* ;7 Inspects Signature National Board, State, Province and Endorsements Date ,=. " ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 7181 Traveler # O0 07/07/08 O 1.Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmingham, AL Date Sheet , Of 7;1 oo Unit 1 Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address 1071003901 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogfe Type Code Symbol Stamp Authorization No.Explratlon Date fl/A/AV N/A I Address .1205 / Residual Heat Removal System I 5. (a) Applicable Construction Code ASME Sec, II1, 1971 Edition, Winter 1972 Addenda, 1567 Code Caso (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thQi 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped'Component Manufacturer Serial No. No, Identification Built Installed ases or RELIEF VALVE CROSBY VALVE S N56904-00-0065 N/A 1PSV8708B 1991 REMOVED YES GAGE CO. _RELIEF VALVE CROSBY VALVE & N56904-00-0037 N/A 1PSV87088 1977 INSTALLED YES I GAGE CO.7. Description of Work Relief valve was replaced with a rotating spare which has been previously In service.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

] PneumatlcE] Nominal Operating Pressure[X Exempt[]Other [] Pressure _ psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.Type Code Symbol Stamp N/A Certificate offA ..N/A Expiration Date WA Signed kw ý TeamLeader Date Ownbrer Owndr's Designeer Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by Hartford Steam Boiler Inspection and insurance Co. of ConnecticUt of Haror necti ct have inspected the components described In this Owner's Report during the period 08/28/07 I to 'a nd state that to the best of my knowledge and belief, the Owner has performed examinations end taken corrective measures described' In this Owner's Report In accordance with the requirements of the ASME Code, Sectlo!n XI.By signing this certificate neither the Inspector nor hia employer makes any warranty, expressed or Implied, concernin'g the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employerfshall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions -A 7',r,, spect ignature National Board, State, Province and Endorsements -pLDate t.- .2uhI ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRI/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Voctle Electric Generatlne Plant Date Sheet Traveler# 07183 06/19/G0 of 1 1 1070494301 and PO)# 7078886 Unit Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Pwv.. Suite 148. Blrminaham. AL 35242 Type Code Symbol Stamp Authorizatlon No.Expiration Date N/A N/IA IWA Address 4. Identification of System 1201 / Reactor Conlant 9ystem 1201 / Reactor C lant Svstern 5. (a) Applicable Construction Code ASME Sec. It1, 1971 Edition, Winter 1972 Addenda, NV/A (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity -2001 Ed. thnJ 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components Code Case National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PUMP WESTINGHOUSE 6-9744D35G01 38 1-1201-P6-002 1984 INSTALLED YES ELECTRIC CORP.7. Description of Work A replacement No. 2 seal housing was installed. The replacement No. 2 seat housinq, serial number 1607, is a rotating spare that has been previously In service.a. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] Pneumatic[] Nominal Operating Pressure[E] Other [] Pressure _psi Test Temp.Exempt[]Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of A rl n No. N/A Expiration Date N/A Signed Team Leader Date Owner or Oreer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoi ' and employed by Hartford Steam Boiler Inspection and insurance Co. of Connecticut of Hartford, Connecticut-have inspected the components described in this Owner's Report during the period 0829/07 to I.1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions t 7-.Sffispecto-O'Signature National Board, State, Province and Endorsements Date Js ". A " ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl 1. Owner Southern Nuclear Operating Co.mpany Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit Traveler# 07187 06/23/08 of 1 1 1070494401 and PO# 7078886 Address 2. Plant Vogtle Electnc Generating Plant Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Pwy., Suite 148, Birmingham, AL 35242 Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A W/A Address 4. Identification of System 1201 /Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. iii, 1971 Edition, Winter 1972 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) NVA 6. Identification Of Components National Corrected, " ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PUMP WESTINGHOUSE 10-9744D35G02 N/A 1-1201-P6-004 1995 INSTALLED YES ELECTRIC CORP.7. Description of Work A replacement No. 2 seal housing was installed. The replacemenl No. 2 seal housing, serial number 1813, is a rotating spare that has been previously in service.8. Test Conducted: Hydrostatic f] Pneumatic[] Nominal Operating PresSure[z] Exempt(]Other [] Pressure .psi Test Temp. __ _ F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of tohion V N/A Expiration Date NIA Signed w Ti Team Leader Date 9 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georala and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of Hartfo .on~etiat have inspected the components described In this Owner's Report during the period 08/29 /7 to f and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correctve measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this ecton.Commissions &s.Inspectlc s Signature -National Board, State, Province and Endorsements Date , ,-_ r, ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07195 1. Owner Southern Nuclear Operating Company Date Name 40 Inverness Center Parkway, Birmingham, AL Sheet Address 2. Plant Vogtle Electric Generating Plant Unit Name Waynesboro, GA 30830 Address R 3. Work Performed by Maintenance Department Type C Name Authori Plant Vogtle Expirat Address 4. Identification of System 1204 S. (a) Applicable Construction Code ASME Sec. Iii, 1977 Edition (b) Applicable Edition of Section XI Used for Repair/Replacement Act (c) Applicable Section Xl Code Case(s) NWA 6. 'Identification Of Components 04110108 I of 1 1053337801 epair/Replacement Organization P.O. No., Job No., etc.ode Symbol Stamp N/A Ization No. N/A ion Date N/A I Safety Injection Systemr , Winter 1977 Addenda, 1644-5 Code Case ivity -2001 Ed. thru 2003 Add..National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built installed (Yes or No)PIPE PULLMAN POWER N/A N/A Vl-1204-003-H006 1987 INSTALLED YES I SUPPORT PRODUCTS _'I 7. Description of Work Snubber PSA-1/4, serial #33467 was replaced with a LUsega Type 30 snubber, serial #30500420/092.

8. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] Exempt[M Other [] Pressure _ psi Test Temp. __OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of Aut r orIon No. N/A Expiration Date N/A -Signed -W ? Team Leader Date Ic t (cS Owner or Own~r's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georola and employed by Hartford Steam Boiler Inspection and insurance Co. of Connecticut of Harfd, Connecticut have Inspected the components described in this Owner's Report during the period 09/17/07 i to ., and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective. measures described In this Owner's Report In accordance with the requirements of the ASME Code, Sectioni Xi.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerningl the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with 'this inspection.j ;;;.r i Commissions

64. " onspar's Signature National Board, State, Province and Endorsements Date /, aP. PA 11 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY .'As By The Provisions Of The ASME Code Section Xl Traveler#

07197 0 1. Owner 2. Plant Southern Nuclear Operating Company Name , 40 Inverness Center Parkway, Birmingham, AL Address VoWtie Electric Generatinq Plant Date Sheet Unit 04/18/08 of 1 1 1053338101 Name Waynesboro, GA 30830: 3. Work Performed by 4. Identification of System Address Malntenaince Department Repair/Replacement Organization P.O. No., Job No., etc.Name Plant Vogtle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 1206 / Containment Spray System 5. (a) Applicable Construction Code. ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(*) Applicable Section Xi Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A VI-1206-002-H027 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber AD- 153, serdal '405 was replaced with a Lisega Type 30 snubber, serial #30500642/86. A We.Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] OtherE ] Pressure .psi Test Temp.Exempt~jJ OF 9. Remarks See Item 7.* Applicable Manufacturer's Data Reports to be attached* .. CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.Type Code Symbol Stamp N/A Certificate ofthorizatlon No. N/A Expiration Date N/A SSigned: Team Leader Date Owner r Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors-and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Harifood Connecticut have inspected the components described in this Owner's Report during the, period 09/17/07 to -/_-,1 >.-f--, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section XI.; By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected,.wlth this Inspection. Commissions GA.V Insl tor's Signature National Board, State, Province and Endorsements Date: 40A. - I ORIGINAL -4',I FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 07203 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date 04/10/OR 04110108 Sheet 1 of I Address Vootle Electric Generating Plant 2. Plant Unit 1 Name Waynesboro, GA 30830 Address 1053339101 RepalirReplacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voqtle Address Type Code Symbol Stamp Authorization No.Expiration Dale N/A N/A N/A 1301/Main Steam Svstem 5. (a) Applicable Construction Code ASME Sec. I11, 1977 Edition, Winter 1977 Addenda, N-249.1 Code Cat (b) Applicable Edition of Section XI Used for Repalr/Replacement Activity 2001 Ed. thru 2003Add.(c) Applicable Section XI Code Case(s) N/A a 6. Identification Of Components National Corrected, ASME Cole Name of Name of Manufacturei Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed Yes or NoL PIPE PULLMAN POWER N/A N/A V I-1301. t 6.HO002 1987 INSTALLED YES SUPPORT PRODUCTS__ _I __!i 7. Description of Work Snubber AD-5503, serial #224 was replaced with a Usega Type 30 snubber, serial #30500211/089. I 8. Test Conducted: Hydrostatic [] Pneumatic] Nominal Operating Pressurel] Exempto'Other r Pressure psi Test Temp. °F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xh.Type Code Symbol Stamp N/A Certificate of Nthorizati N N/A Expiration Date N/A Signed Owner o O'n-'s Team Leader Date !dft rOvrier or Ovner's Designee, Title 04<ýM Er;.. 11IC I E-3. OFUP INPECT"UIOINI I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticu of Htord, Connecticut have Inspected the components described In this Owner's Report during the period 09/17/07 I to la, jaoor,, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Sectioni Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerningithe examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions 6 Y 0 I lnspeeffir's Signature Date /,a M APR. o AD 'National Board, State, Province and Endorsements

  • ORIGINAL 4 FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY* As Required By The Provisions Of The ASME Code Section XI Traveler#

07205 1. Owner Southern NuclearOperating Company Date 04/14/08 P Name 40 Inverness Center Parkway, Birmingham, AL Sheet I of Address 2. Plant Vogle Electric Generating Plant Unit I Name Waynesboro, GA 30830 1053341401 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Voatle Expiration Date N/A Address 4., Identification of System 1301/Main Steam System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thrn 2003 Add, (c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No0)PIPE PULLMAN POWER AN/A N/A V1.1301-109.H004 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-151L, serial #251 was replaced with a Lisega Type 30 snubber, serial #30500263/14.

8. Test Conducted:

Hydrostatic [] Pneumaticn] Nominal Operating Pressure[] Exempt[o], ]Other Pressure -psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME.Code, Section XI.Type Code Symbol Stamp .N/A.Certificate of t o*I N/A Expiration Date N/A Signed; Team Leader Date* Owner or'Oner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION .;a I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boller Inspection and Insurance Co. of Connecticut of Hartford. Connecticut have Inspected the components described In this Owner's Report .during the period 09/17/07 to .and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section. XI..By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. __________________________Commissions 11.4 7s-.Finspec-dlis Signature .National Board, State, Province and Endorsements SDate S P.A!eT ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT AcTIvITY As Required By The Provisions Of The ASME Code Section X1 y Traveler# 07206 04/21/08 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Votile Electric Generating Plant Date Sheet I of I Unit Name Waynesboro, GA 30830 1 1053341501 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voptle Type Coda Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address 13011 Main Steam System 5. (a) Applicable Construction Code ASME Sec. i//, 1977 Edition, Winter 1977 Addenda, N-249-'1 Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A V1-1301-126-H037 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber AD-73, serial #187 was replaced with a LIsega Type 30 snubber, serial #30500235/019.

8. Test Conducted:
9. Remarks See Item 7 Hydrostatic

[] Pneumatic[ Nominal Operating Pressure[] ExemptZJ Other ] Pressure _psi ' Test Temp. OF_ _Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Auhjrizaeon No. N/A Expiration Date N/A Signed. OeJ e n"1t Team Leader Date d/Owner-or Own6r's Des~ignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georaia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Co tcu have inspected the components described in this Owner's Report during the period 09/17/07 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi..By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _ _ _ _ Commissions 6, 75(Pi Inspeor's Signature .National Board, State, Province and Endorsements Date W Atx. oalt 6 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY F* As Required By The Provisions Of The ASME Code Section XI Traveler # 07209 1. Owner Southern Nuclear Operating Company Date 04/09/08 Name 40 Inverness Center Parkway, Birmingham, AL Sheet 1 of Address 2. Plant Vogtle Electric Generating Plant Unit 1 Name Waynesboro, GA 30830 1053343501 Address RepalrlReplacement Organization P.O. No., Job No,, etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vog1le- Expiration Date WN/A Address 4. Identification of System 1305/Condensate and Feedwater System S. (a) Applicable Construction Code ASME Sec. III. 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(q) Applicable SctionXi Code Case(s) N/A 8. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A V1-1305.064-HO06 1987 INSTALLED YES SUPPORT PRODUCTS _7. Description of Work Snubber PSA-100, serial #2504 was replaced with a Lisega Type 30 snubber, serial #30500569/02.

8. Test Conducted:

Hydrostatic [ PneumatfcE Nominal Operating Pressure[] Exempt'l Other [ Pressure _ psi Test Temp. _F 9. Remarks See Ite/n 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE 'I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Iz on No N/A Expiration Date N/A Signed /(" o'~r Team Leader Date

-"gnwne&-Owhor's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the stats or Province of Geordta and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticul of Hartford.

Connecticut have Inspected the components described in this Owners Report during the period 09/17/07 to .7.1_./,2_ X, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XI..By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning !the examinatlons and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer sIhall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this___________________________Commissions , 74.inspe@6r' Signature 'Nationlal Board, State, Province and Endorsements Date lr APA ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear ODeratina Company Name 40 Inverness Center Parkway, Birmingham. AL Date Sheet Unit Traveler# 07221 07/08/08 I of 5 1 Address 2. Plant Voatle Electric Generatina Plant Name Waynesboro, GA 30830 Address RepairlReplacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootla Type Code Symbol Stamp Authorization No.Expiration Oato N/A NAV NAV Address 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N/A (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components Code Case National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No VALVE ATWOOD & 1-18269-07 N/A IHV41320A 1983 CORRECTED YES MORRILL CO., INC.7. Description of Work Installed a replacement plug and cover screws on valve. Copies of Form N-2 for the replacement plug and cover screws are attached.S. Test Conducted: Hydrostatic F] Pneumatlc[E Nominal Operating PressureE[_] Exempt[]Other ] Pressure _psi Test Temp. __ _ F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of A ri n WA Expiration Date N/A E Signed e, V Team Leader Date 7 c?`:-"wne OrOwrler% Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georcia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartfod.Ca nnicgLt have Inspected the components described In this Owner's Report during the period 12/06107 to Z and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In ction._ _ _ _low Commissions 4 7s"L," fnspectcs ignature National Board, State, Province and Endorsements Date / Z/f-iryc .j FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the Provisions of the ASME Code, Section III Not to Exceed One Day's Production-TrL/e Ier- -07 22 (Skeet 2<45 pg. 1 ofil2 1. Manufactured and certified by Fisher Controls International. Inc.. N. Stnningnn

CT (name aind addmess of NPT Cartificate Holder(2. Manufactured for Georgia Power Company, PO Box 1295, Birmingham, AL (name and address of Purchast er)Vogtle Electric Generating Plant, Waynesboro, CA (name and addreisl 3. Location of installation
4. Type: 16B1649 Rev.A SA564 Gr. 630 145 ksi min. n/a 1996 (drawing no.) i. spec. no. ) (tensile strength)

ICRtN Wart built)5. ASME Code. Section III, Division 1: 4.-9*Ji97-191 -) Winter 77 2 n/a ,& Y-zj _ tedlatonl (addenda date) (class) Code Case no.)6. Fabricated in accordance with Const. Spec. (Div. 2 only) n/a Revision n/a Date nj/, (no.)7. Remarks: Plug for Atwood & Morrill 3" Class 300 Figure 1366 BW 8. Nom. thickness (in.) n/a Min. design thickness (in.) n/a Die. ID (ft & in.) n/a Length overall (ft & in.) .n/a....9. When applicable, Certificate Holders' Data Reports are attached for each item of this report: Part or Appurtenance Serial Number National Board No.in Numerical Order n/a Part or Appurtenance Serial Number National Board No.in Numerical Order A0369 (1)(2)(3)(4)(5)(6)(7)(8)(9)(10)111)(12)(13)(141 (15)(16)(17)(18)(19)(20)121)122)(23)(24)(25)i -(26)(27)(28)(29)130)131)132)(33)(34)(35)(36)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(48)(49)(50)+"I.+.4 I i 10. Design pressure 375 psi. Temp, 225 -F. Hydro. test pressure n/a at temp. OF (when applicable) Supplemental information in the form of lists, sketches, or drawings may he used provided (11 size is 8 % x t 1 (2) information in items 2 and 3 on this Date Report is included on each sheet. (3) each sheet is numbered end the number of sheets is recorded at the top of this form.(12/88) This form (E000401 may be obtained from the Order Dept., ASME, 22 Law Drive. Box 2300, Fairfield, NJ 07007-2300. FORM N-2 (Back -Pg. 2 of .2_2 8 e L 3o45 Certificate Holder's Serial Nos. A0369 through n/a CERTIFICATION OF DESIGN Design specifications certified by S.W. Ashworth P.E. State GA Reg. no. 017030 (when applcabl.1 Design report* certified by n/a P.E. State n/a Reg. o. n/a 1when applicable) CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this~llbli=li P conforms to the rules of construction of the ASME Code, Section II1. Division 1.NPT Certificate of Authorization No. N-1847 Expires Sept. 2, 1998 (NPT Cartificate Holder) faluthorized representativrej, CERTIFICATE OF INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by Commercial Union Ins. Co.of Boston, M have inspected these items described in this Data Report on March 18, 1996 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore. neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection. Date 3'-Z3 A Sign ..-Commissions c7,3*/-(Atoie napector) INatI'. as. iifle). endorsements) and state or prov. and no.) FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES* As Required by the Provisions of the ASME Code, Section III Not to Exceed One Day's Production T-rmvv er -0722.2(Skeet 4Vf5 pg. 1 of2 1.2.3.4.5.7.Manufactured and certified by Fisher Controls International. Inn.- N. rofnn tT (name and addressa Of NPT Certiicate Holder)Manufactured for Georgia Power Company, PO Box 1295, Birmingham, AL (name and address of Purchaser) Location of installation Vogtle Electric Generating Plant, Waynesboro, GA fname and addreu)Type: 16B1594 Rev.A SA193 B8 96.4 ksi n/a 1996 (drawing no.) Imt. laie. no.1 (tensile strength) .ICRNI (year built)ASME Code, Section III, Division 1: 9 19'17 Winter 77 2 n/a s,., +&Z-ledhion) iaddenda dejat ela)s) iCode Ca no.s Fabricated in accordance with Const. Spec. (Div. 2 only) n/a Revision n/a Date n/a (no.)Remarks: 7/16"-14 x 11/2" hex head cap screws for Atwood & Morril 3" Clas-n Ion Figure 1366 BW. manufactured by Texas Bolt Co. Heat No. 36231 Quantity 4 bolts all identified with the number "5".8. Nom. thickness (in.) n/a Min. design thickness (in.) n/a Dia. ID (ft & in.) 7/16" Length overall (ft & in.) 1 !/?" 9. When applicable, Certificate Holders' Data Reports are attached for each item of this report: Part or Appurtenance National Serial Number Board No.in Numerical Order 01 5 n/a (2)(3)(4)(5)(61 (7)(8)(9)(10)¶11)(12)(13)(14)(15)(16)(17)(18)(19)(20)(21)(22)(23)(24)(25)Part or Appurtenance National Serial Number Board No.in Numerical Order (26)(27)(28)129)(30)(31)(32)(33)(34)(35)(35)(37)(38)(39)(40)(41)(42)(43)(44)(45)(46)(47)(48)-(49)(50)10. Design pressure 375 psi. Temp. 225 OF. Hydro. test pressure n/a at temp. OF (when applicablel Supplemental information In the form of lists, sketches, or drawings may be used provided ll) size is 8 % X 11, (2) information in Items 2 and 3 on this Data Report is Included on each sheet, (3) each sheet is numbered and the number of sheets Is recorded at the top of this form.412188) This form IE00040) may be obtained from the Order Dept., ASME, 22 Law Drive. Box 2300, Fairfield, NJ 07007-2300. -Troorcler-Z-07221 FORM N-2 (Back -Pg. 2 of__2 ) 2' eel=5 o-5 Certificate Holder's Serial Nos. through CERTIFICATION OF DESIGN Design specifications certified by S.W. Ashworth PE. State GA Reg. no. 017030 (when appicableStn Design report* certified by n/a P.E. State n/a Reg. no. fl/a 1when applic,1Slej) CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this ithese) Hex Head Cap Screws conforms to the rules of construction of the ASME Code, Section IlII, Division 1.NPT Certificate of Authorization No. N-1847 Expires Sept. 2, 1998 Date Ma rch 18, 1 9 9 6 Name Fisher Controls Int'l., Inc. Signed -INPT Certiicate Holder) (authorized ,eprasentatr. CERTIFICATE OF INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by Commerc-ial Union Ins. Co.of Boston, KA have inspected these items described in this Data Report on Harch 18 , 1996 ,and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section Ill, Division 1. Each part listed has been authorized for stamping on the date shown above.By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection. Date '/--Z3 Sigii Commissions 63~~j(Authorho ized inspector lNat'l. Bd. mcin. endorsements) and state or prov, and no.] ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08009 1. Owner Southern Nuclear Operating Company Date 06/19/08 Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Sheet Unit of I Name Waynesboro, GA 30830 Address WO# 1060607904 and PO# 7071336 Repair/Replacement Organization P.O, No., Job No., etc.3. Work Performed by Westinchouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Address Type Code Symbol Stamp Authorization No.Expiration Data N/A IVA N/A 4. Identification of System 1201 / Reactor Coolant System _______ _____`ASME Sec. /II 1971 Summer 1972 N/A 5. (a) Applicable Construction Code **ASME Sec. III 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except for Appendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Ys or No)*PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1981 CORRECTED YES VESSEL ELECTRIC CORP.1201 PIPING PULLMAN POWER N/A N/A 1X4DL4D20 1987 CORRECTED YES SYSTEM PRODUCTS I III_1_ 1 7. Description of Work A full structural weld overlay (FSWOL) was completed on the 1PSV8OIOA safety valve nozzle This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 058-W-01. The FSWOL design included the use of alternatives to existing Code guidance and was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Approval for this alternative repair was obtained under NRC letter NL.08-0405. The FSWOL was completed in accordance with DCP# 1060607901.

8. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating Pressure[X] Exempt[]Other r] Pressure N/A psi Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.Type Code Symbol Stamp N/A Certificate of Pthorization ,. N/A Expiration Date N/A~'Signed .% 'J-Team Leader Date S """ Ow~ner or ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartfrd Con ectict have inspected the components described In this Owner's Report during the period 02/07/08 to 75.,z_ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations-and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this in ection.Commissions 'fspectols Signature National Board, State, Province and Endorsements Date 7 .r- y 4 r ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section X1 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Date Sheet Unit Traveler# 08010 06/19108 1 of 1 W WO# 1060607903 and PO# 7071336 Name Wavnesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Address Type Code Symbol Stamp Authorization No.Expiration Date N/A NIA 4. Identification of System 1201 /Reactor Coolant System`ASME Sec. I1 1971 Summer 1972 N/A S. (a) Applicable Construction Code *°ASME Sec. II/ 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except forAppendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)*PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1981 CORRECTED YES VESSEL ELECTRIC CORP.1201 PIPING PULLMAN POWER N/A N/A IX4DL4D20 1987 CORRECTED YES SYSTEM PRODUCTS I I I I I _ _7. Description of Work A full structural weld overlay (FSWOL) was completed on the 1PSV8010B safety valve nozzle (N-2). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 057-W-0 1. The FSWOL design Included the use of alternatives to existing Code guidance and was submitted to the NRC as ISI-GEN-AL T-07.01 (NL-07-1320 and NL-0 7-2206. Approval for this alternative repair was obtained under NRC letter NL-08-0405. The FSWOL was completed in accordance with DCP# 1060607901.

8. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating Pressureg Exempt[]Other [] Pressure N/A psi Test Temp. N/A OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate offpthorization Do. N/A Expiration Date N/A Signed e kneTt Team Leader Date L. (E3 o Owvner or Ownmer's Deal lnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler inspection and Insurance Co. of Connecticut of HartfodC nn ticut have inspected the components described In this Owner's Report during the period 02/07/08 to , and state that to the best of my knowledge and belief, the Owner hasperformed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions 6,,, 75-6 VelnspectW~Signature National Board, State, Province and Endorsements I Date lo nzý.I- Y _2b ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler # 08011 06/19/08 1. Owner Southern Nuclear Operating Company Date Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Voptle Electric Generating Plant Name Waynesboro, GA 30830 Address Sheet 1 of 1 Unit I WO# 1060607902 and PO# 7071336 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinahouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Type Code Symbol Stamp Authorization No.Expiration Date NAV NA&N/A Address 4. Identification of System 1201 / Reactor Coolant System`ASME Sec. ill 1971 Summer 1972 N/A 5. (a) Applicable Construction Code **ASME Sec. IH/ 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except for Appendix ViII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda 6. Identification Of Components I 7. Description of Work A full structural weld overlay (FSWOL) was completed on the 1PSV8010C safety valve nozzle (N-3). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 056-W-01. The FSWOL design included the use of alternatives to existing Code guidance and was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Approval for this alternative repair was obtained under NRC letter NL-08-0405. The FSWOL was completed in accordance with DCP# 1060607901.

8. Test Conducted.
9. Remarks See Item 7 Hydrostatic R Pneumatic[Z]

Nominal Operating Pressure El Other [] Pressure N/A psi Test Temp. N/A Exemptfl Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of Authorti on N N/A Expiration Date IN/A Signed 92 '/!....- Team Leader Date Z3-"Owhd o'FOIner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georaia and employed by Hartford Steam Boiler Inspection and Insurance-Co. of Connecticut of HartfordConnectcut have Inspected the components described in this Owner's Report during the period 02/07/08 to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions -Dt I V nspec6 s Signature National Board, State, Province and Endorsements IDate et 'r-C-'A564 Abcs ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmingham, AL Date Sheet Unit Traveler# 08012 06/19108 1 of I W WO# 1060607907 and PO# 7071336 Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp Name Authorization No.44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Expiration Date N/A N/A N/A Address 4. Identification of System 1201 Reactor Coolant System*ASME Sec. III 1971 Summer 1972 W/A 5. (a) Applicable Construction Code "°ASME Sec. III 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except forAppendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No*PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1982 CORRECTED YES VESSEL ELECTRIC CORP.1201 PIPING PULLMAN POWER N/A N/A 1X40L4D20 1987 CORRECTED YES SYSTEM PRODUCTS II I__I1_7. Description of Work A full structural weld overlay (FSWOL) was completed on the Pressurizer relief line nozzle (N-4). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 059-W-01. The FSWOL design included the use of alternatives to existing Code guidance and was submitted to the NRC as ISl-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Approval for this alternative repair was obtained under NRC letter NL-08-0405. The FSWOL was completed in accordance with DCP# 1060607901.

8. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] ExemptE]Other [:] Pressure N/A psi Test Temp. N/A -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 1i1J1L. Team Leader Date j Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georala and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford. ConncticuL have inspected the components described In this Owner's Report during the period 02/06/08 to .a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this ins ection..Commissions 6,-4, 75-IaSignature National Board, State, Province and Endorsements Date /0 T.' jp-¢ r aC. 2 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler # 08013 1. Owner Southern Nuclear Operatinq Company Date 06119/08 Name 40 Inverness Center Parkway. Birnmingham, AL Address 2. Plant Vogtle Electric Generating Plant Sheet 1 of 1 Unit 1 Name Waynesboro, GA 30830 Address WO# 1060607905 and PO# 7071336 RepalrlReplacement Organization P.O. No., Job No., etc.3. Work Performed by Westinohouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Blnningqham, AL 35242 Address Type Code Symbol Stamp Authonitatlon No.Expiration Date N/A N/A 4. Identification of System 1201 Reactor Coolant System*ASME Sec. III 1971 Summer 1972 N/A 5. (a) Applicable Construction Code **ASME Sec. III 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except for Appendix VIII (c) Applicable Section Xi Code Case(s) None from the 2001 Edition, No Addenda 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)*PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1982 CORRECTED YES VESSEL ELECTRIC CORP.1201 PIPING PULLMAN POWER N/A N/A 1X4DL4D20 1987 CORRECTED YES SYSTEM PRODUCTS 7. Description of Work A full stnjctural weld oveday (FSWOL) was completed on the Pressurizer spray line nozzle (N-5). This FSWOL was placed over the vessel safe-end weld and included the piping attachment weld 030-W- 14. The FSWOL design included the use of alternatives to existing Code -guidance and was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Apprval for this alternative repair was obtained under NRC letter NL-08-0405. The FSWOL was completed in accordance with DCP# 1060607901.

8. Test Conducted:

Hydrostatic [] Pneumatic[] Nominal Operating PressureZ Exempt[]Other [] Pressure NiA psi Test Temp. NIA -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A CertificateAof JAZol on No.# N/A Expiration Date N/A Signed or )I5u DPC.eg i.'t. Team Leader Date "Z- ,.. .-"wne? or Own' Dee~no, Title ...CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by Hartford Steam Boiler Inspectdion and Insurance Co. of Connecticut of tiagifrd, Con ut have inspected the components described In this Owner's Report during the period 02/O6/08 to .9_2C&Iand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this C ntion.Commissions r-Inspect~hSIgnature National Board, State, Province and Endorsements Date 4Ljr abr it ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASM E Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit Traveler# 08014 06/19/08 1 of 1 I WO# 1060607906 and PC# 7071336 Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Address 4. Identification of System Type Code Symbol Stamp Authorization No.Expiration Date NIA N/A N/A 1201 Reactor Coolant System'ASME Sec. IIl 1971 Summer 1972 N/A 5. (a) Applicable Construction Code **ASME Sec. I// 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Edition, 2003 Addenda except forAppendix VIII (c) Applicable Section XI Code Case(s) None from the 2001 Edition, No Addenda 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed YeoN"PRESSURIZER WESTINGHOUSE 62189 N/A 1-1201-V6-002 1982 CORRECTED YES VESSEL ELECTRIC CORP." 1201 PIPING PULLMAN POWER N/A N/A 1X4DL4D20 1987 CORRECTED YES SYSTEM. PRODUCTS III 7. Description of Work A full structural weld overlay (FSWOL) was completed on the Pressurizer surge line nozzle (N-6). This FSWOL was placed over the vessel sate-end weld and included the deoi~ attachment weld 053- W-01. The FSWOIL desien included the use cf was placed over the vessel safe-end weld and included the oloino a ment weld 053-W-01. elSWOLdn-sioninclu dthauseof alternatives to existing Code ouidance and was submitted to the NRC as ISI-GEN-ALT-07-01 (NL-07-1320 and NL-07-2206). Aporoval for this alternative repair was obtained under NRC letter NL-08-0405. The FSWOL was completed in accordance with DCP# 1060607901.

8. Test Conducted:
9. Remarks See Item 7 Hydrostatic E] Pneumatic']

Nominal Operating PressurezJ Other F1 Pressure N/A psi Test Temp. N/A Exempt[]Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Atlorizatian No. N/A Expiration Date N/A Signed Team Leader Date ' ___________ Owner or Ovner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of -Georgia _and employed by Hartford Steam Boiler Inspection and Insurance Go. of Connecticut of _Hartfod Cnne ticut have inspected the components described in this Owner's Report during the period 01/391/08 to Q a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions g! ;17 Inspect Signature National Board, State, Province and Endorsements Date / 2 , , ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant VogUe Electric Generating Plant Date Sheet Unit Traveler # 08020 07/14/08 I of I 1062027801 Name Waynesboro, GA 30830 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant VogUe Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A Address 1201 /Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. I4 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed 1201 PIPING NUCLEAR 4027-001 N/A 1X6AB08-56 1986 CORRECTED YES SYSTEM INSTALLATION lX6ABOB-58 ..... SER VICES CO. ,_....._ _7. Description of Work Installed replacement 3/4" X 5/16" reducer unions at seal table locations H6, N14, C5, J7 and R6.8. Test Conducted: Hydrostatic [] Pneumaticfl Nominal operating PressureE] Exempt [g]Other n Pressure psi Test Temp. -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certifi cate ofA orl ic NIA Expiration Date NAV Signed _v T Team Leader Date t,0ag O)wnecr Own r's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford, onnecticut have inspected the components described In this Owner's Report during the period 02/04/08 to 1 and state that to the best of my krowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury o property damage or a loss of any kind arising from or connected with this ino econ.Commissions .Inspectof Signature. National Board, State, Province and Endorsements Date /__ 1__0_- " I_ ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler# 08034@ 1.Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit 04/17/08 of I Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 1070957701 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vootle Type Code Symbol Stamp Authorization No.Expiration Date N/A MIA WA Address 1208 /Chemical and Volume Control System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Cai (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thni 2003 Add, (c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Coe Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or NoL PIPE PULLMAN POWER N/A N/A V1-1208-055.H046 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work A replacement nut was installed on the pipe clamp bolt.0 8. Test Conducted:

9. Remarks See Item 7 Hydrostatic R Pneumatlce-Nominal Operating Pressure--

Other F] Pressure _ psi Test Temp.ExemptNJ Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Auor tion No. N/A Expiration Date N/A-Signed X ?\ Team Leader Date " _bwniaror 0wrfer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgia and employed by* Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of art onecticut have inspected the components described in this Owner's Report during the period 03/20/08 1 to & and state that to the best of my knowledge and belief, the Owner has performed examinations and tiken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Sectionj Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions (&A 7'", Flnspec~¶ifs Signature National Board, State, Province and Endorsements Date A-3 ,A .b 0 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham. AL Date Sheet Unit Traveler # 08035 06116/08 of I 1 1062001501 Address 2. Plant Vogtile Electric Generating Plant Name Waynesboro, GA 30830 Address RepairlReplacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. i1l, 1977 Edition, Winter 1977 Addenda, N/A (b) Applicable Edition of Section Xl Used for Repalr/Replacement Activity 2001 Ed. thry 2003 Add.(c) Applicable Section Xi Code Case(s) N/A 6. Identification Of Components Code Case National Corrected, ASME Code Narne of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)PIPE PULLMAN POWER N/A N/A V1-1201-030-H044 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Installed replacement load pin on pipe support.a. Test Conducted: -Hydrostatic [] Pneumatic -] Nominal Operating Pressure[] Exempt[Z Other El Pressure _ psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp WA Certificate of Au rz NIA Expiration DateNI Signed I TeamLeader Date.... (JOwner .idrOv;neres Designee, Title..CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of. Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co, of Connecticut of ecritfo C ccut have inspected the components described In this Owner's Report during the period 03121/08 to o and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcil6 measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this AV Commissions 7, ý.r_ý napeoctor .gnaturei National Board, State, Province and Endorsements ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler # 08'036 Tra for #1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmincham. AL Date Sheet Unit ArMPAO*it- M , 06/16/08 of. -1 1080557701

2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830.Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4.. Identification of System Maintenance Department Name Plant Vog/e Address Type Coda Symbol Stamp Authorization No.Expiration Date 1305 / Condensate and Feedwater Svstem N/A N/A N/A 5. .(a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Case (b) Applicable Edition of Section Xi Used for RepalrlReplacement Activity 2001 Ed. thru 2003 Add, (a) App!lcable Section Xl Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer.

Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification' Built Installed or Noi PIPE PULLMAN POWER N/A N/A V1-1305-064-HO04 1987 INSTALLED YES SUPPORT PRODUCTS _ _I 7. Description of Work Snubber PSA-100, serial #2226 was replaced with a snubber PSA-100, sedal #2175. The removed snubber PSA-100. serial #2226 failed functional testing as documented per CR# 2008104385. The verification of acceptability was not completed until after the pipe support was returned to service as documented by CR# 2008106722. 0 8. Test Conducted: Hydrostatic [] Pneumsaticr Nominal Operating Pressure[ Q Exempt0']Other 11 Pressure psi Test Temp. OF c i 9. Remarks See Item 7 Applicable Manufacturer's Date Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp W .- N/A Certificate of oriosI .N/VA Expiration Date N/A Signed Team Leader Date O9nei or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoql and employed by Hartford Steam Boller Inspection and Insurance Co. of Connecticut! of HartorConnecticut have Inspected the components described In this Owner's Report during the period 04/01/08 I.to , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.1 By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions In.A ~nspectoas Signature .National Board, State, Province and Endorsements Date 03~ 70,0v ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY 'As Required By The Provisions Of The ASME Code Section Xl Traveler# 08037 1. Owner Southern Nuclear Operating Company Date 04/13108 Name 40 Inverness Center Parkway, Birmingham, AL Sheet of 1 Ad, dress 2. Plant Vogtle Electric Generarin Unit 1 Name Waynesboro, GA 30830 1080553601 Address RepairlReplacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Type Code Symbol Stamp N/A Name Authorization No. N/A Plant Vogtle Expiration Date N/A Address 4. Identification of System 1208 / Chemical and Volume Control System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add, (c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code4 Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or No'PIPE PULLMAN POWER N/A N/A VI-1208-449-H013 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work SnubberAD.41, serial #698 was replaced with a snubberAD-41, serial #673.8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] ExemptFX1 Other 5 Pressure -_psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of A;oriza Ion No. N/IA Expiration Date N/A Signed _-i'c7\ Team Leader Date GA-i L(.-, ug Owner or Owndr's Dsignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding-e valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of Hartord Connecticut have Inspected the components described in this Owner's Report during the period 04/01/08 to / and state that to the-best of my knowledge and belief, the Owner has performed examinations end takn corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning tile examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this.Commissions C, v 75'n, YlnspectgiWS-gnsture National Board, State, Province and Endorsements " Date Z6 A te.oA ff26 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI L/Traveler# 08038 04/16/08 1. Owner Southern Nuclear Operating Company Date Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Sheet Unit of 1080555201 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voqtie Type Code Symbol Stamp Authorization No.Expiration Date 1301 /Main Steam System N/A NfA/WA Address 5. (a) Applicable Construction Code ASME Sec. i/1, 1977 Edition, Winter 1977 Addenda, N-249-1 Code CasE (b) Applicable Edition of Section Xi Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A" 6. Identification Of Components e National Corrected, ASME Coae Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or N6)PIPE PULLMAN POWER N/A N/A VI-1301-110-H004 1987 INSTALLED YES I SUPPORT PRODUCTS Aw 7. Description of Work Snubber AD- 151L, serial #486 was replaced with a snubber AD-.151L, serial 8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] Pneumatic[] Nominal Operating PressureD ExemptX-]Other [] Pressure _psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A -Certificate ofAutboritlon No. N/A Expiration Date N/A I Signed Team Leader Date-Owneror o ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georqia and employed by Harfford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford. Connecticut have inspected the components described in this Owner's Report during the period 04/01/08 to & and state that to the best of my knowledge and belief, the Owner has performed examinations and t~ken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Sectionf XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning-the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with !this inspection. _________ _-, ___,__ _________Commissions &9 7,,4.Insp'c4rtPs Sigte National Board, State, Province and Endorsements Date .PR,. aft,,,ye 0 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler# 08039 9 0 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit 04/17/08 of 1 Address 2. Plant Vogtle Electric Generating Plant Name Wavnesboro GA 30830 1080554301 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voatle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A I/A Address l3O02/Auxilinry Faadwntnr Svqtem-I 1302 lAuxiliarv Feedwater Svstem 5. (a) Applicable Construction Code ASME Sec. 11, 1977 Edition, Winter 1977 Addenda, N-249-1 Code Cas (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components a National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)L PIPE PULLMAN POWER N/A N/A VI-1302-108-H019 1987 INSTALLED YES SUPPORT PRODUCTS ]7. Description of Work Snubber AD-501, serial #369 was replaced with a snubber AD-501, serial #163.8. Test Conducted:

9. Remarks See Item 7 Hydrostatic E1 PneumaticD Nominal Operating Pressure[]

Exempt[']Other ] Pressure _ psi Test Temp. _ ___ F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of A rl O I 14119- N/A Expiration Date N/A Signed Team Leader Date /wiffr obwier's Designee, Title~lh CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartfordi Connecticut have Inspected the components described In this Owner's Report during the period 04/01/08 I to Z and state that to the best of my knowledge and belief, the Owner has performed examinations -and tlken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,* Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of'any kind arising from or connected with 'this inspection. _ _ _ _ _ _ ._ _ _ Commissions &A. 7s-e.lnsp-llna or's Signature National Board, State, Province and Endorsements Date ",a L ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl Traveler # 08040 0 1. Owner 2. Plant Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address Vogftle Electric Generating Plant Name, Waynesboro, GA 30830 Address Date Sheet Unit 04117108 i of L 1 1080557201 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Maintenance Department Name Plant Voqtle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A W/A N/A 4. Identification of System 1204 / Safety Inlection System 5. (a) Applicable Construction Code ASME Sec. III, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca, (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A ie 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or N6)PIPE PULLMAN POWER N/A N/A VI-1204-125-H017 1987 INSTALLED YES SUPPORT PRODUCTS 7. Description of Work Snubber PSA-35, serial #11253 was replaced with a snubber PSA-35, serial #11503.S. -Test Conducted:

9. Remarks See Item 7 Hydrostatic 11 Pneumatic[]

Nominal Operating Pressure[] Exemptrx]Other El Pressure _'psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Aut rization No. NIA Expiration Date NIA -Signed Team Leader Date Owner or Ownr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia and employed by. Hartford Steam Boiler Insnection and Insurance Co. of ConnecticQt of Hartford Connecticut have Inspected the components described In this Owner's Report during the period 04/01/08 1 to 77 Q2L, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _ _ _ m Commissions 6A " Inspear's Signature National Board, State, Province and Endorsements Date RZ AP& .AAW ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi Traveler # 08041 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date 04/17/08 Sheet 1 of 1 Address 2. Plant Vogetl Electric Generating Plant Unit Name Waynesboro, GA 30830 1080557301 Address Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Vogtle Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A Address -1305 / Condensate and Feedwater System 1S05 / Cnndansata and Fandwatar Svstam 5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, 1644-5 Code Ca (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xl Code Case(s) N/A 6. Identification Of Components ie National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed es or N6)PIPE PULLMAN POWER N/A N/A V1-1305-062-H006 1987 INSTALLED YES SUPPORT PRODUCTS.7. Description of Work Snubber PSA-IO0, serial #2221 was replaced with a snubber PSA-100, serial #2219.0 8. Test Conducted:

9. Remarks See Item 7 Hydrostatic

[] Pneumatic[] Nominal Operating Pressure[] Exempt[E]Other [] Pressure _ psi Test Temp. _ __ OF Applicable Manufacturer!s Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of Au orization No. AL/A Expiration Date N/A Signed i Team Leader Date '2,2-i'bf WOw~neror Owher's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board-of Boiler and Pressure Vessel Inspectors I and the state or Province of Georgla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of 6Afor d, LQncticut have Inspected the components described in this Owner's Report during the period 04/01/08 1 to .C/__L- .- and state that to the best of my knowledge and belief, the Owner has performed examinations and corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Sectionj Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning Ihe examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with !this Inspection. Commissions GA Y Inspjft6r's Signature National Board, State, Province and Endorsements Date P19. Qb=IJ 0 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Voqtle Electric Generating Plant Date Sheet Unit Traveler# 08042 06/17/08 of 1 1 Name Waynesboro, GA 30830 Address WO# 1071016101 and PO# 7080438 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp Name Authorization No.44 Inverness Center Parkwav, Suite 148, Birmingham, AL 35242 Expiration Date N/A N/A N/A 4. Identification of System Address 1201 / Reactor Coolant System 1528-3 &5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section Xi Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name o0 Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed STEAM WESTINGHOUSE GAGT 1881 N/A 1-1201-B6-001 1981 INSTALLED YES GENERATOR ELECTRIC CORP.7. Description of Work Installed mechanical tube plugs in tube locations R57-C44, R6-Cl 10, R8-C1 12. RIO-Cl 14, R 11-Cl 18 and R13-C96.8. Test Conducted: Hydrostatic F1 Pneumatic[- Nominal Operating Pressurer Exempt]Other [] Pressure psi Test Temp. -F 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of A ri tion N.) NIA _ Expiration Date W/A Signed Team Leader Date-wnerbr wer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georgla and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hard. Connecticut have Inspected the components described in this Owner's Report during the period 04/02/08 to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. __ _ __ _ __ _, _ _ _ Commissions &,4 )'s1-VInspectcWSIgnature National Board, State, Province and Endorsements Date / %7& .2.1e>se ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xl 6 1. Owner Southern Nuclear ODeratino Comoanv 2. Plant Name 40 Inverness Center Parkway, Birmingham, AL Address Vogtie Electric Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit Traveler# 08043 06/17/08 1 of 1 I WO# 1071016101 and PO4 7080438 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co. Type Code Symbol Stamp Name Authorization No.44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Expiration Date N/A N/A W/A Address 1201 / Reactor Coolant System 4. Identification of System 1201 / Reactor Coolant Syýstem 1528-3 &5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)STEAM WESTINGHOUSE GAGT 1884 N/A 1-1201-B6-004 1981 INSTALLED YES GENERATOR ELECTRIC CORP.7. DescrIption of Work Installed mechanical tube plugs In tube location R38-C107, *R1 I-C62, *R12-C98, R22-C51. Additional mechanical tube pluqs were installed In the following locations under Traveler-08050: R9-C62. R10-C62, R6- C59M R6-C60, R7-C59, R7-C60, R7-C61, R8-C59, R8-C60, R8-C61, R8-C62. R8-C63r R8-C64. R9-C60, R9-C61, R9-C63. R9-C64, RIO- C60, R1O-C61, RIO-C63, R1O-C64, R.1-C60, Ril-C61, R11-C63, R1l-C64. R12-C60, R12-C61, R12-C62, R12-C63. R12-C64, R13-C61, R13-C62 and R13-C63.'Mechanical plugs installed on cold leg side of tube only for location R11-C62andR12-C98

8. Test Conducted:

Hydrostatic [] Pneumatic[-] Nominal Operating Pressure[] Exempt[g]Other F1 Pressure _ psi Test Temp. __OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section XI.Type Code Symbol Stamp N/A Certificate of A on .o N/A Expiration Date N/A Signed -TeamLeader oae 7/Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by HaIrtford Steam Boiler Insoection and Insurance CO. of Connecticut of ord- C nn icut have inspected the components described in this Owner's Report during the period 04/02/08 to ,5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. ___ --.__ -___ -___ , _ Commissions r "ZS-'e , inspectofSignature National Board, State, Province and Endorsements Date 2 L7-1 L/," ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRIREPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler # 08044 06/17/08 1. Owner -Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Address 2. Plant Vogtile Electric Generating Plant I of1 Unit Name Wavnesboro, GA 30830 WO# 1080539002 and PO# 7079313 Address RepalrlReplacement Organization P.O. No., Job No., etc, 3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A 4. Identification of System 1201 / Reactor Coolant System 5. (a) Applicable Construction Code ASME Sec. lU, 1977 Edition, Winter 1977 Addenda, N-272 Code Case (b) Applicable Edition of Section Xi Used for RepaidReplacement Activity 2001 Ed. thru2003Add (c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components

7. Description of Work Installed replacement reducer unions at seal table locations B08, C07, N02, A09, A 11 and D12.8. Test Conducted:
9. Remarks See Item 7 Hydrostatic

[] Pneumatlc[-] Nominal Operating Pressure-' Exempt[o]Other El Pressure psi Test Temp. -F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xi.Type Code Symbol Stamp N/A Certificate of Autpoization No. N/A Expiration Date N/A Signed Ak 2 Team Leader Date L il/II 7P._oner'oF OWner'§ Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georoia and employed by _ Hartford Steam BSoler Inspection and Insurance Co. of Connecticut of Hartf rd Co ecti ut have inspected the components described in this Owner's Report during the period 04/03108 to "and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcte measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this ecton.Commissions 6.w4 7s-(,'- Inspect-is Signature National Board, State, Province and Endorsements I Date 0?'/ Z1.SLEAN dah7OiX ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section Xi L.Traveler# 08045 0&/28/08 1. Owner Southern Nuclear Operating Company Date Name 40 Inverness Center Parkway, Birmingham, AL Address 2. Plant Vogtle Electric Generating Plant Sheet 1 of 1 Unit I Name Wavnesboro. GA 30830 1072090901 Repair/Replacement Organization P.O. No., Job No., etc.Address 3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A NWA 4. identification of System 1201 / Reactor Coolant System 1484-3 5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1528-3 Code Case (b) Applicable Edition of Section XI Used for Repair/Replacement Activity 2001 Ed. thru 2003 Add.(c) Applicable Section XI Code Case~s) N/A 6. identification Of Components

7. Description of Work Welded tube plugs were installed In hot leg tube locations RI 1-C62 and R12-C98. Acceptability of welded tube plug installation was completed per "SG Tube Repair Data Sheet I" from procedure 84015-C revision 2.1.8. Test Conducted:
9. Remarks See Item 7 Hydrostatic E Pneumatic[]

Nominal Operating Pressure[] Exempt[Z]Other [] Pressure _ psi Test Temp. _ -F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of A rltion N N/A Expiration Date N/A Signed Team Leader Date 7/-17 AP-wrirbr Owner's Designee, Title 4 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Geormia ' and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Haf Conecticut have inspected the components described in this Owner's Report during the period 04/03/08 to Z/7jf,3EO 1C, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section XI.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions 6-i4.1 nspetgrs Signature National Board, State, Province and Endorsements Date 7 .. " , I ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI Traveler # 08046 06/17/08 1. Owner 2. Plant Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address Voqtle Electric Generating Plant Date Sheet I of 1 Unit 1 Name Waynesboro, GA 30830 Address WO# 1071016101 and PO# 7080438 Repair/Replacement Organization P.O. No., Job No., etc, 3. Work Performed by Westinchouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmlnaham, AL 35242 Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A Address 1201 / Reactor Coolant System 4. Identification of System 1528-3 &5. (a) Applicable Construction Code ASME Sec. III, 1971 Edition, Summer 1972 Addenda, 1484-3 Code Case (b) Applicable Edition of Section Xl Used for Repair/Replacement Activity 2001 Ed. thru 2003Add.(c) Applicable Section XI Code Case(s) N/A 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)STEAM WESTINGHOUSE GAGT 1882 N/A 1-1201-B6-002 1981 INSTALLED YES GENERATOR ELECTRIC CORP.7. Description of Work Installed mechanical tube plugs In tube location R34-C104 8. Test Conducted: Hydrostatic n Pneumatic[] Nominal Operating PressureD] Exemptr Other [] Pressure _psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xh.Type Code Symbol Stamp N/A Certificate of th tio o. N/A Expiration Date N/A Signed Team Leader Date T ?S Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Georia and employed by Hartford Steam Boiler Insoection and Insurance Co. of Connecticut of atdonwt Qnec"ti have inspected the components described In this Owner's Report during the period 04/04/08 to ..-d , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions &Ai 7W'&Ins ýors Signatureý National Board, State, Province and Endorsements Date /_ .AtC ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required By The Provisions Of The ASME Code Section XI (0 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Date Sheet Unit Traveler# 08047 06(16/08 1 of I WO# 1071016101 and PO# 7080438 Address 2. Plant Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Repalr/Replacement Organization P;O. No., Job No., etc.3. Work Performed by Westinghouse Electric Co.Name 44 Inverness Center Parkway, Suite 148, Birmingham, AL 35242 Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A NIA 4. Identification of System 1201 / Reactor Coolant System 1528-3 &5. (a) Applicable Construction Code ASME Sec. IHl, 1971 Edition, Summer 1972 Addenda, 1484-3 (b) Applicable Edition of Section Xl Used for RepairlReplacement Activity 2001 Ed. thnr 2003 Add.(c) Applicable Section XI Code Case(s) N/A Code Case 6. Identification Of Components National Corrected, ASME Code Name of Name of Manufacturer Board Other Year Removed, or Stamped Component Manufacturer Serial No. No. Identification Built Installed 2YsoLo STEAM WESTINGHOUSE GAGT 1883 N/A 1-1201-B6-003 1981 INSTALLED YES GENERATOR ELECTRIC CORP.7. Deacriptlon of Work Installed mechanical tube plugs in tube locations R6-C119, R13-C107 and R42-C52.8. Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating Pressure[] Exempt[']Other E] Pressure -psi Test Temp. OF 9. Remarks See Item 7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A Certificate of A orifl? N/A Expiration Date N/A SSigned .Team Leader Date 4 Own~r or Owntr's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georqia and employed by Hartford Steam Boiler Inspection and Insurance Co, of Connecticut of Harfo Cnnectlcut have Inspected the components described in this Owner's Report during the period 04/04.08 to 2, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. ________________Commissions c.A 7 '5C Signature National Board, State, Province and Endorsements Date / .ThC ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required ByThe Provisions Of The ASME Code Section XI y Traveler# 08054 06/18/108 f 0 1. Owner Southern Nuclear Operating Company Date 2.Plant Name 40 Inverness Center Parkway, Birmingham, AL Address Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Address Sheet Unit of 1 1080620801 and 1080662501 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voctle Type Code Symbol Stamp Authorizatlon No.Expiration Date N/A N/A N/A 1204 / Safety Injection System Address 1204 /Safety Injection System 5. (a) Applicable Construction Code ASME Sec. Ill, 1977 Edition, Winter 1977 Addenda, N/A Code Case (b) Applicable Edition of Section XI Used for RepalrlReplacement Activity 2001 Ed. thru 2003 Add, (c) Applicable Section XI Code Case(s) N/A 6. identification Of Components National Corrected, ASME Coda Name of Name of Manufacture-Board Other Year Removed, or Stamped!Component Manufacturer SerialiNo. No. Identification Built Installed (Yes or No)VALVE DRAGON VALVES, RX3023 N/A 1-1204-U4-141 1984 INSTALLED YES INC. .7. Description of Work Installed replacement bonnet yoke, union nut and stem / disc assembly. The VT-2 system leakage examination was satisfactorily completed under WO# 1080662501.

8. Test Conducted:
9. Remarks See Item 7 Hydrostatic

] PneumatIcD] Nominal Operating PressureX] Exempt[]Other [] Pressure psi Test Temp. _ _OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp N/A r f 0 N/A Expiration Date N/A Signed Team Leader Date ,Owner ol Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Bolier and Pressure Vessel Inspectors and the state or Province of Geonlia and employed by Hartford Steam Boiler Inse Ctlon and Insurance Co. of Connecticut of artfo Connecticut have Inspected the components described In this Owner's Report during the period 04112/08 to a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.I .By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner'a Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection. Commissions &Atior TInspeR sSintr National Board, State, Province and Endorsements Date o?-N, atIA.")A0 .200,w 0 ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required BylThe Provisions Of The ASME Code Section XI 9 1; Owner 2. Plant Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address.Vogle Electric Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit Traveler # 08055 06/18/08 1 of 1 1080620601 and 1080662501 Repair/Replacement Organization P.O. No., Job No., etc.3. Work Performed by 4. Identification of System Maintenance Department Name Plant Voqtle Address Type Code Symbol Stamp Authorization No.Expiration Date N/A N/A N/A-1204 / Safety Inlection System 5. (a).Applicable Construction Code ASME Sec. I1/, 1977 Edition, Winter 1977 Addenda, N/A (b) Applicable Edition of Section'XI Used for'Repair/Replacement Activity 2001 Ed. thru2003 Add.(c) Applicable Section XI Code Case(s) N/A Code Case 6. Identification Of Components -National Corrected, ASME Cods Name of Name of Manufacturer Board Other Year Removed, or Stamped!Component Manufacturer Serial No. No. Identification Built Installed eYes or No)VALVE DRAGON VALVES, RX3024 N/A 1-1204-U4-140 1984 INSTALLED YES INC. I 7. Description of Work Installed replacement bonnet yoke, union nut and stem / disc assembly. The.VT-2 system leakage examination was satisfactorily completed under WO# 1080662501. S. Test Conducted:

9. Remrks See Item 7 Hydrostatic r1Pneumatic["] -Nominal operating

'Pressure[] Exempt[]Other [D Pre.sure _psi Test Temp. OF Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report ere correct and that this conforms to the requirements of the ASME Code, Section Xl.Type Code Symbol Stamp NIA Certificate of ,o tion * /A Expiration Date WA Signed, Vwr n eraDeiIneeam LeaderT 1ý`w~ra) rie'sDesignee. TitleA CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commilssion Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Georola and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford Conncicut have inspected the components described in this Owner's Report during the period 04/12/08 to 1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements of the ASME Code, Sectiont Xl.By signing this certificate neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and-corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with Ithis Commissions &A- )':=~Inspe 4Kr's Signature National Board, State, Province and Endorsements Dae9I 'A3;a67}}