 Issue dateTitleTopic
ML20084H81115 May 1974AO BFAO-7425W:on 740505,HPCI Sys Failed to Deliver Water to Reactor When Initiated on Low Water Level After Reactor Scram.No Absolute Cause Determined.Possibly Caused by Overspeed Trip of Machine
ML20084H8186 May 1974Telecopy AO BFAO-7425T:on 740505,HPCI Sys Failed to Deliver Water to Reactor When Initiated on Low Water Level Following Reactor Scram.Apparently Caused by Overspeed Trip.Sys Restarted Manually & Performed Satisfactorily
ML20084H82623 May 1974AO BFAO-7419W:on 740429,plant Exceeded ETS Limit of 5 F River Temp License.Apparently Caused by Natural Difference in Temp of Water Between Upstream & Downstream Monitors at 5-ft Depth,Due to Diurnal Solar Heating
ML20084H83419 April 1974AO BFAO-7424W:on 740403,unit Tripped Due to Transmission Interruptions.Caused by Tornados.One 161-kV Line Lost.No Known Corrective Actions
ML20084H84323 April 1974AO BFAO-7423W:on 740413,HPCI Failed to Reach Rated Flow in Required Time During Performance of post-maint Testing at Rated Pressure.Caused by Defective 10,000-ohm Coverter Zero Potentiometer in Combined Ramp Generator & Signal ConverterSafe Shutdown
ML20084H85215 April 1974Telecopy AO BFAO-7423T:on 740414,HPCI Failed to Reach Rated Flow in Required Time.Hpci Returned to Svc After Satisfactory Testing
ML20084H86812 April 1974AO BFAO-7422W:on 740404,damage Discovered to HPCI Turbine Steam Supply Piping Hanger Support Rods,Piping Restraints, Steam Supply Valve FCV 73-16 Limit Switches & Turbine Inboard Bearing Pedestal.Cause by Slug of Water
ML20084H88112 April 1974AO BFAO-7421W:on 740403,diesel Engine D Failed to Start W/Right Bank of Air Start Motors During Surveillance Test of Diesel Generator Redundant Air Start Sys.Caused by Starter Failure Due to Rust & Possible Lack of Adequate Lubrication
ML20084H8845 April 1974Telecopy AO BFAO-7421T:on 740403,start Circuit 2,right Bank of D Diesel,Failed to Start Engine During Surveillance Testing of Diesel Generator Redundant Start Sys
ML20084H8894 April 1974AO BFAO-7420W:on 740325,rod Sequence Control Sys Malfunctioned.Caused by Failed Integrated Circuit.Failed Sequence Logic Board Replaced & Rod Sequence Control Sys Logic Tested Satisfactorily
ML20084H89229 March 1974AO BFAO-7419W:on 740321,diesel Generator a Made Inoperable for 5 H W/O Previous Testing of Eccs.Caused by Personnel Error.Detailed Discussion of Tech Specs Held W/Personnel
ML20084H89427 March 1974AO BFAO-7418:on 740318,RCIC Failed to Reach Rated Flow within Required Time After Manual Initiation.Caused by Malfunction of Egm Control Box Due to Low Power Supply Voltage
ML20084H89726 April 1974Amend to AO BFAO-7417W Re 740315 Failure of Suppression Chamber to Drywell Vacuum Breaker Valve FCV 64-28M to Close Fully
ML20084H90025 March 1974AO BFAO-7417W:on 740315,suppression Chamber to Drywell Vacuum Breaker Valve FCV 64-28M Failed to Close Fully as Indicated by Check Light.Cause Unknown Until Valve Can Be Investigated
ML20084H90312 September 1974AO BFAO-7416W:on 740312,HPCI Egm Box Failed.Caused by Defective Transistor.Transistor Replaced
ML20084H90821 March 1974AO BFAO-7416W:on 740312,HPCI Turbine Failed to Reach Rated Speed & Flow During Surveillance Testing.Apparently Caused by Inability of Governor to Respond.Cause Being InvestigatedSafe Shutdown
ML20084H91213 March 1974Telecopy AO BFAO-7416T:on 740312,HPCI Turbine Failed to Reach Rated Speed During Manual Initiation Test. Investigation Underway to Determine Cause
ML20084T96626 April 1976Telecopy AO BFAO-50-259/763T Re Potential Design Deficiency. Power Supplies to Standby Liquid Control Pumps Locked Out Until Accident Signal Cleared or Normal Voltage Restored to Shutdown Boards
ML20084T96923 January 1976AOs BFAO-50-259/761W & BFAO-50-260/762W:on 760114,diesel Generator D Failed Monthly Surveillance Test.Caused by Failure of Hydraulic Actuator to Respond Properly to Signals from Electrical Governor
ML20084T97515 January 1976Telecopies AO BFAO-50-259/761T & BFRO-50-260/762T:on 760114, Diesel Generator D Failed Monthly Surveillance Test.Caused by Mechanical Governor Problems
ML20084U4156 July 1973AO BFAO-731W:on 730628,refueling Interlock Failed.Caused by Switch Being Loosened or Misaligned When Switch Actuating Arm Passed Over Power Cable Which Had Caught Under Platform Frame.Switch Readjusted
ML20084U42729 June 1973Telecopy AO BFAO-731T:on 730628,rod Permissive Light Remained Lit When Loaded Fuel Grapple Moved Over Reactor Pressure Vessel.Caused by Limit Switch Adjustment on Refueling Platform.Switch Readjusted & Functionally Tested
ML20085E93810 October 1975AO BFAO-50-259/75-10W:on 751001,diesel Generator Power Supply Unavailable Automatically to RHRSW Pump Running Continuously to Supply Water.Caused by Commencement of Mod Second Phase Prior to Completion of First Phase
ML20085E9559 July 1975AO BFAO-50-260/759T:on 750709,broken Stem Found on second- Stage Pilot of Main Steam Release Valve 1.Break Point Just Under Lock Nut Above Actuating Piston.Site Inspector Advised
ML20085E96318 July 1975AO BFAO-50-260/759W:on 750322,during Second Stage Relief Valve Testing & Refurbishing,Piston & Stem Locknut Found Loose in Air Actuator Chamber on Valve 2 PCV-1-31.Stem & Nut Drilled Twice.New second-stage Stem Installed
ML20085E97628 May 1975Telecopy Message of AO BFAO-50-259/759T:on 750527,signal Cable Inadvertently Disconnected,Making a & B Source Range Monitors Unavailable.Cables Reconnected & Function Restored
ML20085E97830 May 1975AO BFAO-50-259/758W:on 750521,diesel Generator a Failed to Start During Routine Surveillance Test.Caused by Rust & Grit in Starters Due to Moisture in Air Sys & Inadequate Lubricator Operation.Airline Strainers Cleaned
ML20085E98222 May 1975Telecopy Message of AO BFAO-50-259/758T:on 750521,diesel Generator a Failed to Start During Routine Surveillance Test.Air Motors Changed & Testing Accomplished
ML20085E98530 May 1975AO BFAO-50-260/757W:manual Valve in Drive Water Supply on Control Rod Drive Module 50-15 Found in Open Position.Cause Unknown.Valve Repositioned to Required Closed Position
ML20085E99621 May 1975Telecopy Message of AO BFAO-50-260/757T:on 750520,A Drive Water Supply Valve to Control Rod Drive Found Opened During Surveillance Instruction Performance
ML20085F02227 March 1975AO BFAO-50-259/755W:on 750318,one Less Senior Reactor Operator Was on Shift than Required Per Tech Spec.Caused by Scheduling Error.Weekly Shift Schedule Revised to Indicate Licenses Held by Personnel
ML20085F02425 April 1975AO BFAO-50-259/757W:on 750416,LPCI Injection Valve FCV-74-52 Became Inoperable Electrically.Caused by Bolt Fatigue Failure Due to Vibration,Resulting from Loose Bolts Securing Drive Motor to Valve.Spare Motor Installed
ML20085F03017 April 1975Telecopy Message of AO BFAO-50-259/757T:on 750416,drive Motor Support Bolts Sheared Off LPCI Injection Valve FCV-74-52,making Valve Inoperable Electrically
ML20085F03525 January 1975Telecopy Message of AO BFAO-50-260/754T:on 750123,insp Revealed That Four Bergen-Paterson Arrestors Had Lost Hydraulic Oil & Ability to Function
ML20085F0365 February 1975Telecopy Message of AO BFAO-50-260/755T:on 750205,D Diesel Generator Undervoltage Start RHR Svc Water Pump D1,RHR Pumps 1D & 2D & Core Spray Pumps 1D & 2D Auto Start Feature Found Inoperable for 39 H During Battery Capacity Discharge Test
ML20085F03731 January 1975AO BFAO-50-260/754W:on 750123,four Bergen-Paterson Arrestors Found W/Unacceptable Low Amount of Oil Present During Shock Arrestor Insp.Caused by Small Nick in Sealing Surface of Accumulator Piston Seal.Recommended Seals & O-rings Used
ML20085F0387 February 1975Telecopy Message of AO BFAO-50-259/752T:on 750205,small Leak Discovered in 3/4-inch Carbon Steel Test Connection Outside Containment Boundary During Functional Test of Core Spray Piping Loop 2
ML20085F04215 February 1975AO BFAO-50-259/752W:on 750205,crack Found in 3/4-inch Carbon Steel Test Line on Core Spray Loop II Fullflow Pump Test Loop.Caused by Metal Fatigue Due to Test Connection Line Vibration.Crack Ground Out & Repaired by Welding
ML20085F67820 March 1975AO 50-259/754W:on 750310,while Running Routine Surveillance Test,High Concentrations of Oxygen Discovered in Drywell. Caused by Mixing of Air Retained in Stagnant Areas of Drywell During Initial Purge & Sampling
ML20085F7417 March 1975AO BFAO-50-259/753W:on 750226,main Steam Relief Valve PCV-1-4 Lifted Prematurely & Did Not Reseat Until Reactor Pressure Reached 480 Psig.Cause Unknown.Leakage Suspected. Valves Replaced
ML20085G0009 November 1973AO BFAO-7332W:on 731031,HPCI Condensate Header Low Level Switch LS-73-56A Exceeded Tech Spec Trip Level.Switches Replaced w/1/2-ampere Switch Contacts.New Switches Will Be Replaced W/Original Type Upon Delivery
ML20085G0012 November 1973AOs Bf EAO-7337W-7343W:on 731024-31,fish Killed When Impinged on Intake Screens.Caused by Washing Circulating Water Pump Traveling Screens.Estimate of Number of Fish Impinged on Each Day of Occurrence Submitted
ML20085G0053 March 1975AO BFAO-50-260/756W:on 750221,120-volt Power Supply to RCIC Flow Controller & Suppression Pool Level & Drywell Pressure Indicators Lost.Caused by Mispositioning of 120-volt Selector Switch XS-57-170 to Off Position
ML20085G0242 November 1973AO BFAO-7331W:on 731025,turbine Condenser Low Vacuum Switches PS-2-1A & PS-2-1B Setpoints of 22.75 & 22.8, Respectively,Did Not Meet Tech Spec Requirement.Switches Inspected & Reset.Test Frequency Increased to Biweekly
ML20085G03426 October 1973Telecopy AO BFAO-7331T:on 731025,turbine Condenser Low Vacuum Switches PS-2-1A & PS-2-1B Setpoints of 22.75 & 22.8, Respectively,Did Not Meet Tech Spec Limit
ML20085G04122 October 1973Telecopy AO BFEAO-7334T:on 731021-22,listed Fish Impinged on Intake Screens
ML20085G04614 February 1975AO BFAO-50-260/755W:on 750205,4-kv Shutdown Board D Emergency Control Bus 250-volt Dc Power Supply Lost.Caused by Inadequate Battery Discharge Surveillance Instruction. Changed Instruction Includes Transferance Step
ML20085G04824 October 1973AOs Bf EAO-7331-7336:on 731014 & 17-23:fish Killed When Impinged on Intake Screens.Incidents Occurred While Washing Circulating Water Pump Traveling Screens.Number of Fish Impinged on 731013 Revised
ML20085G08529 January 1975AO BFAO-50-26/753W:on 750119,relief Valve PCV-1-4 Operated Spuriously Several Times.Caused by second-stage & pilot- Stage Leakage Due to Indentation in Seat & Disc.Relief Valve Replaced
ML20085G09724 January 1975AO BFAO-50-260/752W:on 750116,RCIC Turbine Tripped.Caused by Misposition of Mechanical Overspeed Emergency Tappet Nut. Nut Rotated for Proper Alignment W/Emergency Head Lever