05000341/FIN-2010006-07
From kanterella
Revision as of 16:45, 8 October 2017 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Finding | |
---|---|
Title | Inadequate Calculations for Backfit Modifications |
Description | The inspectors identified a finding of very low safety significance with an associated NCV of 10 CFR Part 50, Appendix B, Criterion III, Design Control, with two examples, for failing to perform adequate electrical design calculations to support modifications to the degraded voltage protection scheme. The first example involved the failure to analyze motor starting capability based on voltages afforded by the degraded voltage relay scheme. The second example involved the failure to perform conservative calculations to show that spurious grid separation would not occur during accidents due to action of the degraded voltage relays. This finding was entered into the licensees corrective action program. The finding was more than minor because it was associated with the Mitigating Systems cornerstone attribute of design control and affected the cornerstone objective of ensuring the availability, reliability, and capability of safety-related equipment to respond to initiating events to prevent undesirable consequences. Specifically, the licensee failed to confirm the adequacy of new degraded voltage relay set-points by ensuring motors had adequate voltage to start if safety buses remained connected to offsite power during a loss of coolant accident with degraded voltage. In addition, the licensee failed to ensure that spurious grid separation would not occur during accidents due to action of the degraded voltage relays. This finding is of very low safety significance (Green) because the design deficiency was confirmed not to result in loss of operability or functionality. The inspectors concluded that the cause of the finding was related to the cross-cutting aspect of Human Performance, Resources, because the licensee did not provide complete, accurate, and up-to-date design documentation to assure nuclear safety. (IMC 0310, Section 06.01.b.(3) H.2(c) |
Site: | Fermi |
---|---|
Report | IR 05000341/2010006 Section 1R21 |
Date counted | Jun 30, 2010 (2010Q2) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.21 |
Inspectors (proximate) | B Jose C Baron C Brown C Moore G Skinner L Kozak M Jones P Lougheed Z Falevitsb Jose C Baron C Brown C Moore G Skinner L Kozak M Jones P Laugheed Z Falevit |
CCA | H.7, Documentation |
INPO aspect | WP.3 |
' | |