Text

PARAMETER Dissolved Oxygen Chloride Fluoride TABLE 3.4-2 REACTOR COOLANT SYSTEM CHEMISTRY LIMITS STEADY-STATE LIMIT< 0.10 ppm< 0.15 ppm< 0.15 ppm TRANSIENT LIMIT< 1.00 ppm< 1.50 ppm< 1.50 ppm Limit not applicable with Tavg less than or equal to 250'F.I SHEARON HARRIS -UNIT 1 3/4 4-27 Amendment No.

TABLE 4.4-3 REACTOR COOLANT SYSTEM CHEMISTRY LIMITS SURVEILLANCE REQUIREMENTS PARAMETER Dissolved Oxygen SAMPLE AND ANALYSIS FREQUENCY At least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Chloride At least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> At least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Fluoride Not required with TI, less than or equal to 250 0 F SHEARON HARRIS -UNIT 1 3/4 4-28 Amendment No.