ML17053A239 | 14 November 1978 | LER#78-038/03L-0 on 781025:review of N1-ISP-RE22 Test Results Found 12 Instances Where Procedure Was Violated. Caused by Carelessness in Procedure Implementation. Re-instruction & Closer Supervision Instituted | |
ML17059C101 | 24 June 1998 | LER 98-014-00:on 980525,noted Differences Between Actual Valve Weights & Weights Shown on Engineering Drawings.Caused by Vendor Failing to Provide Accurate Valve Weights.Revised Valve Drawings & Associated Calculation,Per 10CFR21 | Time of Discovery |
ML17341B665 | 5 August 1982 | LER 82-011/03L-0:on 820802,oil Leak on Fuel Oil Supply Manifold Discovered on Diesel Fire Pump.Caused by Defective Braze Joint.Leak Repaired by Manufacturer | |
ML18004C006 | 13 April 1987 | LER 86-002-01:on 861104,procedure N2-OSP-RMC-W0002 Ran for Over 2 H Thereby Violating Tech Specs.Caused by Personnel Error & Procedure Deficiency.Temporary Change Notice Issued to procedure.W/870413 Ltr | |
ML18037A141 | 8 December 1978 | LER#78-040/03L-0 on 781113:#112 Core Spray Topping Pump Motor Breaker Closed Starting Pump But Breaker Closing Spring Motor Was Running Continuously & Not Charging Closing Spring.Caused by Misaligned Motor Assembly at Latching Pawl | |
ML18037A149 | 28 December 1978 | LER 78-041/04T-0 on 781220:during Impingement Sampling Only 23 Samples (22 Hourly Samples & One 2-hr Sample) Were Collected Instead of 24 Required Samples,Caused by one-time Personnel Scheduling Change | |
ML18037A163 | 13 March 1979 | LER 79-001/03L-0 on 790218:during Performance of Surveillance,Test Flow Comparator 11 Did Not Produce Rod Block within Required Tolerance.Caused by Defective Rod Comparator.Component Replaced & Setpoint Left at 14% | |
ML18037A164 | 20 March 1979 | LER 79-002/01T-0 on 790306:during Inservice Insp of Emergency Condenser Steam Supply Line,Six Reportable Indications Found.Caused by Intergranular Stress Corrosion Cracking.Elbow & safe-end Will Be Replaced | |
ML18037A166 | 23 April 1979 | LER 79-002/01X-1 on 790306:during Refueling Outage While Preparing Emergency Condenser Steam Nozzle 5-NB for Replacement of safe-end,discovered Inconel Weld Was Removed from Nozzle.New Safe End Installed | |
ML18037A167 | 1 May 1979 | LER 79-005/03L-0 on 790401:during Periodic Type C Leakage Test,Valves IV-68-06,IV-201-09,IV-201-10 & IV-58.1-02 Were Found to Be in Excess of Tech Specs.Cause Unknown.Repairs Will Be Made During Outage | |
ML18037A169 | 23 May 1979 | LER 79-010/03L-0 on 790424:during Refueling Outage, Containment Vacuum Relief Valve 68 IV-10 Flange Failed Leak Rate test.O-rings Replaced on Flange | |
ML18037A172 | 31 May 1979 | LER 79-008/03L-0 on 790510:during Refueling Outage, Containment Spray Heat Exchangers 112 & 121 Failed Leak Rate Test.Caused by Tube Leaks.Tubes Plugged | |
ML18037A173 | 31 May 1979 | LER 79-009/03L-0 on 790510:during Refueling Outage,Site Operations Review Committee Failed to Review Temporary Change to Maint Procedure N1-MP-7.11 within 7-day Limit. Change Subsequently Reviewed | |
ML18037A174 | 31 May 1979 | LER 79-012/01T-0 on 790523:concrete Anchor Bolt Deficiencies & Missing Seismic Restraints Were Discovered on Class I Seismic Piping Sys.Caused by Incorrect Installation.Concrete Anchor Bolt Repair Program Will Be Completed by 791231 | |
ML18037A176 | 14 June 1979 | LER 79-014/03L-0 on 790319:during Refueling Outage,Core Spray Sys Snubber 40-HS-10 Found Inoperable.Caused by Worn Piston Seals on Core Spray Snubber Resulting in Loss of Fluid from Snubber.Seals Replaced & Snubber Reinstalled | |
ML18037A177 | 14 June 1979 | LER 79-011/03L-0 on 790517:during Refueling Outage, Discovered That Radiographer Received Overexposure of 3,790 Millirems for Second Quarter 1979.Cause Unknown & Under Investigation.Discussed Further in 790615 Ltr to NRC | |
ML18037A181 | 9 July 1979 | LER 79-016/03L-0 on 790626:failure to Review Temporary Electrical Maint Procedure within Seven Days.Review Made & Approvals Received | |
ML18037A182 | 9 July 1979 | LER 79-017/03L-0 on 790612:containment Spray Water Intertie Valves Leaked Causing Failure of Integrated Leak Rate Test. Valves Removed,Cleaned & re-installed | |
ML18037A188 | 10 August 1979 | LER 79-018/03L-0 on 790726:vacuum Relief Sys Switch 68-12B Failed to Open at Proper Setpoint.No Cause Identified.Switch Adjusted to Proper Setpoint | |
ML18037A194 | 7 September 1979 | LER 79-021/04T-0:on 790905,noted That Analysis of Excesssive Nuclide Water Sample Concentrations Was Not Completed within 30 Days.Caused by Late Rept by Contractor & High Influx of Samples.Addl Personnel Added | |
ML18037A197 | 10 September 1979 | LER 79-019/03L-0:on 790816,during Steady State Operation, Routine Mgt Review Disclosed Failure to Complete Five Surveillance Tests on Schedule.Tests Immediately Performed & Completed.Personnel Instructed to Follow Published Schedule | |
ML18037A198 | 10 September 1979 | LER 79-020/03L-0:on 790901,during Steady State Operation, Drywell Cooler 14 Tripped & Leakage Increased to Above Five G/Minute.Caused by Cooler Tube Leak.Cooler Isolated & Returned to Acceptable Level.Shutdown Terminated | |
ML18037A203 | 19 September 1979 | LER 79-013/03L-1:on 790525,during Refuelling Outage,Three Instrument Surveillance Procedures Were Implemented Before Required Temporary procedure-change Signatures Were Obtained.Cause Not Stated | |
ML18037A204 | 1 October 1979 | LER 79-022/01T-0:on 790918,noted Failure to Install Seismic Constraint on Containment Spray Sys Outside Primary Containment Per Const Drawings.Initiated Design & Order to Install Constraint.Containment Spray Loop Inoperable | |
ML18037A207 | 2 November 1979 | LER 79-023/03L-0:on 791004,cooling Water Pump of Diesel Generator 103 Tripped.Caused by Burned Contacts in Breaker. Breaker Repaired & Pump Started Manually.Preventative Maint Procedure Will Be Revised | |
ML18037A209 | 19 November 1979 | LER 79-025/03L-0:on 791027,during Surveillance Testing, Personnel Unable to Zero Side Average Power Range Monitor Flow Converter 11.Caused by Component Failure.Entire Unit Replaced & Problem Eliminated | |
ML18037A233 | 16 January 1980 | LER 80-002/04L-0:on 800109,during Steady State Operation, Review of Differential Recorder Revealed Condenser Inlet/ Screenwell Discharge Differential Temp Went Over Established Limits.Caused by Instrument Malfunction | |
ML18037A235 | 10 January 1980 | LER 80-001/03L-0:on 800102,during Steady State Operation, Calculations Determined Planar Linear Heat Generation Rate Exceeded Tech Specs.Cause Unknown.Power Decreased. Calculation Revealed Heating Generation Rate within Limits | |
ML18037A236 | 21 January 1980 | LER 80-003/01T-0:on 800109,lab Analysis Not Performed on Charcoal Filter Samples from Rx Bldg & Control Room Emergency Ventilation Sys Per Tech Specs.Caused by Change in Operating Cycle Length.Will Revise Surveillance Schedule | |
ML18037A240 | 15 February 1980 | LER 80-005/01X-0:on 800203,engineering Evaluation of GE SIL 299 Required That low-low Setpoint for Reactor Core Water Level Be Raised 20 Inches.Caused by Efforts to Precisely Measure Actual to Indicated Water Level Difference | |
ML18037A241 | 20 February 1980 | LER 80-006/04L-0:on 800123-24,condensor Inlet/Circulating Water Discharge Temp Exceeded Tech Spec Limit.Following Flow Reversal,Discharge Temp Exceeded Lake Ambient by More than Tech Spec Limit.Caused by Instrument Failure | |
ML18037A243 | 20 March 1980 | LER 80-007/03L-0:on 800303,while Shutdown for Maint,Attempts to Close Both Air Operated Outside Main Steam Isolation Valves Failed.Caused by Rust Buildup in Pilot Shuttle.New Instrument Air Sys Is Being Installed | |
ML18037A245 | 20 March 1980 | LER 80-008/03L-0:on 800315,during Steady State Operation, Alarm in Control Room Signaled Loss of Flow to Stack Gas Sampling Sys.Caused by Stack Sample Flow Inlet Valve Failing Closed,Due to Arcing Relay Contacts | Grab sample |
ML18037A262 | 3 June 1980 | LER 80-010/03L-0:on 800528,while Performing Valve Checks, Operator Discovered Cardox Tank Pressure Below Tech Spec Limits.Caused by Delivery of Too Low Temp Carbon Dioxide by Supplier.Low Pressure Alarm Connected | |
ML18037A263 | 3 June 1980 | LER 80-009/03L-0:on 800521,during Steady State Operation, Attempts to Stroke 122 Containment Spray Isolation Valve Failed.Caused by Isolation Valve Solenoids Being Dirty. Revising Procedures to Require Periodic Maint for Valve | |
ML18037A276 | 22 July 1980 | LER 80-011/04L-0:on 800623,recorder Review Showed Condenser Inlet/Circulating Water Discharge Delta Temp Had Exceeded Tech Spec Limit on 800620-23.Station Load Reduced,Recorder Scale Expanded & Tech Spec Change Initiated | |
ML18037A278 | 1 August 1980 | LER 80-012/03L-0:on 800419,during Surveillance Testing of Turbine Anticipatory Trip Bypass,Rx Scram Switch 02-13A Was Operating Outside Setpoint.Caused by Instrument Drift.Switch Readjusted & Will Be Tested Monthly | |
ML18037A281 | 8 August 1980 | LER 80-014/03L-0:on 800717,during start-up Performance for IE Bulletin 80-17 Auto Scram Test,Operability Test Attempted on Valve During Shutdown Period.Valve Failed to Open Upon Manual Initiation.Valve Removed & Disassembled | |
ML18037A283 | 18 August 1980 | LER 80-015/04L-0:on 800804,during Steady State Operation, Offgas Monitoring Sys Inadvertently Placed in Purge Mode of Operation.Caused by Technician Error.Sys Returned to Normal Operating Mode,Restoring Sys Operability | |
ML18037A289 | 9 September 1980 | LER 80-019/04T-0:on 800827,during NRC Insp at Normal Operation,Discovered Removable Bottom Door Seals of Outer Door of Reactor Bldg Track Bay Were Not Installed Properly. Caused by Personnel Error | |
ML18037A291 | 29 September 1980 | LER 80-020/03L-0:on 800830,while Experiencing Electrical Storm During Normal Operation,Loss of Meteorological Data Transmission to Control Room Instruments Occurred.Caused by Transceiver Failure.Transceiver Repaired & Returned to Svc | |
ML18037A295 | 20 October 1980 | LER 80-023/03L-0:on 800922,111 Absolute Filter Access Cover Was Found Off Housing.Caused by Residual Pressure in Containment Nitrogen Inerting Line Pressurizing Filter Housing When Torus Venting Initiated.Cover Reinstalled | |
ML18037A296 | 24 October 1980 | LER 80-022/03L-0:on 800927,low Power Range Monitor Detector Failed Rendering Average Power Range Monitor 18 Inoperable. Caused by Internal Shorting.Low Power Range Monitor Will Be Replaced During Next Refueling | |
ML18037A298 | 30 October 1980 | LER 80-024/03L-0:on 800930,during Audit,Discovered That Point Valve Was Not Recorded on 790721 Instrument Surveillance Test for Drywell High Pressure Trip Sys.Caused by Personnel oversight.Two-level Review Instituted | |
ML18037A305 | 5 September 1980 | LER 80-018/03L-0:on 800808,during Normal Operation, Emergency Diesel Generator 103 Fuel Oil Day Tank Low Level Alarm Was Received.Caused by Inadvertent Opening of Day Tank Drain Valve.Tank Refilled.Oil Valve Sys Locked | |
ML18037A307 | 2 December 1980 | LER 80-026/01T-0:on 801118,input Error Discovered Which Resulted in Reduction in Calculated Pressure Margin to Reactor Safety Valve Setpoints During Possible Transients | |
ML18037A309 | 24 November 1980 | LER 80-025/03L-0:on 801028,stack Gas Monitoring Sys Rendered Inoperable When Inadvertently Left in Purge Operation Mode for 9.5-h.Caused by Technician Failing to Return Sys to Normal Operation.Monitor Returned to Operation | |
ML18037A312 | 26 December 1980 | LER 80-027/03L-0:on 801126,operability Tests Were Not Immediately Performed as Required.Caused by Misunderstanding of Intent of Procedure.Testing Performed | |
ML18037A313 | 29 December 1980 | LER 80-028/04T-0:on 801215,results of 801103,26 & 1201 Milk Sample Tests Showed Detectable I-131 at Three Locations. Caused by Chinese Nuclear Weapons Test During Oct.Plant Not Accountable for Detected Levels | |
ML18037A314 | 30 December 1980 | LER 80-031/01T-0:on 801216,feedwater Flow Control Valve Pneumatic Positioner Unit II Vented Excessive Amount of Air. Caused by Cracked & Worn Rubber Goods.Rubber Goods Replaced & Retested |