ML13255A275

From kanterella
Revision as of 15:43, 28 April 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Final Safety Analysis Report (Fsar), Amendment 110, Section 3.6, Protection Against Dynamic Effects Associated with the Postulated Rupture of Piping
ML13255A275
Person / Time
Site: Watts Bar Tennessee Valley Authority icon.png
Issue date: 08/14/2013
From:
Tennessee Valley Authority
To:
Office of Nuclear Reactor Regulation
Shared Package
ML13255A164 List: ... further results
References
Download: ML13255A275 (299)


Text

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-1WATTS BARWBNP-1103.6 PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPINGGeneral Design Criterion 4 of Appendix A to 10 CFR 50 requires that structures, systems, and components important to plant safety be protected from the dynamic effects of a pipe rupture. This section of the FSAR describes the design measures necessary to ensure compliance with this requirement. This section is subdivided into Part A and Part B. To be consistent with the standard format, all sections and subsection numbers are suffixed with either A or B.Part A (3.6A) includes all piping systems inside and outside containment except the reactor coolant loop piping. The reactor coolant branch lines, however, are within the scope of this part. Also, jet impingement considerations of the reactor coolant loop on components other than those associated with the primary loop are within the scope of this report.Part B (3.6B) includes the reactor coolant loop system except as stated in 3.6A.3.6A PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING (EXCLUDING REACTOR COOLANT SYSTEM PIPING)Criteria presented herein regarding break size, shape, orientation, and location are in accordance with the guidelines transmitted to TVA by the NRC in letter, dated December 1972, and subsequent amendments for outside containment, and NRC Regulatory Guide 1.46 for inside containment. These criteria also include considerations which are further clarified in the NRC Branch Technical Positions ASB3-1 and MEB 3-1 where appropriate. Arbitrary intermediate breaks (AIBs) postulated in accordance with the documents noted above are eliminated by NRC Generic Letter 87-11

[4]. The final routing of field routed systems will not be completed until late in the plant construction schedule. Field-routed piping generally possesses very little potential, insofar as their functions are concerned, toward affecting plant shutdown. Their failure can, however, cause damage to other components and equipment, especially electrical, which may be required for shutdown of the plant. Field-routed and field-located items such as electrical conduit, cable trays, instrument and control lines, and junction and terminal boxes, etc., are protected as required for plant shutdown. Where field routing was required, guidance was provided to minimize the number of unacceptable interactions. A followup field review and evaluat ion for identifying unacceptable interactions and ensuring implementation of corrections is performed.The following definitions and assumptions are applicable to this section:DEFINITIONS 1Acceptable Interaction

3.6-2PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110A pipe rupture interaction for which, from a systems standpoint, the net required safety functions for a particular rupture are not impaired when assuming a single active component failure.

2Active ComponentAny component which must perform a mechanical motion or change of state during the course of accomplishing a primary safety function.

3Double-Ended RuptureA circumferential pipe rupture where flow is sustained from both ends of the break.4Environmental EffectsThe wetting, pressure, temperature, flammable, radiation, etc., conditions within the zone of influence (Definition 28) of a pipe rupture.

5Essential Systems and ComponentsSystems and components required to shutdown the reactor and/or mitigate the consequences of a postulated pipe failure without offsite power. The seismic classification of essential components and systems is in accordance with Regulatory Guide 1.29.

6High Energy Fluid SystemsFluid systems that, during normal plant conditions, satisfy the following: (a)Maximum operating temperature exceeds 200°F, and (b)Maximum operating pressure exceeds 275 psig.Systems may be classified as moderate energy (see Definition 13) if the total time that the above conditions are exceeded is less than either of the following: (a)One percent of the normal operating life span of the plant.(b)Two percent of the time period required for the system to accomplish its design function.

7Inside ContainmentInside containment is defined for pipe rupture evaluation purposes to include all piping inside the Shield Building and the main steam valve rooms. The

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-3WATTS BARWBNP-110actual containment boundary for integrity purposes is normally taken at the second isolation valve.

8Jet Impingement ForceThe jet force on an object resulting from a ruptured pipe. The magnitude of this force depends on such parameters as the thermodynamic conditions of the fluid in the pipe, distance of the pipe rupture from the target and the shape of the target.

9 Jet ThrustThat reactive dynamic force on a ruptured pipe due to a fluid being accelerated out of a break.

10Line-Mounted ValvesValves located in a line and supported by the line.

11Loss-of-Coolant Accident (LOCA)LOCA is defined as a net loss of reactor coolant inventory when makeup is provided only by the normal makeup system and an orderly shutdown of the plant is prevented. Normal makeup is sized to maintain a constant reactor coolant system (RCS) inventory with a rupture equivalent to a 3/8-inch diameter hole. Therefore, a rupture is considered a LOCA when the flow rate is greater than the equivalent flow from a 3/8-inch diameter hole.

12LOCA BoundaryFor piping extended from the RCS, the boundary of postulated pipe rupture which cannot be isolated when assuming a single active failure shall be defined as follows: (a)First locked closed or administratively closed isolation valve (pressurizer safety valves are examples). The valves forming the Class1 boundary in all drain lines are considered as administratively closed.(b)Second of two normally open, remotely operable, independent isolation valves capable of automatic closure and verification that they will close.(c)First normally closed check valve capable of verification that it is closed and capable of providing isolation from a reactor coolant source.(d)Second of two normally open check valves capable of verification that they will close and capable of providing isolation from a reactor coolant source. (Verification that a check valve will close should be interpreted 3.6-4PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110as meaning capable of periodic test that will verify its capability of closure, such as during a refueling outage.)(e)First normally open and remotely operable automatic isolation valve following a normally open check valve (capable of providing isolation from a reactor coolant source) if both are capable of verification that they will close.If a pipe failure beyond the above defined boundary of possible isolation could result in a normally open boundary valve failing to close, then a LOCA may exist beyond that boundary.

13Moderate Energy Fluid Systems Fluid systems that, during normal plant conditions, satisfy either of the following: (a)Maximum operating temperature is 200°F or less or (b)Maximum operating pressure is 275 psig or less.Other systems which may be classified as moderate energy are discussed in Definition 6.

14Normal Plant Conditions Plant operating conditions during reactor startup, refueling, operation at power, hot standby, or reactor cooldown to cold shutdown condition.

15Outside ContainmentOutside containment includes all of those regions not included in the definition of 'Inside Containment' (Definition 7).

16 Pipe WhipThe movement of a pipe caused by jet thrust resulting from a pipe failure. Pipe whip is assumed to occur in the plane defined by piping geometry and configuration unless limited by structural members, pipe restraints, or pipe stiffness.

17Primary Safety FunctionThe passive or active function of a structure, system, or component which must remain functional to assure directly: (1) the integrity of the RCPB, (2) the capability to shutdown the reactor and maintain it in a safe shutdown condition, or (3) the capability to prevent or mitigate the consequences of accidents which could result in potential offsite exposures in excess of the guideline exposure of 10 CFR 100.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-5WATTS BARWBNP-110 18Postulated Piping FailuresLongitudinal splits, circumferental ruptures, or through-wall leakage cracks.

19Protective Structures or CompartmentsStructural units provided to separate or enclose redundant trains of safety related systems or enclose high and moderate energy lines. (These structures are designed as Seismic Category I.)

20Reactor Coolant Pressure Boundary (RCPB)Those pressure containing components such as pressure vessels, piping, pumps, and valves, which are: (a)Part of the reactor coolant system or (b)Connected to the reactor coolant system, up to and including any of the following:(i)The outermost containment isolation valve in system piping which penetrates the containment.(ii)The second of two valves normally closed during normal reactor operations in system piping which does not penetrate the containment.(iii)The reactor coolant system safety and relief valves.

21Safety RelatedThose plant features which are important to safety because they perform either a primary safety function or a secondary safety function.

22 Secondary Safety FunctionThe function of a portion of a structure, systems or component which must retain limited structural integrity because its failure could jeopardize the achievement of a primary safety function or because it forms an interface between Seismic Category I and Seismic Category I(L) or nonseismic plant features.23Seismic Category IThose structures, systems, or components which perform primary safety functions are designated as Seismic Category I and are designed and constructed so as to assure achievement of their primary safety functions at all times including a concurrent safe shutdown earthquake (SSE).

3.6-6PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 24Seismic Category I(L)Those portions of structures, systems, or components which perform secondary safety functions and are designed and constructed so as to assure achievement of their secondary safety functions at all times including a concurrent safe shutdown earthquake (SSE).

25Shutdown Logic DiagramA logic diagram identifies safety related systems and safety functions and actions required for shutdown to safe conditions.

26Single Active Component FailureA single active failure is the failure of an active component to complete its intended function upon demand. The failure of an active component of a fluid system is considered to be a failure of the component to perform its function not the loss of structural integrity. The direct consequences of a single active failure are evaluated. (A single active failure is postulated to occur simultaneously with the pipe failure; passive failures are not postulated.)

27Terminal EndsExtremities of piping runs that connect to structures, components (e.g., vessels, pumps, etc), or pipe anchors that act as rigid constraints to piping thermal expansion. A branch connection to a main piping run may be considered as a terminal end of the branch run unless each of the following conditions are met: (a)That branch is modeled with the main piping run.(b)A rigorous ASME, Class 1, 2, or 3 analysis is conducted.(c)The nominal size of the branch line, in the vicinity of the branch connection, is greater than or equal to one-half the nominal size of the run.28Zone of InfluenceThe maximum physical range of the direct effects of pipe whip, jet impingement, and/or the environmental effects resulting from a pipe failure.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-7WATTS BARWBNP-110 ASSUMPTIONSIn analyzing the effects of postulated piping failures, the following assumptions shall be made relative to plant and system operation before and after a pipe failure.

1 Operating ModeAll normal plant operating modes (see Definition 14) shall be investigated when evaluating the effects of a postulated pipe failure.

2Single Active Component FailureA single active failure is assumed in systems used to mitigate consequences of the postulated piping failure and to shutdown the reactor. The single active failure is assumed to occur in addition to and concurrent with the postulated piping failure and any consequences of the piping failure.

3Available SystemsAll available systems, including those actuated by operator actions, may be employed to mitigate the consequences of a postulated piping failure. In judging the availability of systems, account shall be taken of the postulated failure and its consequences such as unit trip and loss of offsite power and of the assumed single active component failure and its consequences. The feasibility of carrying out operator actions shall be judged on the basis of ample time and adequate access to equipment being available for the proposed actions. No operator action is assumed to be initiated for at least 10 minutes after pipe failure.

4 Offsite PowerIn general, if it is the worst case, offsite power shall be assumed to be unavailable during a portion of or throughout the sequence of events that follow a pipe failure. This loss of offsite power shall be assumed to act concurrently with the postulated pipe failure and the single active failure. If it can be shown that the loss of offsite power is not a consequence of the pipe failure, then a loss of offsite power is not assumed.

5Unintended Operation of EquipmentThe performance of an unintended active function by equipment not within the zone of influence of a pipe failure shall not be postulated. Unintended operation of equipment within the zone of influence of the pipe failure may occur if caused by the pipe failure, provided the unintended operation is a credible postulation. Unintended operation will not be considered to place equipment in any operating mode other than those modes for which it is normally required to function.

3.6-8PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 6Operator ResponseIt shall be assumed that a proper sequence of events is initiated by the operator to bring the plant to a safe condition, with the capability of going to a cold shutdown if required. However, it shall be assumed that no operator action is initiated for at least 10 minutes after pipe failure. Additional time will be allocated for actions outside the main control room.

3.6A.1 Postulated Piping Failures in Fluid Systems Inside and Outside Containment 3.6A.1.1 Design Bases 3.6A.1.1.1 List of Potential TargetsSafety related systems or components that are located proximate to and are susceptible to the consequences of failures of piping systems are discussed in Section3.11.3.6A.1.1.2 Interaction CriteriaThe following criteria define how interactions are evaluated:

1Pipe Whip InteractionA whipping pipe is not considered to inflict unacceptable damage to other pipes and associated supports of equal or greater size and wall thickness. A whipping pipe is considered capable of only developing through-wall leakage cracks in other pipes of equal or greater size with smaller wall thickness.Any active component (electrical, mechanical, and instrumentation and control) shall be assumed incapable of performing its active function following impact by any whipping pipe unless an analysis or test is conducted to show otherwise. Active components in pipe lines which are allowed to whip are assumed to be incapable of performing their active functions unless the line is sufficiently restrained to control the motion of the components to limits for which they have been qualified.Structural components shall be assumed to fail upon experiencing pipe impact loads that exceed the allowable limits. Plastic action of steel, yield line methods etc., may be used to determine the allowable limits where applicable.

2Jet Impingement InteractionsJet impingement force from a pipe is not considered to inflict unacceptable damage to other pipes and associated supports of equal or greater size and wall thickness. The jet impingement force is considered capable of only developing through-wall leakage cracks in other pipes of equal or greater size with smaller wall thickness.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-9WATTS BARWBNP-110Active components (electrical, mechanical, and instrumentation and control) shall be assumed incapable of performing their function when subjected to a jet unless the active component is enclosed in a qualified spray-proof enclosure (such as one qualified to the NEMA IV, Hosedown Test Standard), the component is known to be insensitive to such an environment, or unless justified that the active function will not be impaired.When the jet consists of steam or subcooled liquid that flashes at the break, unprotected components located at a distance greater than 10 diameters (ID) from the break or equivalent diameter of the crack shall be assumed undamaged by the jet without further analysis. The basis for this criterion is contained in Reference [5].Concrete erosion that may result from jet impingement shall be assumed to be of insufficient magnitude to jeopardize structural integrity.

3Environmental InteractionAn active component (electrical, mechanical, and instrumentation and control) shall be assumed incapable of performing its active function upon experiencing environmental conditions exceeding any of its environmental ratings. However, credit for the component may be taken if sufficient time is available for accomplishing its function before environmental ratings are exceeded.3.6A.1.1.3 Acceptability Criteria 1 SystemsThe capability to eventually achieve a cold shutdown condition shall not be jeopardized even if the pipe failure is followed by a single active failure. The system requirements and available redundancy shall be that shown on a shutdown logic diagram, as supplemented by current system descriptions and equipment lists, for mitigating the effects of the postulated failure.Repair of failures may be considered to assure achievement of the cold shutdown condition where such repairs can be shown to be practicable and timely, and provided the unit can be held in a safe state during the time required for the repair.

2 Protective StructuresThe effects of a postulated piping failure, including environmental conditions resulting from the escape of contained fluids, should not preclude habitability of the control room or access to surrounding areas required for safe control of reactor operations that are needed to cope with the consequences of the piping failure.

3.6-10PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110For piping systems that are enclosed in suitably designed structures or compartments to protect other structures, systems, and components important to safety, pipe breaks shall be postulated according to section 3.6A.2 and the resulting jet thrust loading effects determined. "Worst case" breaks may be postulated in a piping component within the protective structure or compartment at locations which result in the maximum loading from the impact of the postulated ruptured pipe and jet discharge force on each wall, floor, and roof of the structure or compartment, including internal pressurization.3.6A.1.1.4 Protective MeasuresWhere physical separation of source and target and relocation or rerouting are not feasible, the following protective devices will be provided to mitigate the unacceptable consequences of the postulated ruptures.

1Pipe Whip Restraints: An engineered structure which permits limited pipe motion and rotation but limits or prevents unrestricted pipe whip. Crushable material may be used with certain restraints to absorb the kinetic energy of the ruptured pipe, and to limit the loads on the restraint structure.

2Jet Deflector: A barrier which shields a target from the forces and environmental conditions within a jet.

3Impact Barrier: An engineered structure located to limit pipe motion and designed to withstand the impact of a whipping pipe.

4Pipe Sleeve: A metal sleeve that encloses a portion of a process pipe and is designed to restrict and redirect jet forces.Welding for protective structures designed to the requirements of AISC (see Section 3.8.1.2, Item 2) was in accordance with the American Welding Society, "Structural Welding Code," AWS D1.1 (see Section 3.8.1.2, Item 4). Nuclear Construction Issues Group documents NCIG-01 and NCIG-02 (see Section 3.8.1.2, Item 12) may be used after June 26, 1985, to evaluate weldments that were designed and fabricated to the requirements of AISC/AWS.

3.6A.1.2 Description of Piping System ArrangementSeparation was the primary consideration in the piping system layout and arrangement. Where physical separation is not feasible, protective devices shall be provided as required. Protection shall be provided such that the environmental design limits of mechanical and electrical equipment required for safe shutdown are not exceeded. Habitability is discussed in Section 6.4.3.6A.1.3 Safety EvaluationSafety functions shall be identified for initiating events by means of shutdown logic diagrams (SLD). The SLD shall identify at least one success path from each postulated event to each protective function required to prevent the event's potentially PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-11WATTS BARWBNP-110unacceptable results. Each SLD shall include the set of all safety systems necessary to provide the protective function specified at the end of the success path. Shutdown logic diagrams may be supplemented by current system descriptions and equipment lists.For each postulated pipe rupture, credible unacceptable interactions shall be evaluated.Possible interactions shall be evaluated to determine their credibility, damage potential, and acceptability from the standpoint of a safe shutdown capability.In establishing system requirements for each postulated break, it is assumed that a single active component failure occurs concurrently with the postulated rupture.3.6A.2 Determination of Break Locations and Dynamic Effects Associated with the Postulated Rupture of Piping3.6A.2.1 Criteria Used to Define Break and Crack Locati on and Configuration3.6A.2.1.1 Pipe Failure Type, Size, and Orientation 1Circumferential RuptureThe break area is equal to the effective cross-sectional flow area of the pipe at the break location. The plane of the break is normal to the pipe flow axis. Flow may be out of each of the broken ends (double ended rupture) of the pipe, depending upon reverse flow capability. This break is applicable to high energy piping and branch runs whose diameter is greater than 1 inch nominal pipe size. Circumferential ruptures are assumed to result in a lateral offset of one pipe diameter unless mitigating devices, structure members, or the inherent pipe stiffness can be specifically shown to limit this offset.

2Longitudinal SplitThe break area is assumed to be equal to the effective pipe cross-sectional flow area at the break location. If the break occurs at a transition from a smaller pipe to a larger pipe, the flow area is defined as one-half the sum of the upstream and downstream cross-sectional flow areas. The length of the break is two pipe inside diameters and is parallel with the pipe flow axis. As an alternate analysis procedure, fluid flow may be assumed to be from a circular opening equal to the effective cross-sectional flow area of the pipe. In the absence of a detailed analysis, the break is assumed at any location around the circumference of the pipe. Alternatively, a single split may be assumed at the point on the circumference of highest tensile stress as determined by a detailed stress analysis. This break is applicable to high energy pipe that has a nominal pipe size of 4 inches or larger.

3.6-12PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 3Through-Wall Leakage CrackThe crack area may be based on a circular opening with an area equal to an equivalent rectangular opening of one-half the piping inside diameter in length and one-half the wall thickness in width and can be oriented in any direction.3.6A.2.1.2 Break Location 1High Energy Fluid System (A)ASME Section III Class 1 Piping RunsCircumferential ruptures and longitudinal splits, in accordance with Sections 3.6A.2.1.1 (Item 1) and 3.6A.2.1.1 (Item 2), are postulated to occur at the following locations in ASME Section III Class 1 piping:

(1)The terminal ends of piping or branch runs (circumferential ruptures only).(2)At intermediate locations per either one of the following [method a or method b]: (a)At each location of potential high stress and fatigue, such as pipe fittings (elbows, tees, reducers, etc.), valves, and flanges, or (b)At all locations where either one of the following are met.(i)S n < 2.4 S m* (Equation 10) and U > 0.1 (U calculated according to NB-3653.5); or (ii)S n > 2.4 S m* (Equation 10) and S e > 2.4 S m (Equation 12), or S > 2.4 S m (Equation 13), orU > 0.1 (U calculated according to NB-3653.6)

  • For stress qualification to Summer 1973 Code, use 3.0 S
m. For stress qualification to Winter 1982 Code, use 2.4 S
m.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-13WATTS BARWBNP-110Where:Longitudinal splits need not be postulated in Class 1 piping at terminal ends or branch connections.Through-wall leakage cracks are postulated in all high energy pipe outside containment whose diameter is greater than one inch nominal pipe size. Through-wall leakage cracks are not postulated in high energy piping inside containment whose diameter is greater than 1 inch nominal pipe size. However, through-wall leakage cracks are postulated in the main steam and feedwater lines inside containment where impingement could occur on the ice condenser doors. Also, through-wall leakage cracks, may be postulated in other high energy lines in particularly susceptible areas.(B)Break Locations in ASME Section III Class 2 and 3 Piping RunsCircumferential ruptures and longitudinal splits, in accordance with Sections 3.6A.2.1.1 (Item 1) and 3.6A.2.1.1 (Item 2), are postulated to occur at the following locations in ASME Section III Class 2 and 3 piping:

(1)The terminal ends of piping or branch runs (circumferential ruptures only).S n=primary plus secondary stress intensity range, as calculated from Equation 10 in Subarticle NB-3600 of the ASME Boiler and Pressure Vessel Code,Section III for normal and upset plant condition loads with the upset plant condition loads defined as: sustained loads + all system operating transients associated with upset condition + OBE.

S m= allowable design stress intensity value, as defined in Subarticle NB-3600 of the ASME Boiler and Pressure Vessel Code,Section III.

U=the cumulative usage factor, as calculated in accordance with Subarticle NB-3600 of the ASME Boiler and Pressure Vessel Code,Section III.

S e=Nominal value of expansion stress as defined in equation (12) of NB-3653.6 of ASME Code,Section III.

S=The range of primary plus secondary membrane plus bending stress intensity as defined in equation (13) of NB-3653.6 of ASME Code,Section III.

3.6-14PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 (2)At intermediate locations selected by either one of the following method a) or method b): (a)At each location of potential high stress or fatigue, such as pipe fittings (elbows, tees, reducers, etc.), valves and flanges, or (b)At all locations where the stress, S, exceeds 0.8 (1.2 S h + S a)where:Through-wall leakage cracks are postulated as indicated in Section 3.6A.2.1.2 (Item1A).(C)Exceptions for Longitudinal Splits and Circumferential RupturesThe following exceptions are applicable to high energy Class 1, 2 and 3 piping and to high energy non-safety class piping for which a Class 2 or 3 analysis is conducted.

(1)Longitudinal splits need not be postulated at terminal ends or branch connections.

(2)When values defined in 3.6A.2.1.2 are exceeded for Class 1 piping or the stresses exceed 0.8 (1.2 S h + S a), for Class 2 and 3 piping longitudinal splits need not be postulated if the stress in the axial direction is greater than or equal to 1.5 times the stress in the circumferential direction; and circumferential ruptures need not be postulated if the stress in the circumferential direction is greater than or equal to 1.5 times the stress in the axial direction.(D)High Energy Non-Safety-Class and Field Routed Fluid SystemsCircumferential ruptures and longitudinal splits in high energy non-safety-class and high energy field routed piping components are postulated to occur at terminal ends and at intermediate pipe fittings, flanges, and valves. Through-wall leakage cracks are postulated as indicated in Section 3.6A.2.1.2, Item 1A.

S=stresses under the combination of loadings associated with the normal and upset plant condition plus OBE loadings, as calculated from the sum of Equations (9) and (10) in Subarticle NC-3600 of the ASME Boiler and Pressure Vessel Code,Section III.

S h and S a=Allowable stresses at maximum (hot) temperature and allowable stress range for thermal expansion, respectively, for Class 2 and 3 piping as defined in Subarticle NC-3600 of ASME Code,Section III.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-15WATTS BARWBNP-110Break locations in high energy non-safety-class systems, which are analyzed to the same requirements as Class 2 or 3 piping, (these cases will be fully coordinated and documented) may be postulated according to the requirements of Section 3.6A.2.1.2, Item 1B.

2Moderate Energy Fluid SystemsCircumferential ruptures and longitudinal splits are not postulated in any moderate energy lines. Through-wall leakage cracks are postulated in moderate energy piping which exceed a nominal pipe size of 1 inch, but may be excluded where either of the following rules apply.(A)Piping systems are located in areas containing systems and/or components important to safety enveloped by previously postulated high energy breaks in the same region.(B)Where the maximum stress, S, as defined in Section 3.6.A.2.1.2 (Item 1B) is less than or equal to 0.4 (1.2 S h + S a) for Class 2 and 3 piping or where S n by equation 10 is less than or equal to 1.2 S m for Class 1 piping.The cracks should be postulated to occur individually at locations that result in the maximum effects from fluid spraying and flooding. It shall be at any location on the pipe circumference or along the surface of the pipe.

3High/Moderate Energy InterfacesLine supported valves sometimes form the interface between high energy lines and moderate energy lines. In this case, the fixity as implied in the word, 'terminal,' does not exist at the line supported valve. This condition is treated as if there were no terminal.

3.6A.2.1.3 Fail ure ConsequencesThe failure interactions that must be evaluated to determine the consequences of failure are dependent upon the energy level of the pipe considered. They are as

follows: 1High Energy PipingCircumferential ruptures and longitudinal splits (a)Pipe whip.(b)Jet impingement.(c)Environmental effects.

3.6-16PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Through-wall leakage cracks (a)Jet impingement (b)Environmental effects 2Moderate Energy PipingThrough-wall leakage cracks (a)Environmental effects.In particularly susceptible areas, the jet impingement load associated with a through-wall leakage crack in moderate energy piping with the pressure exceeding 275 psig shall also be considered.

3.6A.2.1.4 FloodingFlooding consequences are also considered in addition to the local effects listed above in Section 3.6A.2.1.3 from piping failures. Additional environmental concerns are addressed in Section 3.11.2.

1High Energy Line Breaks (HELBs)For the purposes of flooding evaluations, fluid systems that, during normal plant conditions are either in operation or maintained pressurized under conditions where maximum operating temperature exceeds 200

°F are conservatively classified as high energy. This is bounding since for a given line, the flow from a high energy break emanates from a larger break area than flow from a moderate energy crack. The circumferential rupture is the bounding break for HELB flooding analyses.Systems classified as high energy are re-classified as moderate energy if the total time that the above conditions are exceeded is less than either of the following: (a)1% of the normal operating life span of the plant, or (b)2% of the time required for the system to accomplish its system design function.The systems evaluated for high energy break flooding include the reactor coolant, main steam, feedwater, auxiliary boiler, auxiliary feedwater steam supply, and chemical and volume control system.

2Moderate Energy Line Breaks (MELBs)For the purposes of flooding evaluations, fluid systems are classified as moderate energy that, during normal plant conditions, are either in operation or maintained pressurized (above atmospheric pressure) under conditions PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-17WATTS BARWBNP-110where: (1) The maximum operating temperature is 200

°F or less or (2) the 1or 2% exclusion rules described above are applicable. The through-wall leakage crack is the postulated break for the MELB flooding analysis. Flood levels are calculated for the plant on an area basis. Both submergence and structural loading are addressed in the flooding studies.HELB and MELB flooding effects are evaluated on all essential equipment on a case by case basis. If it is determined that an essential component is not qualified or cannot be demonstrated to operate under the adverse flood conditions, then the essential component is protected. Protection is accomplished by relocating the component or by installing a barrier or curb. Safe shutdown is ensured for design basis HELB/MELB flooding events through these actions.

3.6A.2.1.5 Leak-Before-Break ApplicationThe application of leak-before-break as applied to the primary loop piping is discussed in Section 3.6B.1.In addition, leak-before-break technology has been applied to the pressurizer surge line to eliminate the dynamic effects of a pressurizer surge line rupture as a design basis for Watts Bar Nuclear Plant. This is in accordance with the final rule change to General Design Criteria 4 [Ref. 12]. Authorization for their elimination is discussed in Reference [9] and is based on fracture mechanics results presented in References [10] and [11].3.6A.2.2 Analytical Met hods to Define For cing Functions a nd Response Models 3.6A.2.2.1 Assumptions 1The thrust load acting on the pipe due to a blowdown jet is equal and opposite to the jet.

2The discharge coefficient is equal to 1.0.

3The break opens to its defined size in 1 millisecond.

4For the purpose of estimating jet forces, the blowdown is to an infinite volume at standard conditions.

5The initial fluid condition within the pipe prior to rupture is that for normal plant operating condition.

6The jet profile expansion half angle is 20 degrees.

3.6-18PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 3.6A.2.2.2 Blow down Thrust LoadsThe thrust force at any time, T (t) is given bywhere:E = fluid density at break at time t V E = fluid velocity at break at time t AjE = pipe break exit area P E = control volume pressure at break at time t P A = ambient pressure g c = gravitation constantA simplified analysis may be conducted by assuming that the fluid is blowing down in a steady state condition with frictionless flow from a reservoir at fixed absolute pressure Po. (Po is the initial line pressure.) When the fluid is subcooled, nonflashing liquid, the flow will not be critical at the break area so that:

and If P A <

> P A, the thrust force may be conservatively approximated by: 3.6A.2.2.3 Jet Impingement LoadsThe loads on an object exposed to the jet from a pipe break can be determined from the blowdown thrust and the profile of the impinged object. where Y j= Normal load applied to a target by the jet A i = Cross-sectional area of jet intercepted by target structure A j = Total cross-sectional area of jet at the target structure S F = Shape factor D LF= Dynamic load factorT= Total blowdown thrust at break as calculated in Section 3.6A.2.2.2 = Angle between jet axis and a line perpendicular to the target.The ratio A i/A j represents the proportion of the total mass flow from the jet which is intercepted by target structure. A dynamic load factor of 2.0 shall be used in the absence of an analysis justifying a lower value. The following shape factors are recommended. P E P o 2 K 1+------------ -K K 1------------- -=T1.26 P o A jE=Y j T A i A j-----S F D LFcos= 3.6-20PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Jet impinging on a slab [Figure 3.6-1 sector (a)]Rectangular jet impinging on a pipe larger than jet [Figure 3.6-1 sector (b)]Rectangular jet impinging on a pipe with h greater than D o [Figure 3.6-1 sector (b)] Circular jet impinging on pipe with jet diameter (D j = 2r j) less than pipe diameter [Figure3.6-1 sector (c)]Circular jet impinging on pipe with jet diameter greater than pipe diameter [Figure 3.6-1 sector (d)]These are the most common cases that will occur in the pipe rupture evaluation. Other shape factors may be obtained by idealizing the surface as infinitesimal planes and performing an integration over the area impinged upon by the jet. S F 1=S F 1 h 2 D o---------- -=S F 1 2---=S F10.424 Dj D o--------=S F0.576= PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-21WATTS BARWBNP-1103.6A.2.3 Dynamic Analysis Methods to Verify Integrity and Operability3.6A.2.3.1 General Criteria for Pipe Whip Evaluation 1The dynamic nature of the piping thrust load shall be considered. In the absence of analytical justification to the contrary, a dynamic load factor of 2.0 may be applied in determining piping system response. 2Nonlinear (elastic-plastic strain hardening) pipe and restraint material properties may be considered as applicable. 3Pipe whip shall be considered to result in unrestrained motion of the pipe along a path governed by the hinge mechanism and the direction of the vector thrust of the break force. A maximum of 180° rotation may take place about any hinge. 4The effect of rapid strain rate of material properties may be considered. A 10% increase in yield strength may be used to account for strain rate effects. 3.6A.2.3.2 Main Reactor Coolant Loop Piping SystemThe dynamic analyses applicable to the reactor coolant loop piping are discussed in Section 3.6B.3.6A.2.3.3 Othe r Piping SystemsThe pressure time history, jet impingement load on targets, and the thrust resulting from the blowdown of postulated ruptures in piping systems shall be determined by thermal and hydraulic analyses or a conservative simplified analyses.In general, the loading that may result from a break in piping will be determined using either a dynamic blowdown or a conservative static blowdown analysis. The method for analyzing the interaction effects of a whipping pipe with a restraint will be one of the following: 1Equivalent static method 2Lumped parameter method 3Energy balance method.In the cases where time history or energy balance method is not used, a conservative static analyses model will be assumed. The loading factors to be used for the static model are discussed in Section 3.6A.2.3.5.The lumped parameter method is carried out by utilizing a lumped mass model. Lumped mass points are interconnected by springs to take into account inertia and stiffness properties of the system. A dynamic forcing function or equivalent static loads may be applied at each hypothesized break point with unacceptable pipe whip interactions. Clearances and inelastic effects will be considered in the analyses. 3.6-22PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110The energy balance method is based on the principle of conservation of energy. The kinetic energy of the pipe generated during the first quarter cycle of movement will be assumed to be converted into equivalent strain energy, which will be distributed to the pipe or the support. The strain in the restraint shall be limited to 50% of the ultimate uniform strain.3.6A.2.3.4 Simplified Pipe Whip AnalysisA conservative method may be used to determine for a given rupture whether pipe whip takes place. This method is based on calculation of the minimum internal forces necessary to form a plastic hinge in the pipe, and the number of hinges required for a pipe whip mechanism.Occurrence of a pipe whip is dependent on formation of a sufficient number of hinges to develop a mechanism. Two commonly encountered examples are:A. Cantilever pipe with end loadB. Continuous pipe supported at both ends with lateral loadWhereL, L 1 , L 2 = Distance from support to load Mult = The ultimate moment Twhip = The thrust load at which pipe whip will occur.The applied thrust load shall consider a dynamic amplification factor of 2.0 unless an analysis is performed to justify a lesser value. T whip M ult L----------

T whip 2 M ult 1 L 1------1 L 2------+

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-23WATTS BARWBNP-110 3.6A.2.3.5 Pipe Whip Restraint DesignThe design limits which shall be used in the design of pipe whip restraints are shown in the following table: Type of Design Plastic ElasticLoading CombinationD+L+T a+P a+Y r+Y j+Y m D+L+T a+P a+Y r+Y j+Y mStress/strain limits50% uniform1.5 S m or 1.2 S y,Ultimate strainbut not to exceed 0.7 S uNote: Earthquake and pipe rupture are not assumed to exist concurrently when evaluating the pipe whip restraints.Where:D=Dead load L=Live T a=Thermal load resulting from postulated break P a=Pressure load resulting from postulated break Y r=Pipe restraint reactions resulting from postulated break Y j=Jet impingement load generated by postulated break Y m=Pipe whip impact load resulting from postulated break S m=Design stress - intensity S y=Yield stress S u=Ultimate tensile stressDynamic response amplification was accounted for by multiplication of loads by appropriate dynamic factors or through use of dynamic analysis. The following dynamic load factors were used for the local structure components design.

1For piping system with no gaps at the restraint, a dynamic load factor of 2.0 was applied regardless of pipe size.

2For piping system with gaps not exceeding 1 inch at the restraint, a dynamic load factor of 3.0 may be applied.

3.6-24PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 3A linear interpolation for gaps between zero and 1 inch may be made. The above dynamic factors in items 1 and 2 are applicable to small line (6-inch nominal diameter or less) without subsequent analyses. Items 2 and 3 may also be applied to large lines (larger than 6-inch nominal diameter) providing sufficient analyses are performed to show that the dynamic factor has not been exceeded.

4For gaps in excess of 1 inch, dynamic load factors shall be justified by analyses.3.6A.2.3.6 Energy Absorbing Materials An energy absorbing material (crushable honeycomb) is sometimes used to absorb the kinetic energy of the ruptured pipe and to limit the loads on the restraint structure. For systems where the energy balance method of analysis is used, the kinetic energy of the pipe generated during the first quarter cycle of movement will be assumed to be converted into equivalent strain energy, which will be distributed on the pipe or the support. The actual crush shall not exceed 90% of the available crush depth.

3.6A.2.4 Guard Pipe Assembly Design CriteriaGuard pipes for penetrations are classified as TVA Class K. The chemical and mechanical tests and nondestructive examinations shall be in accordance with the ASME Material Specification. Markings and certified mill tests shall be in accordance with the requirements for process pipe. All welding shall be made in accordance with ASME Code,Section III, NC-4000. All girth butt welds shall be magnetic particle or liquid penetrant inspected in accordance with Appendix IX of ASME Code,Section III. Acceptance standards shall be in accordance with NE-5000.The guard pipe shall be designed for the same temperature and pressure as the process pipe. However, the allowable stresses shall be 90% of yield strength (0.2%

offset) at design temperature.The guard pipe shall be designed to have its lowest natural frequency greater than 33 Hz where possible to allow the zero period acceleration to be used. Where 33 Hz is not practical, the actual frequencies expanded by 10%, shall be used in conjunction with the appropriate floor response spectra, to determine the design acceleration. The seismic loading shall be that which results from input accelerations of 1.5 g horizontal and 1 g vertical for the operating basis earthquake and twice these values for the safe shutdown earthquake.Inservice inspections and accessibility requirements are discussed in Section 5.2.8 for ASME Class 1 systems. Section 6.6 for ASME Class 2 and 3 systems and Section 3.8.2.7.9 for ASME Class MC and metallic liners of Class CC components.

Penetration assemblies to be used for piping penetrations of containment areas are discussed in Section 3.8.2.If circumferential ruptures or longitudinal splits are postulated in the process pipe (in accordance with Section 3.6A.2.1.2) at locations enclosed by the guard pile, the guard PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-25WATTS BARWBNP-110pipe shall be capable of mitigating the consequences of the break. If no circumferential ruptures or longitudinal splits are postulated in the process pipe, arbitrary through-wall leakage cracks shall be assumed and the guard pipe shall be capable of mitigating the consequences of the cracks.

3.6A.2.5 Summary of Dynamic Analysis ResultsA letter from J. E. Gilleland to Mr. Giambusso dated May 16, 1974, submitted CEB Report No. 72-22, "Evaluation of the Effects of Postulated Pipe Failures Outside of Containment for the Sequoyah Nuclear Plant Units 1 and 2." In this letter it was stated that this report is also applicable to the Watts Bar Nuclear Plant and upon completion of the Watts Bar piping outside the containment, any differences between the Sequoyah and Watts Bar designs would be addressed in the Watts Bar FSAR. The major differences between the Watts Bar and Sequoyah designs outside containment are the main steam and feedwater routing in the open bay area of the Control Building.

3.6A.2.5.1 Stress Summary and Isometrics - Inside ContainmentThe stress summary for each of the postulated break locations for the following systems larger than 4 inches in nominal size are presented in Tables 3.6-1 through 3.6-6.Table No.System Description3.6-1Main Steam Lines 3.6-2Main Feedwater Lines3.6-3Auxiliary Feedwater Steam Supply Lines - Unit 1 3.6-3AAuxiliary Feedwater Steam Supply Lines - Unit 2 3.6-4SI Cold Leg Injection 3.6-5RHR/SI Hot Leg Recirculation, Loop 4 3.6-6SI Hot Leg Recirculation, Loops 1, 2, and 3

Isometrics showing break type locations, protective device locations and constrained directions of the above systems are presented in Figures 3.6-2 through 3.6-17.Inside containment the isometrics for Unit 2 are generally opposite hand to Unit 1. The stress summaries and isometrics are based on the analysis current at the time of the amendment submittal indicated on the figures and tables. This information is considered to be representative and presents typical historical results for Units 1 and 2.

3.6-26PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-1103.6A.2.5.2 Summary of Protection Requirements and Is ometrics-Outside ContainmentA summary of protection requirements including break types and locations for main steam and main feedwater lines are presented in Tables 3.6-9 and 3.6-10, respectively. Isometrics showing break types, locations. protective device locations and constrained directions for these lines are shown in Figures 3.6-21 through 3.6-24.Outside containment, the break types, break locations, isometrics, protective device locations and constrained directions for Unit 2 are generally opposite hand to Unit 1. The isometrics and protection requirements reflect the analysis current at the time of amendment submittal indicated on the figures and tables. This information is considered to be representative and presents typical historical results for Units 1 and2. 3.6B PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING 3.6B.1 Break Locations And Dynamic Effects Associated With Postulated Primary Loop Pipe Rupture The dynamic effects of postulated double-ended pipe ruptures in the reactor coolant loop piping have been eliminated from the design basis of the Watts Bar Nuclear Plant by the application of leak before break technology in accordance with the final rule change to General Design Criterion 4 (Reference 12). Authorization for their elimination is provided in Reference [6] and is based on fracture mechanics analysis results presented in References [7] and [8].The plant design bases was revised in several areas to take advantage of the elimination of reactor coolant loop (RCL) pipe breaks. The protective measures taken to mitigate the dynamic effects of these breaks remain in place. However, these protective devices no longer perform a pipe whip restraint function. See FSAR Section 5.5 and Figures 5.5-11, 5.5-12, and 5.5-13.In other areas, design basis analyses have been conducted based on the original postulated double-ended breaks. Even with the elimination of these dynamic effects, these analyses continue to demonstrate the adequacy and acceptability of the plant design. These analyses shall remain the analyses of record unless indicated otherwise in this safety analysis report.Leak-before-break has also been applied to the pressurizer surge line as discussed in Section 3.6A.2.1.5.As stipulated in the final rule change to GDC-4, a non-mechanistic double-ended rupture of the largest pipe in the reactor coolant system is still postulated for the PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-27WATTS BARWBNP-110purposes of containment design, ECCS design, and environmental qualification of electrical and mechanical equipment.Previously postulated breaks in branch lines (except the pressurizer surge line) attached to the reactor coolant loops remain unaffected.

3.6B.2 Analytical Met hods to Define Forcing F unction and Response ModelsThe reactor coolant loop breaks used in determining the forcing functions (discussed below) and in calculating the resulting hydraulic transients and loadings have been eliminated as noted in Section 3.6B.1. However, these analyses envelope the effects of any remaining breaks, e.g., in branch lines at the loop attachment points, and as such continue to demonstrate the adequacy of the design for these loadings. Following is a summary of the methods used to determine the dynamic response of the reactor coolant loop associated with postulated pipe breaks in the loop piping. Detailed descriptions of the methods are given in Reference [1].In order to determine the thrust and reactive force loads to be applied to the reactor coolant loop during the postulated loss of coolant accident (LOCA), it is necessary to have a detailed description of the hydraulic transient. Hydraulic forcing functions are calculated for the ruptured and intact reactor coolant loops as a result of a postulated LOCA. These forces result from the transient flow and pressure histories in the reactor coolant system. The calculation is performed in two steps. The first step is to calculate the transient pressure, mass flow rates, and thermodynamic properties as a function of time. The second step uses the results obtained from the hydraulic analysis, along with input of areas and direction coordinates and calculates the time history of forces at appropriate locations in the reactor coolant loops.The hydraulic model represents the behavior of the coolant fluid within the entire reactor coolant system. Key parameters calculated by the hydraulic model are pressure, mass flow rate, and density. These are supplied to the thrust calculation, together with appropriate plant layout information to determine the time dependent loads exerted by the fluid on the loops. In evaluating the hydraulic forcing functions during a postulated LOCA, the pressure and momentum flux terms are dominant. The inertia and gravitational terms are taken into account in evaluation of the local fluid conditions in the hydraulic model.The blowdown hydraulic analysis is required to provide the basic information concerning the dynamic behavior of the reactor core environment for the loop forces, reactor kinetics and core cooling analysis. This requires the ability to predict the flow, quality, and pressure of the fluid throughout the reactor system. The MULTIFLEX 3.0

[Ref. 17] computer code was developed with this capability, which is an enhancement and extension of MULTIFLEX 1.0 [Ref. 2], NRC reviewed and approved computer code developed for the same space-time dependent analysis of nuclear power plants.

The MULTIFLEX 3.0 features which differ from MULTIFLEX 1.0 are primarily related to vessel forces. The loop forcing functions do not differ significantly from those 3.6-28PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110generated using the NRC approved MULTIFLEX 1.0 model. MULTIFLEX 3.0 has been accepted by NRC for several applications [Ref.13], [Ref. 14], [Ref. 15], [Ref. 16] and has been extensively used for the LOCA analysis of various 2, 3 and 4 loop nuclear plants.MULTIFLEX is a digital computer program for calculation of pressure, velocity, and force transients in reactor primary coolant systems during the subcooled, transition, and the early saturation portion of blowdown caused by LOCA. During this phase of accident, large amplitude rarefaction waves are propagated through the system with the velocity of sound causing large differences in local pressures. As local pressures drop below saturation, causing formation of steam, the amplitudes and velocities of these waves drastically decrease. Therefore,the largest forces across the loop piping due to wave propagation occur during the subcooled portions of the blowdown transient. MULTIFLEX includes mechanical structure models and their interaction with the thermal-hydraulic system, although these features are only involved in the vessel and steam generator modeling. The THRUST computer program was developed to compute the transient (blowdown) hydraulic loads resulting from a LOCA.The blowdown hydraulic loads on primary loop components are computed from the equation.Which includes both the static and dynamic effects. The symbols and units are:F=Force, lb fA=Actual calculated break flow area, ft 2P=System pressure, psia=Mass flow rate, lb m/sec=Density, lb m/ft 3g=Gravitational constant = 32.174 ft/sec 2 A m=Mass flow area, ft 2In the model to compute forcing functions, the reactor coolant loop system is represented by a similar model as employed in the blowdown analysis. The entire loop layout is described in a coordinate system. Each node is fully described by: 1)blowdown hydraulic information, and 2) the orientation of the streamlines of the force nodes in the system, which includes flow areas, and projection coefficients along the three axes of the global coordinate system. Each node is modeled as a separate control volume with one or two flow apertures associated with it. Two apertures are used to simulate a change in flow direction and area. Each force is divided into its x, F144 AP14.7-m*2 gA m 2144------------------------

-+=m*

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-29WATTS BARWBNP-110y, and z components using the projection coefficients. The force components are then summed over the total number of apertures in any one node to give a total x force, totaly force, and total z force. These thrust forces serve as input to the piping/restraint dynamic analysis.The THRUST Code is described in Reference [3].3.6B.3 Dynamic Analysis of the Reactor Coolant Loop Piping Equipment Supports and Pipe Whip RestraintsThe dynamic analysis of the reactor coolant loop piping for the LOCA loadings is described in Section 5.2.1.10.Section 5.2 defines the loading combinations, associated with the reactor piping systems, considered to assure the integrity of vital components and engineered safety features.REFERENCES 1'Pipe Breaks for the LOCA Analysis of the Westinghouse Primary Coolant Loop,' WCAP-8082-P-A (Proprietary) and WCAP-8172-A (Non-Proprietary), January 1975.

2WCAP-8708-PA (Westinghouse Proprietary), WCAP-8709-A (Non-Proprietary), "MULTIFLEX A FORTRAN Computer Program for Analyzing Thermal-Hydraulic Structure System Dynamics," Takeuchi, K., etal, Semptember 1977.

3'Documentation of Selected Westinghouse Structural Analysis Computer Codes,' WCAP-8252, Revision 1, May 1977.

4'Relaxation in Arbitrary Intermediate Pipe Rupture Requirements', NRC Generic Letter 87-11, June 19, 1987.

5'Two Phase Jet Loads' NUREG/CR-2913, January 1983.

6NRC Letter to TVA, dated May 17, 1990, "Safety Evaluation of Primay Loop Piping".7 TVA Letter to NRC dated April 17, 19 89, "Elimination of Primary Loop Pipe Breaks".8"Technical Justification For Eliminating Large Primary Loop Pipe Rupture As The Structural Design Basis For Watts Bar Units 1 & 2", WCAP- 11984 (Non-Proprietary) and WCAP-11985 (Proprietary), November 1988.

9 NRC letter to TVA, dated April 28, 1993, "Leak-Before-Break Evaluation of the Pressurizer Surge Line".

3.6-30PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 10TVA Letter to the NRC dated June 22, 1992 transmitting enclosures, "Technical Justification for Eliminating Pressurizer Surge Line Rupture as the Structural Design Basis for WBN Units 1 and 2", WCAP-12773 (proprietary) and WCAP-12774 (nonproprietary), both dated December 1990.

11TVA letter to the NRC dated March 26, 1993 transmitting supplemental information to the reference 10 letter.

12Federal Register, Volume 52, Number 207, October 27, 1987, 41288.

13WCAP-15029-P-A/WCAP-15030-NP-A, "Westinghouse Methodology for Evaluating the Acceptability of Baffle-Former-Barrel Bolting Distribution Under Faulted Load Conditions," R. E. Schwirian, et al, January 1999.

14WCAP-15245 (Proprietary)/WCAP-15246 (Non-Proprietary), "Control Rod Insertion Following a Cold Leg LBLOCA, D. C. Cook Units 1 and 2," J.A.Barsic, D. C. Garner, Y. C. Lee, K. B. Neubert, C. Yu, February 28, 1999.15WCAP-11004-P/WCAP-11005 (NP), "Comparison of DATA for Beaver Vally Power Station Unit 2 with WCAP-9735 Data, Prepared for NRC Review in Conjunction with Review of WCAP-9735, Docket No. 50-412," D.R.Bhandari, K. Takeuchi, M. E. Willis, November 1985.

16WCAP-11522 (Proprietary)/WCAP-11523 (Non-Proprietary), "Response to NRC Questions on the LOCA Hydraulic Force Analysis of the Beaver Vally Power Station Unit 2, Prepared for NRC Review in Conjunctions with Review of WCAP-9735, Docket No. 50-412," D. C. Garner, M. P. Kachmar, M.R.Wengerd, June 1987 17WCAP-9735 Rev. 2 (Proprietary), WCAP-9736 Rev. 1 (Non-Proprietary), "MULTIFLEX 3.0, A FORTRAN-IV Computer Program for Analyzing Thermal-Hydraulic-Structural System Dynamics Advances Beam Model," Takeuchi, K. et al, February, 1998.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-31WATTS BARWBNP-110Note: All breaks are circumferential ruptures.* Branch connection stresses were not available.** Breaks selected to satisfy the minimum of intermediate breaks are no longer required.

Reflects Analysis Which Was Current at Time of Amendment 51 SubmittalTable 3.6-1 Summary of Combined Stresses at Break Locations - Main Steam Lines (Sheet 1 of 1) FIGURE NO.LINE NO. BREAK NO.

COMBINED STRESS(psi)ALLOWABLE PIPE RUPTURE STRESS0.8(1.2S h + S a) (psi)3.6-23.6-33.6-4 3.6-51-MS-11-MS-21-MS-3 1-MS-4 MS1-B0-1** MS1-B0-2** MS1-B0-3 MS1-B0-4N MS1-B0-5N MS1-B0-6 MS2-B0-1 MS2-B0-2**

MS2-B0-3** MS2-B0-4N MS2-B0-5N MS2-B0-6 MS3-B0-1 MS3-B0-2** MS3-B0-3N MS3-B0-4N MS3-B0-5 MS3-B0-6** MS4-B0-1** MS4-B0-2** MS4-B0-3 MS4-B0-4N MS4-B0-5N MS4-B0-6321162905516925**300924599029432 26230**251752914526407**2776626658310763060514347*

  • 25726378003780037800**378003780037800 37800**378003780037800**3780037800378003780037800*
  • 37800 3.6-32PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Table 3.6-2 Summary of Combined Stresses At Break Locations - Feedwater Lines(Sheet 1 of 2)FIGURE NO.LINE NO.BREAK NO.COMBINED STRESS (psi) ALLOWABLE PIPE RUPTURE STRESS0.8(1.2S h + S a) (psi)3.6-63.6-73.6-8 3.6-91-FW-11-FW-21-FW-3 1-FW-4 FW1-B0-1 FW1-B0-2**

FW1-B0-3N FW1-B0-4N FW1-B0-5N FW1-B0-6** FW1-B0-7 FW9-B0-1N FW9-B0-4N FW2-B0-1 FW10-B0-1N FW2-B0-2** FW2-B0-3N FW10-B0-4N FW2-B0-5N FW2-B0-6**

FW2-B0-7 FW3-B0-1 FW3-B0-2** FW3-B0-3** FW3-B0-4N FW11-B0-4N FW3-B0-6N FW11-B0-1N FW3-B0-7 FW4-B0-1 FW4-B0-2**

FW4-B0-3N FW4-B0-4N FW4-B0-5N FW4-B0-6** FW4-B0-7 FW12-B0-1N FW12-B0-4N 965116919***2443423499*

  • 24519*16306*
    • 24748 23130226581518113407*
    • 19775 978712898***1891518203*
  • 3240032400***3240032400*
  • 32400*32400*
    • 32400 32400324003240032400*
    • 324003240032400***3240032400*
  • PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-33WATTS BARWBNP-110Table 3.6-2 Summary of Combined Stresses At Break Locations - Feedwater Lines (Sheet 2 of 2)Note: All breaks are circumferential ruptures.*Branch connection stresses were not available.
    • Breaks selected to satisfy the minimum of intermediate breaks are no longer required.Reflects Analysis Which Was Current at Time of Amendment 51 Submittal 3.6-34PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Notes:1. C = Circumferential, L = Longitudinal Split2. Not required to be postulated** Breaks selected to satisfy the minimum number of intermediate breaks are no longer required.Reflects Analysis Which Was Current At Time of Amendment 51 SubmittalTable 3.6-3 Summary of Combined Stresses at Break Locations - Auxiliary Feedwater System Steam Supply Lines For Unit 1(Sheet 1 of 1)

FIGURE NO. LINE NO.BREAKNO.COMBINEDSTRESS (psi)ALLOWABLE PIPERUPTURE STRESS0.8(1.2S h + S a) (psi)BREAK TYPE (NOTE 1)3.6-10(Unit 1)1-AFD-81-AFD-7 1-AFD-7 1-AFD-9 1-AFD-9 1-AFD-9 1-AFD -

- AFD8-BO-1 AFD7-BO-1 AFD7-B1-2X 721 719 40**

1 LMM L81**

L82 ** 1814619515 (Note 2)36751 35073 20305 664222438 23087 2300032400324003240032400 32400 32400 32400 32400 32400 C C C C,L C,L C C

C C

C PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-35WATTS BARWBNP-110Note: All breaks are circumferential.** Breaks selected to satisfy the minimum number of intermediate breaks are no longer required.Reflects Analysis Which Was Current at Time of Amendment 51 SubmitttalTable 3.6-3A Summary of Combined Stresses at Break Locations - Auxiliary Feedwater System Steam Supply Line For Unit 2(Sheet 1 of 1)

Figure No. Line No. Break No.CombinedStress (psi)Allowable Pipe Rupture Stress0.8 (1.2 S h + S a) (psi)3.6-10 2-AFD-8AFD8-B0-12142632400(Unit 2)2-AFD-8AFD8-B2-1** - 324002-AFD-7AFD7-B0-11724332400 2-AFD-9AFD7-B2-2**1610432400- 2 219932400

-912542732400

-92**187233240097**1770232400 3.6-36PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Table 3.6-4 Summary of Combined Stresses at Break Locations - SI Cold Leg Injection(Sheet 1 of 2)FIGURENO. LINE NO.BREAK NO.COMBINEDSTRESS(psi)ALLOWABLE PIPE RUPTURE STRESS0.8(1.2S h + S a) (psi)BREAK TYPE(NOTE)3.6-11(Loop 1)1-SI-5SI5-B0-1NSI5-B0-2NSI5-B0-3**300464403821902394483944838172 C C,L C1-SI-506SI506-B0-1N**SI506-B0-2N**SI506-B0-3N**3166935242 9354372443724438172 C C C 3.6-12(Loop 4)1-SI-4SI4-B0-1NSI4-B0-2NSI4-B0-3N**238074132527237394483944838172 C C,L C1-SI-511SI511-B0-1N**SI511-B0-2N**SI511-B0-3N**140134227532244381723724437244 C C C 3.6-13(Loop 2)1-SI-9SI9-B0-1NSI9-B0-2SI9-B0-3**SI9-B2-5 8827 8950357071199839448394483817239448 C C,L,X C C,L1-SI-507SI507-B0-1N**SI507-B0-2N**SI507-B0-3N**

28782581825815372443724437244 C C C 3.6-14(Loop 3)1-SI-10SI10-B0-1NSI10-B0-3SI10-B0-4 SI10-B0-5**SI10-B1-6SI10-B1-7133771223715800 436701629711652394483944839448 381723944839448 C C,L,X C,L C C,L,X C,L,X1-SI-510SI510-B0-1N**SI510-B0-2N**SI510-B0-3N**45985 (61970)43727 (57446)41913 (56095)372443724437244 C C C PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-37WATTS BARWBNP-110Table 3.6-4 Summary of Combined Stresses at Break Locations - SI Cold Leg Injection(Sheet 2 of 2)Note: C = Circumferential, L = Longitudinal split X = Break not required to be postulatedStress shown in parenthesis is Unit 2 stress at the same locationBreaks selected to satisfy the minimum number of intermediate breaks are no longer required. Note that longitudinal splits, although indicated above, were not required to be considered at intermediate locations where the criteria for a minimum number of break locations was applied. ** Class 1 stresses are not shown. Note that in this historic analysis the Class 1 piping was designed to the requirements of subsection NC.Reflects Analysis Which Was Current at Time of Amendment 51 Submittal 3.6-38PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Allowable stress intensity values: 3S m = 48996-58950 psi, 2.4S m = 39197-47160 psiNotes: 1) For equation number, refer to NB-3600 of the ASME Code Section III.2) U is based on NB-3653.5 if S n < 3S m or NB-3653.6 if S n > 3S m3) C = Circumferential break; L = Longitudinal split4) Location criteria:A - Terminal end B - S n < 3S m and U > 0.1; or S n > 3S m and S e > 2.4S m, or S > 2.4S m, or U > 0.1, Summer 1973 codeC - Break selected to satisfy the minimum number of intermediate breaks based on highest stress intensity per equation10, (This is no longer required).Reflects Analysis Which Was Current at Time of Amendment 51 SubmittalTable 3.6-5 Summary of Stresses at Break Locations - RHR/SI Hot Leg Recirculation, Loop 4(Sheet 1 of 1)FIGURE NO. LINE NO. BREAKNO. EQUATION 10 1 S n (psi) EQUATION 12 1 S e (psi) EQUATION 13 1S (psi) USAGEFACTOR, U 2BREAK TYPE 3LOCATION CRITERIA 43.6-151-RHR-6RHR6-B0-1NRHR6-B0-2N RHR6-B0-3N RHR6-B0-4 RHR6-B0-5 RHR6-B0-6N RHR6-B0-7N RHR6-B0-8N5915989977 93475 91510 77232 72556 78263 77616924210427 14639 14148 14128 4273 018 151112406520308 10414 14188 20308 20554 26597 139090.0110.872 0.672 0.763 0.402 0.302 0.303 0.173 C C,L C,L C,L C,L C,L C,L C,L A B B

B B

B B

B1-RHR-7RHR7-B0-1RHR7-B0-2N8673593711102972314025388241200.5550.841 C,L C,L B B1-SI-14SI14-B0-1NSI14-B0-2N883935691721576857425922156790.4320.0 C C A C 3.6-39PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Allowable stress intensity values: 3S m = 50592 psi, 2.4S m = 40474 psiNotes: 1) For equation number, refer to NB-3600 of the ASME Code Section III2) U is based on NB-3653.5 if S n < 3S m or NB-3653.6 if S n > 3S m3) C = Circumferential break; L = Longitudinal split4) Location criteria:A - Terminal end B - S n < 3S m and U > 0.1; or S n > 3S m and S e > 2.4S m, or S > 2.4S m, or U > 0.1, Summer 1973 code C - Break selected to satisfy the minimum number of intermediate breaks based on highest stress intensity per equation 10,(this is no longer required).Reflects Analysis Which Was Current at Time of Amendment 51 SubmittalTable 3.6-6 Summary of Stresses at Break Locations - SI Hot Leg Recirculation Loops 1, 2, and 3(Sheet 1 of 1)FIGURE NO. LINE NO. BREAK NO. EQUATION 10 1 S n (psi) EQUATION 12 1 S e (psi) EQUATION 13 1S (psi) USAGEFACTOR U 2BREAK TYPE 3LOCATION CRITERIA 43.6-161-SI-15SI15-B0-1N456241788205040.0CA3.6-171-RHR-4RHR4-B0-14199814358197330.0CA1-RHR-5RHR5-B0-1 RHR5-B0-2N

RHR5-B0-36282458135 598323325133855 329481637215368 154890.0060.0 0.0 C C C A C C

3.6-40PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Table 3.6-7 Deleted by Amendment 79 PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-41WATTS BARWBNP-110Table 3.6-8 Deleted Per Amendment 64 3.6-42PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Table 3.6-9 Summary of Protection Requirements - Outside Containment 4 - MAIN STEAM (Page 1 of 6) PIPING SYSTEM Main SteamPIPING NOMINAL DIA. 36 inch PIPING SCHEDULE 1.307-inch wall BREAKLOCATIONBREAK 1 TYPE THRUST 1DIRECTION WHIP 2FORMEDEFFECT ON REQUIRED 3COMPONENTSAcceptable/UnacceptableRequired Fix201,301, 203,303CDownstreamYesPipe whip into refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tankJet impingement on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tank205,305, 207,307CDownstreamYesPipe whip into refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tankJet impingement on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tankUpstreamYesJet impingement on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tank209,309CDownstreamYesPipe whip into refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tankSee page 6 of 6 for Notes.

3.6-43PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110Jet impingement on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tankUpstreamYesJet impingement on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tank211,311CDownstreamYesPipe whip damage to A1 wall of Auxiliary BuildingUnacceptable, wall fails, environmental damage to essential components will result from steam entering Auxiliary

BuildingRestraints H31W, H21WUpstreamYesJet impingement on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tank217,317CDownstreamYesPipe whip damage to A1 wall of Auxiliary BuildingUnacceptable, wall fails, environmental damage to essential components will result from steam entering Auxiliary

BuildingRestraints H31W, H21WUpstreamYesPipe impact on refueling water storage tankUnacceptable, results in loss of emergency core cooling water supplyProvide a bunker to prevent unacceptable damage to tankSee page 6 of 6 for Notes.Table 3.6-9 Summary of Protection Requirements - Outside Containment 4 - MAIN STEAM (Page 2 of 6) PIPING SYSTEM Main SteamPIPING NOMINAL DIA. 36 inch PIPING SCHEDULE 1.307-inch wall BREAKLOCATIONBREAK 1 TYPE THRUST 1DIRECTION WHIP 2FORMEDEFFECT ON REQUIRED 3COMPONENTSAcceptable/UnacceptableRequired Fix PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-44WATTS BARWBNP-110217,317LUpYesJet impingement on ceiling of counting room and radio-chemical laboratory (unit 1 only)Unacceptable, ceiling fails, environmental damage to essential components due to steam entering elevation 713 of the Auxiliary Building Sleeves S217 S317LDownYesPipe impact on ceiling of counting room and radio-chemical laboratory (unit 1 only)Unacceptable, ceiling fails, environmental damage to essential components due to steam entering elevation 713 of the Auxiliary Building Sleeves S217 S317LeftYesPipe whip into Auxiliary Building HVAC intakeUnacceptable, environmental damage to essential components due to steam entering elevation 737 of the Auxiliary

BuildingSleeves S217, S317RightYesJet impingement on Auxiliary Building HVAC intakeUnacceptable, environmental damage to essential components due to steam entering elevation 737 of the Auxiliary

BuildingSleeves S217, S317218,318CUpstreamYesPipe whip damage to south wall of south steam valve roomUnacceptable, damage to main steam and feedwater isolation valves located in valve roomRestraints G22W, G32W418,118,218,318LRightYesJet impingement on spreading room exhaust duct in C11-wall (unit 2 only)Unacceptable, loss of Control Building habitability due to steam environmentHVAC to have 3 psi backdraft damper installed to prevent steam from entering

control buildingSee page 6 of 6 for Notes.Table 3.6-9 Summary of Protection Requirements - Outside Containment 4 - MAIN STEAM (Page 3 of 6) PIPING SYSTEM Main SteamPIPING NOMINAL DIA. 36 inch PIPING SCHEDULE 1.307-inch wall BREAKLOCATIONBREAK 1 TYPE THRUST 1DIRECTION WHIP 2FORMEDEFFECT ON REQUIRED 3COMPONENTSAcceptable/UnacceptableRequired Fix 3.6-45PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110419,119,219, 319CUpstreamYesPipe impact on elevation 755, which supports control room HVAC equipmentUnacceptable, floor fails and results in environmental damage to control roomRestraints L42D, L12D, L22D, L32D420,120,220, 320CUpstreamYesPipe impact on elevation 755, which supports control room HVAC equipmentUnacceptable, floor fails and results in environmental damage to control roomRestraints L42D, L12D, L22D, L32D423124LUpYesPipe impact on elevation 729 floor of Turbine Building adjacent to doors to Control BuildingUnacceptable, floor fails, possible damage to essential components

within Control Building due to jet/missile impingement on Control

Building doorsSleeves S424, S125423,124LDownYesJet Impingement on elevation 729 floor of Turbine Building adjacent to doors to Control BuildingUnacceptable, floor fails, possible damage to essential components

within Control Building due to jet/missile impingement on Control

Building doorsSleeves S424, S125424,125,225,325CUpstreamYesPipe impact on the north-wall of Control BuildingUnacceptable, wall fails, environmental damage to essential components

within Control BuildingRestraints M42S, M32S, M22S, M12SSee page 6 of 6 for Notes.Table 3.6-9 Summary of Protection Requirements - Outside Containment 4 - MAIN STEAM (Page 4 of 6) PIPING SYSTEM Main SteamPIPING NOMINAL DIA. 36 inch PIPING SCHEDULE 1.307-inch wall BREAKLOCATIONBREAK 1 TYPE THRUST 1DIRECTION WHIP 2FORMEDEFFECT ON REQUIRED 3COMPONENTSAcceptable/UnacceptableRequired Fix PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE3.6-46WATTS BARWBNP-110424,125LUpYesPipe impact on elevation 729 floor of Turbine Building adjacent to door to Control BuildingUnacceptable, floor fails, possible damage to essential components

within Control Building due to jet/missile impingement on Control

Building doorsSleeves S424, S125424,125LDownYesJet impingement on elevation 729 floor of Turbine Building adjacent

to door to Control BuildingUnacceptable, floor fails, possible damage to essential components

within Control Building due to jet/missile impingement on Control

Building doorsSleeves S424, S125425,126,226, 326CUpstreamYesPipe impact on n-wall of Control BuildingUnacceptable, wall fails, environmental damage to essential components in

Control BuildingRestraints M42S, M12S, M22S, M32SThrough-Wall Leakage CracksThrough-wall leakage crack break below Control Building HVAC exhaust ducting at elevation 755 on q-wall (unit 2 only)Through-wall leakage crack break would fill control room HVAC with steamUnacceptable, loss of habitability of control roomHVAC to have 3 psi backdraft damper installed to prevent steam from entering control roomSee page 6 of 6 for Notes.Table 3.6-9 Summary of Protection Requirements - Outside Containment 4 - MAIN STEAM (Page 5 of 6) PIPING SYSTEM Main SteamPIPING NOMINAL DIA. 36 inch PIPING SCHEDULE 1.307-inch wall BREAKLOCATIONBREAK 1 TYPE THRUST 1DIRECTION WHIP 2FORMEDEFFECT ON REQUIRED 3COMPONENTSAcceptable/UnacceptableRequired Fix 3.6-47PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110 Notes:1)Direction of thrust on pipe. Jet load is opposite. For circumferential (C) breaks consider upstream thrust on the upstream pipe and downstream thrust on the downstream pipe. For longitudinal (L) breaks consider up, down, lateral left, and lateral right thrust (facing downstream).2)Whip trajectory is governed by hinge mechanism and direction of vector thrust of break force. Maximum 180° rotation about any plastic hinge. Sweep of jet is governed by pipe motion.3)Type of effect (jet, whip, environment, etc.) and components affected. 4)This applies to unit 1. Unit 2 is opposite hand unless otherwise noted. Reflects Analysis Which Was Current at Time of Amendment 51 SubmittalThrough-wall leakage crack break below Auxiliary Building HVAC intake canopy at elevation 743 on A1-wallThrough-wall leakage crack break would fill Auxiliary Building

with steamUnacceptable, environmental damage to essential components in Auxiliary BuildingHVAC to have temperature sensors installed which control intake fans, preventing steam from entering Auxiliary BuildingIn all other cases effects of through-wall leakage crack breaks are acceptable.Table 3.6-9 Summary of Protection Requirements - Outside Containment 4 - MAIN STEAM (Page 6 of 6) PIPING SYSTEM Main SteamPIPING NOMINAL DIA. 36 inch PIPING SCHEDULE 1.307-inch wall BREAKLOCATIONBREAK 1 TYPE THRUST 1DIRECTION WHIP 2FORMEDEFFECT ON REQUIRED 3COMPONENTSAcceptable/UnacceptableRequired Fix 3.6-48PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREWATTS BARWBNP-110THIS PAGE INTENTIONALLY BLANK PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREOF PIPING3.6-49WATTS BAR WBNP-110Table 3.6-10 (Page 1 of 3)Summary of Protection Requirements - Outside Containment 4 - FeedwaterPIPING SYSTEM FeedwaterPIPING NOMINAL Dia. 18 inch PIPING SCHEDULE 80 BREAK LOCATION BREAK 1 TYPE THRUST 1 DIRECTION WHIP 2 FORMED EFFECT ON REQUIRED 3 COMPONENTS Acceptable/Unacceptable Required Fix 418, 118, 218, 318 LLeft NoJet impingement on spreading room exhaust duct in C11-wall (unit 2 only)Unacceptable loss of Control Building ventilationProvide 3 psibackdraft damper 420, 120, 220, 320 LDown YesPipe impact on elevation 708 floor of Control BuildingUnacceptable, failure of floor allows pipe whip into electrical board room air handling units below.

Environmental damage to essential components and loss of control room habitability may result.Restraints J42U, J12U, J22U, J32U 421, 121, 221, 321 CDownstream YesPipe impact on elevation 708 floor of Control BuildingUnacceptable, failure of floor allows pipe whip into electrical board room air handling units below.

Environmental damage to essential components and loss of control room habitability may result.Restraints J42U, J12U, J22U, J32U 422, 122, 222, 322 CDownstream YesPipe impact on elevation 708 floor of Control BuildingUnacceptable, failure of floor allows pipe whip into electrical board room air handling units below.

Environmental damage to essential components & loss of control room habitability may result.Restraints J42U, J12U, J22U, J32U 423, 123, 223, 323 CUpstream YesPipe impact on C-3 wall of Control BuildingUnacceptable, failure of wall allows pipe whip into spreading room of Control Building. Environmental damage to essential components and loss of control room habitability may result.Restraints K42W, K12W, K22W, K32WSee page 3 of 3 for notes.

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREOF PIPING3.6-50WATTS BAR WBNP-110424,124,224, 324 CUpstream YesPipe impact on C-3 wall of Control BuildingUnacceptable, failure of wall allows pipe whip into spreading room of Control Building. Environmental damage to essential components and loss of control room habitability may result.Restraints K42W, K12W, K22W, K32W425,125,225, 325 CDownstream YesPipe impact on elevation 755 floorUnacceptable, floor fails and results in environmental damage to control room.Restraints K42W, K12W, K22W, K32W LDown YesPipe impact on C-3 wall of Control BuildingUnacceptable, failure of wall allows pipe whip into spreading room of Control Building. Environmental damage to essential components and loss of control room habitability may result.Restraints K42W, K12W, K22W, K32W426,126,226, 326 CDownstream YesPipe impact on elevation 755 floorUnacceptable, floor fails and results in environmental damage to control room.Restraints K42W, K12W, K22W, K32W LDown YesPipe impact on C-3 wall of Control BuildingUnacceptable, failure of wall allows pipe whip into spreading room of Control Building. Environmental damage to essential components and loss of control room habitability may result.Restraints K42W. K12W, K22W, K32W428,128,228,328 CDownstream YesPipe impact on elevation 755 floorUnacceptable, floor fails and results in environmental damage to Control Building.Restraints K42W, K12W, K22W, K32WSee page 3 of 3 for notes.Table 3.6-10 (Page 2 of 3)Summary of Protection Requirements - Outside Containment 4 - FeedwaterPIPING SYSTEM FeedwaterPIPING NOMINAL Dia. 18 inch PIPING SCHEDULE 80 BREAK LOCATION BREAK 1 TYPE THRUST 1 DIRECTION WHIP 2 FORMED EFFECT ON REQUIRED 3 COMPONENTS Acceptable/Unacceptable Required Fix

3.6-51PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREOF PIPINGWATTS BARWBNP-110 Notes:1) Direction of thrust on pipe. Jet load is opposite.For circumferential (C) breaks consider upstream thrust on the upstream pipe and downstream thrust on the downstream pipe.

For longitudinal (L) breaks consider up, down, lateral left, and lateral right thrust (facing downstream).2) Whip trajectory is governed by hinge mechanism and direction of vector thrust of break force. Maximum 180

° rotation about any plastic hinge. Sweep of jet is governed by pipe motion.3) Type of effect (jet, whip, environment, etc.) and components affected.

4) This applies to unit 1. Unit 2 is opposite hand unless otherwise noted.

Reflects Analysis Which Was Current at Time of Amendment 51 Submittal Through-Wall Leakage cracksThrough-wall leakage crack break below Control Building HVAC exhaust ducting at elevation 755 on q-wall (unit2 only)Through-wall leakage crack break would fill control room HVAC with

steamUnacceptable, loss of habitability of control roomHVAC to have 3 psi backdraft damper installed to prevent steam entering control roomThrough-wall leakage crack break below Auxiliary Building HVAC intake canopy at elevation 743 on A1-wallThrough-wall leakage crack break would fill Auxiliary Building HVAC with

steamUnacceptable, environmental damage to essential components in Auxiliary BuildingHVAC to have temperature sensors installed, which control intake fans, preventing steam from entering Auxiliary Bldg.In all other cases, effects of through-wall leakage crack breaks are acceptable.Table 3.6-10 (Page 3 of 3)Summary of Protection Requirements - Outside Containment 4 - FeedwaterPIPING SYSTEM FeedwaterPIPING NOMINAL Dia. 18 inch PIPING SCHEDULE 80 BREAK LOCATION BREAK 1 TYPE THRUST 1 DIRECTION WHIP 2 FORMED EFFECT ON REQUIRED 3 COMPONENTS Acceptable/Unacceptable Required Fix

3.6-52PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTUREOF PIPINGWATTS BARWBNP-110THIS PAGE INTENTIONALLY BLANK PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-53WATTS BARWBNP-110Figure 3.6-1 Shape Factors

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-54WATTS BARWBNP-110Figure 3.6-2 Isometric of Postulated Break Locations (Main Steam Line from Steam Generator #1)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-55WATTS BARWBNP-110Figure 3.6-3 Isometric of Postulated Break Locations (Main Steam Line from Steam Generator #2)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-56WATTS BARWBNP-110Figure 3.6-4 Isometric of Postulated Break Locations (Main Steam Line from Steam Generator #3)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-57WATTS BARWBNP-110Figure 3.6-5 Isometric of Postulated Break Locations (Main Steam Line from Steam Generator #4)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-58WATTS BARWBNP-110Figure 3.6-6 Isometric of Postulated Break Location (Feedwater Line to Steam Generator # 1)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-59WATTS BARWBNP-110Figure 3.6-7 Isometric of Postulated Break Location (Feedwater Line to Steam Generator # 2)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-60WATTS BARWBNP-110Figure 3.6-8 Isometric of Postulated Break Location (Feedwater Line to Steam Generator # 3)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-61WATTS BARWBNP-110Figure 3.6-9 Isometric of Postulated Break Location (Feedwater Line to Steam Generator # 4)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-62WATTS BARWBNP-110Figure 3.6-10 Isometric of Postulated Break Locations (Auxiliary Feedwater Steam Supply Lines)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-63WATTS BARWBNP-110Figure 3.6-11 S.I. Cold Leg Injection Loop 1 Isometric PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-64WATTS BARWBNP-110Figure 3.6-12 S.I. Cold Leg Injection Loop 4 Isometric PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-65WATTS BARWBNP-110Figure 3.6-13 S.I. Cold Leg Injection Loop 2 Isometric PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-66WATTS BARWBNP-110Figure 3.6-14 Isometric of Postulated Break Locations (SI Cold Leg Injection Loop 3)

PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-67WATTS BARWBNP-110Figure 3.6-15 RHR/S.I. Hot Leg Recirculation Loop 4 Isometric PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-68WATTS BARWBNP-110Figure 3.6-16 S.I. Hot Leg Recirculation Loop 2 Isometric PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-69WATTS BARWBNP-110 Figure 3.6-17 RHR Hot Leg Recircul ation Loops 1 and 3 Isometric PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-70WATTS BARWBNP-110Figure 3.6-18 Deleted by Amendment 79 PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-71WATTS BARWBNP-110Figure 3.6-19 Deleted -Amendment 64 PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-72WATTS BARWBNP-110Figure 3.6-20 Deleted -Amendment 64 PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-73WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.6-21 Main Steam Line Break Locations Outside Containment PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-74WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.6-22 Main Steam Line Pipe Rupture Protection Outside Containment PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-75WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.6-23 Main Feedwater Line Break Locations Outside Containment PROTECTION AGAINST DYNAMIC EFFECTS ASSOCIATED WITH THE POSTULATED RUPTURE OF PIPING3.6-76WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.6-24 Main Feedwater Line Pipe Rupture Protection Outside Containment SEISMIC DESIGN 3.7-1WATTS BARWBNP-110 3.7 SEISMIC DESIGNThe original analyses of Category I structures were performed using methodologies that were prevalent prior to issuance of the Standard Review Plan (SRP) (NUREG-0800, Rev. 1.) Throughout this se ction, the bases fo r these analyses are called the "Original Seismic Analysis Criteria" and analysis results (Amplified Response Spectra (ARS), forces, displacements, etc.) using these criteria are termed Set A. The plant's design basis is Set A criteria.As a result of various seismic analysis issues identified during 1987-1989, reanalysis of some structures was necessary. The intent of the reanalysis was to demonstrate, by addressing these issues, the seismic design adequacy of structures, systems and components. Evaluations of the adequacy of existing hardware are based on SRP compatible criteria and current practices. This criteria, called the "Evaluation Seismic Analysis Criteria," includes the Site Specific Response Spectra (SSRS) developed for WBN, three-dimensional seismic models, and SRP compatible damping values. Evaluation criteria analysis results are termed Set B criteria.In order to develop seismic input for future designs and modifications of existing designs, the Category I structures analyzed for Set B criteria were also reanalyzed using the original criteria with current modeling techniques, including soil-structure interaction. These analyses results are termed Set C.The SRP 1981, Revision 1 formed the basis for Set B and Set C analyses, updated to the provisions of SRP, 1989, Revision 2. Specific evaluations were performed for the following: (a)The requirement of varying the soil shear modulus by +100%, -50% from the best-estimate (mean), and the best estimate soil shear modulus.(b)The limitation of hysteretic soil damping ratio to the maximum of 15%. The seismic responses (ARS, accelerations, displacements, forces, and moments) defined by the envelope of Set B and Set C (Set B+C) are for use in new designs and modifications. New designs and modifications initiated after October 1, 1989, are based on Set B+C responses.Underground electrical conduit banks were evaluated using Set B criteria. Conduit banks were reevaluated because the original seismic analysis was not retrievable, and the design criteria had been revised to incorporate the design requirement to consider axial loads in the analysis of conduit banks. Set B and Set C analysis were not performed for the Waste Packaging Area, (WPA), and Condensate Demineralizer Waste Evaporator Structure, (CDWE), since these two structures do not house any safety-related systems and components. Furthermore, Set B and Set C analyses were not performed for the essential raw cooling water system (ERCW) retaining walls, miscellaneous yard structures and Class 1E electrical system manholes and handholes because the seismic design input for these features is the ground motion;

3.7-2SEISMIC DESIGN WATTS BARWBNP-110thus, the generation of ARS are not necessary, and there are no outstanding issues which necessitate a reevaluation. If a reevaluation of such features to resolve CAQ's etc., is required, Set B ground motion will be used in the reevaluation.3.7.1 Seismic Input 3.7.1.1 Ground Response SpectraVibratory ground motions are defined by two sets of site seismic design response spectra: the Modified Newmark Ground Re sponse Spectra or Original Site Design Response Spectra for Set A and Set C analyses and the Site Specific Ground Response Spectra for Set B (Evaluation) analyses.

3.7.1.1.1 Original Si te Ground Response Spect ra (Set A and Set C)The original site seismic design response spectra which define the vibratory ground motion of the Operating Basis Earthquake (OBE) and the Safe Shutdown Earthquake (SSE) for rock-supported structures are shown in Figures 2.5-236a and 2.5-236b. The maximum rock acceleration for the SSE is 0.18g for horizontal motion and 0.12g for vertical motion. The OBE is equal to one-half the SSE, as outlined in Section 2.5.2.7, with maximum horizontal and vertical rock accelerations of 0.09g and 0.06g, respectively.

3.7.1.1.2 Site Specific Ground Response Spectra (Set B)Seismic input motions for the evaluation of existing structures, systems, and components are defined by the top-of-rock SSRS shown in Figures 3.7-4a through 3.7-4r. Peak SSE and OBE top-of-rock accelerations are 0.215g (horizontal SSE), 0.15g (vertical SSE), 0.09g (horizontal OBE), and 0.06g (vertical OBE).3.7.1.2 Design Time Histories 3.7.1.2.1 Time Hi stories for Original Site Gr ound Response Spectra (Set A and SetC)For time history analyses, four artificial acceleration time histories were developed so that the response spectra produced by the arithmetic average of the response spectra of each individual record envelope the site seismic design response spectra. Figures3.7-1 through 3.7-4 show the comparison, for the various damping ratios, of these averaged response spectra and the site seismic design response spectra for the SSE. Table 3.7-1 lists the system period intervals at which the response spectra are calculated.

3.7.1.2.2 Time Hi stories for Site Specific Gr ound Response Spectra (Set B)Set B analyses utilize three statistically independent acceleration time histories. The response spectra for these three statistically independent time histories are shown in Figures 3.7-4a through 3.7-4r. These time histories satisfy the SRP design spectra enveloping requirements.

SEISMIC DESIGN 3.7-3WATTS BARWBNP-110The power spectral density function (PSDF) enveloping criteria of NUREG/CR-5347 were used to ensure adequate energy content of the artificial time histories. The PSDF enveloping criteria are that the PSDFs of artificial time histories whose response spectra envelope the 84th-percentile target response spectra should generally envelope the "minimum required" target PSDF for the corresponding non-exceedance probability level to ensure adequate motion energy contents of artificial time histories. The minimum required target PSDF is defined as the 80% of the target PSDF. The minimum required horizontal and vertical 84th-percentile target PSDFs for the Watts Bar site-specific ground motions were calculated and compared with the corresponding PSDFs of the artificial time histories as shown in Figures 3.7-4s, 3.7-4t, and 3.7-4u.As can be seen from Figures 3.7-4s and 3.7-4t, the PSDFs of the horizontal artificial time histories envelope the corresponding minimum required 84th-percentile target PSDFs in the frequency range of 0.7 cps to 25 cps. The PSDF of the artificial time history H2 dip slightly below the horizontal minimum required 84th-percentile target PSDF in the small frequency range of 0.5 cps to 0.7 cps. This slight dip is considered inconsequential because the response spectral values of H2 time history envelope the site-specific response spectra in this frequency range and no structural frequencies of Category I structures exist in this low frequency range. Thus, the horizontal SSRS-compatible artificial time histories have adequate motion energy contents and their PSDFs satisfy the PSDF enveloping criter ia proposed in NUREG/CR-5347 in the frequency range of 0.7 cps to 25 cps.Similarly, as can be seen from Figure 3.7-4u, the PSDF of the vertical artificial time history envelope the corresponding minimum required, 84th-percentile target PSDF in the frequency range from 1.6 to 25 cps. The PSDF of the artificial time history has very slight dips below the vertical minimum required 84th-percentile target PSDF in the small frequency ranges of 0.40 to 0.42 cps, and 1.2 to 1.6 cps. These slight dips are considered inconsequential because the response spectral values of the vertical time history envelope the site-specific response spectra in these frequency ranges and no structural frequencies of Category I structure exist in this low frequency range. Thus, the vertical SSRS-compatible artificial time history has adequate motion energy contents and its PSDF satisfy the PSDF enveloping criteria proposed in NUREG/CR-5347 in the frequency range of 1.6 to 25 cps.3.7.1.3 Critical Damping ValuesThe specific percentages of critical damping values used for Category I structures, systems, and components are provided in Table 3.7-2 for Sets A, B, and C.

3.7.1.4 Supporting Me dia for Seismic Cate gory I StructuresA complete description of the supporting media for each Seismic Category I structure is provided in Section 2.5.4. Pertinent data concerning the supporting media for Set A, B, and C analyses of each Seismic Category I structure is also given in Table 3.7-3.

3.7.2 Seismic

System AnalysisThis section describes the seismic analysis performed for Category I structures.

3.7-4SEISMIC DESIGN WATTS BARWBNP-1103.7.2.1 Seismic Analysis MethodsThe seismic methods of analysis used for the Category I structures listed in Section3.2.1 are described in the following sections.

3.7.2.1.1 Category I Rock-Supported Stru ctures - Original Analyses (Set A)The seismic analyses of Category I structures were based upon dynamic analyses using the lumped mass normal mode method with idealized mathematical models. The inertial properties of the models were characterized by the mass, eccentricity, and mass moment of inertia of each mass point. Mass points were located at floor slabs, changes in geometry, and at intermediate points to adequately model the structure. The stiffness properties were characterized by the moment of inertia, area, shear shape factor, torsion constant, Young's modulus, and shear modulus. Significant modes of vibration were considered in determining the total response. For structures with built-in asymmetry and open structures which have low torsional resistance, coupled translation and torsion were included in the dynamic analyses. Torsional effects for the closed structures with small eccentricities have insignificant effect on the responses. To demonstrate this, a dynamic analysis study of the steel containment vessel, including an accidental eccentricity of 5% of the diameter, showed that the induced torsion had a negligible effect on the acceleration response spectra. Structural response was calculated in both the east-west and north-south directions except where symmetry justifies analyses in one direction. The effect of the vertical component of earthquake motions on the structural response was included.For structures surrounded by soil, the effect of the soil stiffness on the structural response was determined by replacing the soil with springs of equivalent stiffness. Due to seismic motion, the soil pressure against structures was increased above the static soil pressure. The magnitude of this increase was determined by using the shaking table experiments performed for the design of TVA's Kentucky Hydro Project[1]. For a ground acceleration of 0.18g the static soil pressure was increased by 46% for a dry fill and 22% for a saturated fill. This incremental increase was combined with the static pressure as a triangle of pressure whose apex is at the rock surface and maximum ordinate is at the ground surface. In addition to the soil pressure increase as described above for a saturated fill, the hydrostatic pressure of water within the fill was increased 22%. This incremental increase was combined with the static water pressure as a triangle of pressure whose apex is at the water surface and maximum ordinate is at the rock surface or bottom of structure. Calculations using the shaking table experiment results have been confirmed using information in Reference[2]. A more detailed description of the seismic analyses of Category I rock-supported structures is discussed below.The in situ measured shear wave velocity of the bedrock upon which the structures are founded has an average value of 5,900 feet per second (Section 2.5.4.8). Therefore, the effect of structure-foundation interaction was investigated for the major structures.

The results of the investigation are discussed below as one of the parameters associated with the analysis of those structures.

SEISMIC DESIGN 3.7-5WATTS BARWBNP-110The structural response was computed using the response spectrum modal analysis method. The techniques used to account for the three components of motion and the method of combining modal responses when computing the structural response of a structure are explained in Sections 3.7.2.6 and 3.7.2.7, respectively.Response spectra were produced by the time history-modal analysis method using the four artificial accelerograms discussed in Section 3.7.1.2 and the techniques of Sections 3.7.2.5 and 3.7.2.9.When torsion is considered, accelerations and deflections were calculated at the farthest points on the structure from the shear center, on the axis perpendicular to the direction of motion. The moment and shear due to earthquake motion were used in combination with other appropriate loads to determine overturning moments.

The response was calculated for both th e OBE and the SSE, except when the same percentages of critical structural damping were specified for both earthquake levels, in which case the response was calculated for the OBE only (the SSE results are twice the OBE results). For applicable stress criteria, see Section 3.8.The damping ratios used in the dynamic analyses of the structures are given in Table3.7-2.To ensure that the results of the seismic analysis of the structures were used in the design, the analyses became part of the nuclear plant design criteria and were submitted to the design sections responsible for design and to the principal engineer. For more detailed procedures and criteria of design control measures, see Section 3.8.Shield Building Two separate, distinct analyses were performed on the reinforced concrete structure to determine the response of the structure to horizontal motion when modeled as a cantilever beam and the response of the dome to vertical motion when modeled as a shell.The Watts Bar Shield Building is identical to the Shield Building at TVA's Sequoyah Nuclear Plant. The building has been assumed to have identical structural properties in both the east-west and north-south directions. A sketch of the lumped mass model is shown in Figure 3.7-5 and the structural properties are listed in Table 3.7-4. The dome was considered a rigid body and its weight added at mass point 25. The dynamic analyses in both the horizontal and vertical directions was done by the normal mode response spectrum method. Although no structural eccentricities exist in the building, an accidental eccentricity of 5% of the diameter was assumed in the design. Periods for the normal modes of vibration are listed in Table 3.7-5.Since torsion is considered, the maximum structural accelerations and deflections will not occur at the center of mass but rather at the point on the structure farthest from the shear center. For the Shield Building the shear center is located at the geometric center. Accordingly, all structural accelerations and deflections as well as the floor response spectra have been computed at a point located on the shell wall. Structural 3.7-6SEISMIC DESIGN WATTS BARWBNP-110responses were calculated for both the OBE and SSE using structural damping of 2 and 5 percent, respectively.Foundation-structure interaction studies were performed to determine the response characteristics of the Shield Building steel containment-interior concrete system to rocking-type motion. These analyses were performed considering lumped-mass models of the structure coupled with foundation springs. These springs were calculated as detailed by Whitman

[3]. The results of these investigations indicated that the Shield Building accelerations would increase by less than 15% compared to the accelerations of a rigid base, single structure system. As a result, all spectra used to compute structural response and all accelerograms used to compute floor response spectra were multiplied by a factor of 1.15. The site response spectra for structures without rocking have previously been shown in Figures 2.5-236a and 2.5-236b. The effects of the soil which partially surround the building were investigated for the Sequoyah Nuclear Plant

[4] and the effects are negligible.Floor response spectra were computed for four individual artificial earthquakes (increased in amplitude by 15%) and the result found by taking the arithmetic mean of the four analyses. Spectra were computed for damping ratios of 0.005, 0.01, and 0.02 for the OBE and 0.005, 0.01, 0.02, 0.030, 0.040, and 0.050 for the SSE. Vertical modes of vibration were calculated for comparison with the results for the dome as a shell.

The rigid-body simulation of the dome as performed in the analysis of the cantilever beam model does not provide an accurate representation of the response of the dome to vertical earthquake excitation. Thus, an analogy was developed using shell theory to determine the earthquake moments and forces in the dome.Figure 3.7-6 illustrates the logic performed in the analysis. The shell model is shown in Figure 3.7-7.A flexibility matrix was developed using the shell model and the analysis performed using the response spectrum modal analysis techniques. The modes involving primarily deformation of the cylinder as computed in this analysis (modes 1 and 5) compare favorably with modes 1 and 2 of the vertical lumped mass cantilever beam analysis as shown in Table 3.7-5 (periods agree within 3%). Modes 2, 3, and 4 are primarily modes of vibration involving the dome. Also, the total meridional force at the base of the building as calculated by this method compares closely with the total force at the base in the cantilever beam analysis. This indicated the appropriateness of the analogy.The structural response for the shell model was calculated for both the OBE and the SSE using structural damping of 2% and 5%, respectively.Interior Concrete Structure The idealized lumped mass model of the reinforced concrete structure used in the dynamic earthquake analysis is shown in Figure 3.7-8. Element properties are given in Table 3.7-6 and mass point properties in Table 3.7-7. The foundation structure interaction analysis of the Shield Building interior concrete-steel containment system discussed above for the Shield Building analysis revealed no significant change in the SEISMIC DESIGN 3.7-7WATTS BARWBNP-110response of the interior concrete structure as compared to the response assuming a fixed base. Therefore, the dynamic analysis was performed using a fixed base model.The dynamic earthquake analysis was performed by the response spectrum modal analysis technique. The results were computed for both the OBE and SSE conditions with structural damping of 2% and 5% respectively. The effects of torsion and longitudinal motion were considered. Periods for the normal modes of vibrations are listed in Table 3.7-8.Response spectra were produced for damping values of 0.005, 0.01, and 0.02 for the OBE at mass points 1, 2, 3, 4, 6, 8, 10, 12, 13, and 14 for motion in both the east-west and north-south directions. Response spectra for vertical motion were obtained at ground and at mass point 14, and linear interpolation (Section 3.7.2.5) was used to produce vertical spectra at intermediate mass points. Response spectra were produced for damping values of 0.005, 0.010, 0.020, 0.050, 0.100, and 0.150 for the SSE at mass points 3, 5, 6, 8, 9, 10, 11, and 14 for motion in both the east-west and north-south directions. Response spectra for vertical motion were produced at mass point 14 and ground. Linear interpolation (see Section 3.7.2.5) was used to obtain vertical response spectra at intermediate points.Auxiliary/Control BuildingThe idealized lumped mass model of the reinforced concrete structure is shown in Figure 3.7-9. Foundation-structure interaction was investigated by using a lumped mass-rock spring model, as discussed in Section 3.7.2.4. The results verified that a fixed base analysis may be used with no loss in accuracy. The dynamic analysis was performed by the response spectrum modal analysis technique. The results were computed for the OBE condition, and resu lts for the SSE were obtained by doubling the values from the OBE. Element properties for the fixed base model are given in Table 3.7-9 and mass point properties in Table 3.7-10. Contributory weights to account for the soil contained within the wing walls at the north end of the structure were included in the total weights of the appropriate mass points. The effects of torsion and longitudinal motion were considered. Periods for the normal modes of vibrations are listed in Table 3.7-11.Steel Containment Vessel The containment vessel dynamic seismic analyses were performed using a lumped mass beam model. Structural and equipment masses were included, and structural properties were computed by hand calculations. The beam model and its properties are shown in Figure 3.7-7B.Maximum overturning moments, shears, deflections, and shell stresses were computed by the response spectrum method. The site seismic design response spectra for 1% damping described in Sections 2.5.2.6 and 2.5.2.7 were utilized. The analyses were performed by CBI proprietary computer program 1017 described in Appendix 3.8C. Total response was computed by taking the absolute sum of modal responses.

3.7-8SEISMIC DESIGN WATTS BARWBNP-110A time-history analysis using the model in Figure 3.7-7B was performed in order to develop response spectra for equipment attached to the containment vessel. Four artificial earthquakes having an averaged response spectrum greater than the design response spectrum provided the seismic input. Using each of the artificial earthquakes individually, the beam model was analyzed and histories of acceleration were generated. For each of the acceleration histories, response spectra for various mass points and values of assumed damping were generated. The design spectra were the envelopes of the spectra generated from the four earthquakes and were used to design the vessel and the vessel's appurtenances in the scope of CBI, the vessel designer, fabricator, and erector. These calculations were performed by CBI computer programs 1017, 1044, and 1668, all of which are described in Appendix 3.8C.As part of the review process and to provide response spectra for the design of equipment, piping and subsystems attached to and or supported by the containment vessel not supplied by the CBI, TVA performed an independent dynamic seismic analysis of the containment vessel. The ground motion input used to generate the floor response spectra consisted of the same four accelerograms of artificial earthquakes used by CBI.The containment was idealized as a beam-type model consisting of lumped masses connected by massless elastic members. This lumped mass model is shown in Figure3.7-7C. The element properties and inertial properties which were used in the analysis are shown in Table 3.7-5A and Table 3.7-5B, respectively.North Steam Valve RoomThe idealized lumped mass model of the reinforced concrete structure is shown in Figure 3.7-10. The structure is founded on bedrock and partially imbedded in soil. The effect of the soil restraint on the seismic response of the structure was included in the lumped mass model as soil spring restraints. The soil springs were calculated in accordance with the methodology given in Section 3.7.2.1.3. Element properties are shown in Table 3.7-12 and mass point properties in Table 3.7-13.The dynamic analysis was performed using the response spectrum modal analysis technique. Response spectra were produced for selected elevations within the structure by the time history modal analysis method. Results were computed for the OBE with results for the SSE obtained by doubling those for the OBE. The frequencies for those modes considered important to the response of the structure are listed in Table 3.7-14.Essential Raw Cooling Water Intake Pumping StationThe idealized lumped mass model of the reinforced concrete structure used in the analysis is shown in Figure 3.7-11. The dynamic analysis was performed by the response spectrum modal analysis technique. The results were computed for both the OBE and SSE with an assumed structural damping of 5% for each earthquake. Element properties are given in Table 3.7-15 and mass point properties in Table3.7-16. The effects of torsion and soil restraint were considered. Periods for normal modes of vibration are listed in Table 3.7-17.

SEISMIC DESIGN 3.7-9WATTS BARWBNP-110In addition, the effect on the building response of various water levels inside the pump wells was studied. The results of this study showed that the natural period of vibration was affected by variations in water level. Therefore, the structural responses used for design were those for the "worst-case" conditions. The amplitude of the response spectra peaks was not significantly affected by the water level variations. Only the location of the peak changed as the natural periods changed in response to water level variations. Accordingly, the response spectra peaks were broadened to account for the range of variations in natural period.The response spectra for horizontal motion were produced for damping ratios of 0.005, 0.01, and 0.02 for both the OBE and SSE at mass points 6, 7, 8, and 10. Response spectra for vertical motion were produced for the base and mass points 8 and 10.

Vertical spectra for intermediate mass points were developed using linear interpolation, as outlined in Section 3.7.2.5. Essential Raw Cooling Water Intake Pumping Station-Retaining WallsThe reinforced concrete retaining walls were designed as a rigid structure subjected to the top of rock acceleration. Dynamic soil pressures on the retaining wall was determined in accordance with Reference [1].

3.7.2.1.2 Category I Rock - Supported Structures - Ev aluation and New Design or Modification Analyses (S et B and Set B+C) Analysis methodologies used in the original analyses (Set A) of Category I rock-supported structures were used in Evaluation (Set B) and New Design/Modification (Set B plus Set C) analyses except as noted in the remainder of this subsection. These exceptions provide for a seismic modeling approach which is consistent with current SRP Subsection 3.7.2 (NUREG 0800, Rev. 1) requirements.Structures were represented as three-dimensional lumped mass stick models in the analyses except when coupling effects from omitted degrees of freedom were not significant. Actual centers of rigidity and actual mass eccentricities were modeled. Sufficient numbers of modes were included in the response to assure participation of at least 90% of the total mass. The simultaneous effects of three components of seismic input were considered by combining the co-directional responses resulting from the three components of input either by algebraic summation (for simultaneous inputs) or by the square-root-of-the-sum-of-squares (SRSS) method. For design of structural elements, calculated seismic torsional moments were increased to account for accidental torsion. This increase is determined by multiplying the story shear force by the accidental eccentricity (defined as + 5% of the structure dimension perpendicular to the direction of excitation.) Rock-supported structures (ACB, IPS) were modeled as fixed base structures except where rock-structure interaction (Reactor Building) or structure-surrounding soil interaction (NSVR) effects were important. In these cases, three-dimensional finite element analysis was used to account for the interaction effects. The analyses were based on a foundation rock shear wave velocity of 5900 fps (Section 2.5.4.8). For rock-supported structures deeply embedded in soil, the effect of soil-structure 3.7-10SEISMIC DESIGN WATTS BARWBNP-110interaction was considered and, where significant, included in the analysis model. The soil stiffness was determined as discussed in Subsection 3.7.2.1.4.Structural damping values used in Set B and Set C analyses are given in Table 3.7-2. Where necessary, element associated damping was converted to modal damping using the strain energy composite modal damping approach.Reactor Building Rock-Structure Interaction AnalysisThe Reactor Building consists of the Shield Building (SB), Steel Containment Vessel (SCV), and interior concrete structure (ICS) including the NSSS piping, equipment, and components. The Set B and Set C Reactor Building model is a three branch, three dimensional (3-D) lumped mass model with branches representing the ICS, SB, and SCV. The ICS model was developed from a finite element analyses whereas the SB and SCV models were Set A models updated to include, in the vertical model, the fundamental vertical drumming mode of the dome for each of these structures. The ICS model used for the analyses also includes the NSSS model.The Reactor Building is partially embedded in soils below the finished grade at Elevation 728.0 and in foundation rock below Elevation 702.78. In order to take into account the embedment effect on seismic responses, rock-structure interaction analyses were performed for the Reactor Building using the 3-D SSI analysis-computer program SASSI.For the seismic response analysis, the input ground motion input was prescribed at the surface of the rock foundation (Elevation 702.78). This is the elevation of the top of the Reactor Building basemat where base fixity was provided for the structural models used in the original design basis seismic analysis (Set A). For rock-structure interaction analyses, the structural models for SB, SCV, and ICS were coupled together through the common Reactor Building basemat. The embedment of the Reactor Building basemat in the rock foundation was considered.Using the SASSI computer program, time history response analyses for the Reactor Building were performed in the frequency domain using the Fast Fourier Transform (FFT) method.Shield Building (SB)The Set B and Set C dynamic model for the axisymmetric Shield Building structure is represented by a 3-D lumped mass single stick (Figure 3.7-5A) having the center of mass coincident with the center of rigidity for each lumped mass elevation. The model consists of 25 lumped masses interconnected with 25 elastic beam elements and a single-degree-of-freedom (SDOF) system located at the dome spring line elevation (Elevation 852.0) for simulating the fundamental vertical drumming mode of the dome.

Except for the vertical SDOF system for the dome and the concrete modulus, the model configuration, lumped masses, and elastic beam element properties are the same as those used in the original design basis seismic analyses (Set A analysis). The vertical SDOF system for representing the fundamental vertical drumming mode of the dome was developed by matching the frequency and effective modal mass of the SEISMIC DESIGN 3.7-11WATTS BARWBNP-110SDOF system with those of the fundamental vertical drumming mode of the dome obtained from a separate finite element modal analysis for the dome. The model geometry, lumped masses, and elastic beam element properties for SB used for Set B and Set C analyses are summarized in Table 3.7-4A.Interior Concrete Structure (ICS)The ICS consists of a complex assemblage of curved walls, columns and slabs which have some cross sections with significant asymmetry. In order to develop a seismic model, static, 3-D, finite element analyses were performed to determine the equivalent beam properties that simulate the seismic responses of the ICS. Consistency of equivalent stick model properties and response transfer functions with those of the finite element model demonstrated the adequacy of the 3-D equivalent stick model.Since the equivalent beam model results in center-of-rigidity locations for axial and bending deformations different from those for shear and torsional deformations, the 3-D stick model for the ICS was represented by a combination of two sticks. One stick consists of elements with only axial areas of the structure located at the centers of rigidity for axial and bending deformations and another stick consists of elements with all other beam element properties, except the axial area, located at the centers of rigidity for shear and torsional deformations. The final configuration of the 3-D stick model for the ICS is shown in Figures 3.7-8A and 3.7-8B.Mass and member element properties are summarized in Tables 3.7-6A and 3.7-6B. Mass properties are unchanged from those of the original analysis (See Table 3.7-7).Steel Containment Vessel (SCV)The dynamic model for the SCV Set B and Set C analyses is represented by a 3-D lumped mass, concentric single stick model as shown in Figure 3.7-7A. The model consists of 23 lumped masses interconnected with 23 elastic beam elements and a vertical SDOF system located at the dome spring line elevation (Elevation 814.5) to represent the fundamental vertical mode of the dome. Mass and member element properties are defined in Table 3.7-5C. Except for the mass eccentricities and the SDOF vertical model, the model configuration, lumped masses, and elastic beam element properties are the same as those used in the original (Set A) design basis seismic analyses described in Section 3.7.2.1.1. During the analysis of Set B and SetC, it was determined that the 5% accidental eccentricity will yield much higher eccentric responses than from the actual eccentricities which were used in Set A analysis. Therefore, the actual eccentricities were neglected in Set B and Set C analyses. However, 5% accidental eccentricity was used to calculate torsional moments. The SDOF vertical dome model for SCV was developed by matching the frequency and effective modal mass of the SDOF system with those of the fundamental vertical mode of the dome obtained from a separate finite element modal analysis.Nuclear Steam Supply System (NSSS) ComponentsFor Set B and Set C analyses, the dynamic model for the NSSS components is coupled with the Interior Concrete Structure (ICS) model, and the coupled model is 3.7-12SEISMIC DESIGN WATTS BARWBNP-110 used for seismic response analyses. The dynamic model for the NSSS components included in the coupled model for the ICS consists of the models for the Reactor Pressure Vessel (RPV), four primary reactor coolant loop piping (hot legs, cold legs, and cross-over legs), the steam generator (SG), and the reactor coolant pump (RCP) associated with each loop, as shown in Figures 3.7-8C through 3.7-8G. In coupling the NSSS model to the ICS stick model, the RCL attachment points are connected to the ICS model at the appropriate elevations of the attachment points through rigid links.

The dynamic model data fo r the NSSS components are obtained from Westinghouse Electric Corporation.Due to the presence of gaps and tension-only tie rods at the NSSS supports, these supports exhibit nonlinear behavior under dynamic loading conditions. For the purpose of linear response analysis, four linearized NSSS analysis cases, each with a unique set of linearized NSSS support stiffn ess, are used to represent the nonlinear behavior under various dynamic loading conditions. For each NSSS analysis case, a specific set of NSSS supports with their specified orientations are activated for a particular loading condition and linear support stiffnesses are developed and provided by Westinghouse Electric Corporation to represent the active supports for application to the particular analysis case.The final acceleration response spectra and movements values are the envelope values resulting from the different NSSS cases. Furthermore, the ARS and movement values at the corresponding locations of the four loops are enveloped to obtain the enveloped ARS and movements applicable to all four loops.The seismic analysis of the NSSS components which was performed by Westinghouse is discussed in Section 5.2.1.10.Auxiliary Control Building (ACB)The Set B and Set C three-dimensional lumped parameter fixed-base model of the Auxiliary Control Building is shown in Figure 3.7-9A. The centers of mass and centers of rigidity were modeled at their actual geometric locations as defined in Table 3.7-9A. The element properties and masses are unchanged from the original analysis, except for the concrete shear modulus, and are listed in Tables 3.7-9 and 3.7-10.The dynamic analysis was performed by the time-history modal analysis technique. Structural responses were computed and floor ARS were generated for the same elevations as Set A. For Set C, since the structure damping ratios for OBE and SSE are the same (5%), the OBE responses were computed and the SSE responses were obtained by doubling the OBE responses. Separate OBE and site-specific SSE analyses were performed for Set B using structure damping ratios of 4% for OBE and

7% for site-specific SSE.Essential Raw Cooling Water Intake Pumping Station (IPS)The ERCW IPS original analysis model is updated to consider torsional effects. It incorporates rotatory inertia and the eccentricities between the centers of mass and centers of rigidity. No lateral soil springs were included as these had been determined SEISMIC DESIGN 3.7-13WATTS BARWBNP-110from previous analyses to produce a negligible soil-structure interaction effect. The highest water level was used for both the Set C SSE and OBE earthquakes and Set B site-specific SSE and OBE earthquakes, since this condition yields the lowest frequency and hence would produce the highest response levels. The Set B and SetC IPS model is shown in Figure 3.7-11A. Table 3.7-15A presents the element properties. Tables 3.7-16A and 3.7-16B define the weight properties and coordinates of centers of mass and centers of rotation, respectively.North Steam Valve Room (NSVR)To account for the soil-structure interaction effects due to the presence of backfill surrounding the foundation walls, soil-structure interaction (SSI) analyses were performed for the NSVR. The methodology used for SSI analysis is the same as that used for Category I soil-supported structures described in Section 3.7.2.1.4.The three-dimensional lumped mass model used in the seismic analysis of the NSVR superstructure is shown in Figures 3.7-10A and 3.7-10B, and the model properties are given in Tables 3.7-13A and 3.7-13B.

3.7.2.1.3 Category I So il-Supported Structures - Or iginal Analysis (Set A)For structures founded on soil, the acceleration at top of rock was amplified or attenuated through the soil deposit using the techniques outlined in Section 3.7.2.4. The soil-supported structures were analyzed using lumped-mass and soil spring modeling techniques. A typical model is shown in Figure 3.7-12.Table 3.7-3 contains a tabulation of Seismic Category I soil-supported structures for the plant (small miscellaneous structures are not included in the table). Details of the supporting media and foundation characteristics are presented in Table 3.7-3 and Section 3.7.1.4. The horizontal and vertical translational soil springs and the rocking soil spring included in the lumped-mass model to simulate soil structure interaction are calculated using the procedures outlined by Whitman[3]. The damping ratio used for soil-supported structures depends on the predominant type of motion, as explained by Richard[5], but is not permitted to exceed 10% in any case. Embedment effects are accounted for by constructing a translational soil spring using Whitman's vertical spring expressions and attaching it to appropriate point or points on the structure.Specific features associated with the seismic analysis of the Category I soil-supported structures are discussed below.Diesel Generator BuildingThe idealized lumped mass model of the reinforced concrete structure used in the analysis is shown in Figure 3.7-13. Element properties are given in Table 3.7-18 and mass point properties in Table 3.7-19. The effects of horizontal translation and rocking of the base were considered.The soils investigation of Section 2.5.4 revealed a soils profile from bedrock consisting of a firm silty gravel overlain by lean clays, silt of low plasticity, and sandy silt. In order to assure a firm foundation for the structure, the material between the top of firm gravel 3.7-14SEISMIC DESIGN WATTS BARWBNP-110and the grade slab (a depth of approximately 17 feet) was excavated and replaced with compacted granular fill.The Diesel Generator Building is founded on granular fill overlying firm gravel (see Figure 2.5-226). The shear wave velocity for the foundation material was determined to be 1650 ft/s and was used to calculate the value of the soil springs for the lumped-mass soil-structure interaction model. A parametric study was conducted to investigate the effects on building response of varying the shear wave velocity of the foundation material from 1150 ft/s to 2150 ft/s. The parametric study resulted in the structure being designed for earthquake loads from the peak of the amplified response spectrum for surface motion. The predominant motion of the structure was a translatory rigid body motion. Motion of this type results in large damping; therefore, a damping ratio of 0.10 was used for the analysis. Longitudinal motion was also considered. Periods for the normal modes of vibrations are listed in Table 3.7-20. Response spectra were produced for damping ratios of 0.005, 0.010, 0.020, 0.050, and 0.070 for mass points 1, 3, and 6 for motion in both east-west and north-south directions.Waste Packaging Area (WPA)The following two paragraphs describe the original design basis analysis for using SetA criteria performed for the WPA.The idealized lumped mass model of the reinforced concrete structure is shown in Figure 3.7-14. Element properties are given in Table 3.7-21 and mass point properties in Table 3.7-22. The analysis indicated that the primary motion of the structure was in rocking and translation of the base. Motion of this type results in large damping; therefore, a damping ratio of .10 was used in the analysis. Longitudinal motion was also considered. Periods for the normal modes of vibration are listed in Table 3.7-23.Due to the extent of excavation for the Auxiliary Building and the results of the investigation for the Diesel Generator Building, all in situ material down to the top of rock was excavated and replaced with compacted granular fill for the WPA (see Figure2.5-225). The shear wave velocity for the material was determined to be 1650 ft/s, and was used to calculate the value of the soil springs for the lump-mass soil-structure interaction model. A parametric study was conducted to investigate the effects on building response of varying the shear wave velocity from 1150 ft/s to 2150 ft/s. The parametric study resulted in the structure being designed for earthquake loads from the peak of the amplified response spectrum for surface motion. Additional studies beyond those described above have been performed to determine relative displacements between the WPA and the Auxiliary and Control Buildings.Refueling Water Tanks and ERCW Pipe TunnelsThe refueling water tank and foundations were designed for seismic loads determined from the basic procedure outlined above. Soil property variations were considered in SEISMIC DESIGN 3.7-15WATTS BARWBNP-110order to define conservative design loads, and ten-percent damping was used because of predominant translational soil spring motion. The adequacy of the design was later verified by more exact analytical techniques for soil-structure and fluid-structure interaction.Pipe tunnels are analyzed as discussed under "Underground Electrical Concrete Conduit Banks" except axial loads are not considered due to the segmented configuration of the tunnel. Dynamic soil pressures on the walls are determined in accordance with Reference [1].Underground Electrical Concrete Conduit BanksThe underground electrical concrete conduit banks which lead from the Auxiliary Building to the Diesel Generator Building and the Intake Pumping Station were seismically analyzed.Utilizing the average values for the soil shear wave velocity and density, the ground deformation pattern in terms of wave length and amplitude is determined. The buried conduit banks are assumed to deform along with the surrounding soil layers.The average shear wave velocity of a single layer representation of a multi-layered soil system may be determined by:Where, V ST= Average shear velocity in the soil, ft/sec V S = Shear velocity in each layer of soil, ft/sech' = Depth of each layer of soil, fth = Total depth of soil, ftThe fundamental period of the single layer is calculated from the following equation:

If the depth of the soil layer varies over the distance traversed by the buried conduit bank, both cases, for maximum and minimum depths, are considered.

V ST V s h'h----------

-=T 4h V ST----------(seconds)

=

3.7-16SEISMIC DESIGN WATTS BARWBNP-110The maximum amplitude of the sine wave which represents the maximum displacement of the conduit bank is:

Where,T = Fundamental period, secAccel = Amplified soil acceleration value, in/sec 2The wave length, L, is calculated as:

L = V ST TThe bending moment resulting from the seismic disturbance, assuming the conduit bank follows the soil and deforms as a sine wave, is given by:

where,M = Maximum bending moment, in-lbE = Modulus of the conduit bank, psiI= Moment of inertia of the conduit bank, in 4A = Maximum amplitude, inL = Wave length, inThe axial strain experienced by the conduit banks due to deformation of the soil is also evaluated. The axial strain due to seismic propagating waves is computed following the methods of Newmark

[15], [16], Yeh[18], and Kuesel[17] which assume the soil is linearly elastic and homogenous, the conduit bank behaves as a slender beam, and the buried member deforms with the surrounding soil (this implies the strain in the soil equals the strain in the member).The effect of soil strain from a seismic event on conduit bank turns in a buried system must be analyzed in greater detail than just calculating the axial strain. The effect of ADisplacement T 2------2* (Accel)==M 2 EIA L 22------------------

=

SEISMIC DESIGN 3.7-17WATTS BARWBNP-110these strains on turns is more complex due to the turn trying to resist the strain. The complexity is a function of the conduit bank and backfill soil properties.The basis for determining the effect of the strains on the conduit bank turns is described by Shah and Chu

[19]. The Shah and Chu theory has been developed into an analysis procedure by Goodling[20, 21, 22]. The committee on Seismic Analysis of the ASCE Structural Committee on Nuclear Structures and Materials prepared a report "Seismic Response of Buried Pipes and Structural Components"[23] which explains and amplifies the referenced methodology

[19] and analysis procedure[20, 21, 22]. These references shall be used for analysis of the effects of axial strain on buried conduit bank turns.The magnitude of friction acting on the conduit banks to use in the analysis depends on several factors, such as surface condition, contact pressure, soil strengths, etc. The friction force acting on the conduit banks is determined in accordance with Reference[24].Differential movement due to soil settlement or displacement during a seismic event was also evaluated in accordance with criteria given in Sections 2.5.4.10 and 2.5.4.8, respectively.The conduit banks were evaluated for settlement due to the potential liquefaction of the underlying soil as discussed in Section 2.5.4.8 (see Figures 2.5-576 through 2.5-578 for the potential settlement values). The banks were evaluated for potential settlements between manholes and at building/conduit interfaces. The only area of potential structural inadequacy was at the Intake Pumping Station (IPS). The conduit banks in this area (see Figure 3.8.4-46) required modification to accommodate the potential settlements. This modification consists of cutting 10 grooves on all 4 sides of the banks. The 2 inch wide by 2 inch deep grooves on top and sides and 3 inch wide by 2 inch deep grooves on the bottom begin 76 feet from the IPS and are spaced at 8inch between centers for a distance of 6 feet along each bank. Settlement of the conduit banks will cause plastic hinges to develop at the grooves and at the pile supports farthest from the IPS. This results in a structural mechanism which will allow the conduit bank to settle without compromising the intended function of the encased conduits.Class 1E Electrical Systems Manholes These manholes are rigid structures which have the same motion as the soil deposits in which they are located. The soil deposits were analyzed as explained in Section3.7.2.4. The accelerations obtained for the soil deposit at the level of the manholes were used to determine the inertia force on the structures and to calculate the increase in the static soil pressure using the shaking table experiments performed for the design of TVA's Kentucky Hydro Project[1], as discussed in Section 3.7.2.1.1.Miscellaneous Yard StructuresThe ERCW discharge overflow structure, ERCW standpipe structures I and II, and other miscellaneous yard structures are normally rigid structures. These structures are 3.7-18SEISMIC DESIGN WATTS BARWBNP-110designed for a rigid body acceleration. Dynamic soil pressures on the walls, if appropriate, are determined in accordance with Reference [1].Structure Interaction Analysis - WPA, CDWE, and ACBIn the WPA Original Analysis (Set A) a decoupled, two-stage SSI analysis was used to determine conservative structural responses. An analysis, using the Set A Criteria and revised soil properties, confirmed that there is sufficient gap between the WPA and ACB to preclude impact during a seismic event. For the CDWE, the Set A analysis was based on engineering judgments relating to the modeling of the supporting piles and on the assumption of full contact between the building's mat foundation and underlying soil. Additional analysis was performed to more accurately consider the stiffness of the pile groups and the postulated gap between the slab and soil. Results of this analysis confirmed that the gap between the buildings is sufficient for seismic separation and the design of the structure and piles is adequate.

3.7.2.1.4 Category I Soil-Supported Structures - Evaluation and New Design/Modification Analysis (Set B and Set B+C)For Category I structures founded upon soil, the top-of-rock motions were considered to be amplified (or attenuated) through the soil. The value of amplification and the change in frequency content of the excitation were determined by a soil column analysis that incorporates strain-dependent soil properties. The soil properties were varied by the amount given in Tables 2.5-17A through 2.5-17D to obtain different soil surface motion time histories associated with mean, upper bound and lower bound shear moduli and bulk modulus for the horizontal and vertical analyses, respectively. For vertical motion, strain-compatible soil properties determined from the horizontal analysis were used. Using these surface motions as control motions, OBE and SSE and site-specific SSE and OBE Soil-Struc ture Interaction (SSI) analyses were performed and structural responses including floor acceleration time histories were obtained. The SSI analyses were performed using a 3-D flexible-volume substructuring technique and Fast Fourier Transform (FFT) method. From the floor acceleration time histories, ARS were developed. For Set C, the responses obtained from the four time history analyses were averaged. For Set B, the co-directional responses from the three component earthquake excitations were combined using the SRSS method for each of the three soil property cases. Responses from these three soil property cases were enveloped for Set B and C.Details of the supporting media and foundation characteristics to be used in Set B and Set C analysis of Category I soil-supported structures are discussed in Section 2.5. Additional details of seismic analyses specific to each of the Category I soil-supported structures are described in the following paragraphs.Diesel Generator BuildingThe 3-D lumped parameter model used for the Diesel Generator Building is shown in Figures 3.7-13A and 3.7-13B, and the associated model properties are given in Tables3.7-19A and 3.7-19B.

SEISMIC DESIGN 3.7-19WATTS BARWBNP-110Refueling Water Storage TankThe hydrodynamic effects were modeled considering the effects of tank flexibility. The 3-D lumped parameter model of the refueling water storage tank is shown in Figure3.7-13C, and the associated model properties are given in Table 3.7-19C.Waste Packaging AreaThe waste packaging area does not house any safety systems and components. Therefore, Set B and Set C analyses were not performed.ERCW Pipe TunnelsSince the tunnels are embedded in soil, their response follows the response of the surrounding soil medium. Therefore, the ARS for the tunnels were obtained as the envelope of the ARS at the tunnel elevation from the soil column analyses considering mean, upper bound and lower bound shear moduli. For Set C, the ARS from the four time history analyses were averaged prior to enveloping. The horizontal ARS and the vertical ARS were determined from analysis of the appropriate soil column. The seismic analysis methodology used for the pipe tunnels is described in Section 3.7.2.1.3.

3.7.2.1.5 Category I Pile-Supported Structures - Orig inal Analysis (Set A) For structures founded on piles, the acceleration at top of rock was considered to be amplified through the soil as discussed in Section 3.7.2.4. The translational and rocking foundation springs included in the lumped mass model of the structure to characterize soil-structure interaction were calculated using Reference [3]. The damping ratio used for soil-supported structures depended upon the predominant type of motion as explained in Reference [5].A more detailed description of the seismic analysis of Category I pile-supported structures is discussed below.Additional Diesel Generator BuildingRefer to Section 3.7.2.1.6.Condensate Demineralizer Waste Evaporator Building (CDWE)The CDWE Building is a pile supported, reinforced concrete structure. The building consists of two stories and is approximately 54 feet-9 inches by 41 feet-9 inches in plan and 59 feet high. The pile group supporting the CDWE Building consists of 104 vertical and 46 batter piles driven through 30 feet of soil to refusal in sound rock.The seismic analysis of the CDWE Building was comprised of both a normal mode analysis using lumped mass models and a plane strain analysis using 2-dimensional models. The normal mode analysis was conducted for the north-south, east-west, and vertical directions. The plane strain analysis was conducted for the east-west and vertical directions assuming a unit depth in the north-south direction.

3.7-20SEISMIC DESIGN WATTS BARWBNP-110In the normal mode analysis, a model of the soil deposit was used to determine the acceleration time history at the top of ground from the specified bedrock acceleration records. The top of ground acceleration records were then used as input to a lumped mass model of the CDWE Building through a set of translational and rotational springs representing the pile group. The lumped mass models for the normal mode analysis are shown in Figure 3.7-15A.The earthquake motion used in the analysis was determined by amplifying the four artificial earthquake input at top of rock through the supporting soil. The maximum top of rock horizontal accelerations for these earthquakes are 0.09g and 0.18g for the OBE and the SSE, respectively. The vertical motions are two-thirds of the horizontal.The amplification of these earthquakes through the soil is performed by considering the soil as an elastic medium and making a dynamic analysis of a slice of unit thickness considering only the horizontal resistance of the soil. The soil deposit was divided into layers which would permit transmission of vibrational frequencies up to 30 Hz. An average value of the shear modulus was determined for each layer based on the effective vertical stress in the layer and then an average for the entire deposit was calculated. To account for uncertainties in the soil properties, three soil profiles were considered in the normal mode analysis. The three profiles correspond to soil deposits having the calculated average value of shear modulus and variations of + 50% in the shear modulus. Only the average profile was considered in the plan strain analysis. The values of shear modulus and corresponding shear wave velocities for the three soil profiles are shown in Table 3.7-23A. A damping ratio of 10% is used for the soil.

From this analysis, four corresponding top of rock earthquake motions are obtained for use as input to the structural model. The vertical motion at top of ground is assumed to be two-thirds of the horizontal motion.The lumped mass model of the building for the normal mode analysis consists of four mass points and four elements, the mass and inertia of the base, and translational and rotational springs representing the pile group. The mass points, elements, and spring properties are given in Table 3.7-23A.The pile group is composed of 104 vertical and 46 batter piles. The pile group was modeled by equivalent translation and rocking springs in both horizontal directions and a vertical spring.Once a set of spring constants were determined, the lateral and rocking springs were both modified by the same factor to produce a natural period for the structure of 0.15 second in each horizontal direction to correspond to the peak in the top of ground acceleration response spectrum. The spring constants representing the pile group are shown in Table 3.7-23A.A normal mode time history analysis of the lumped mass model was conducted. A damping factor of 5% of critical was used in this step of the analysis for both soil springs and structural elements. The loads thus compared were considered to be overly conservative, and since the top of ground horizontal accelerations were approximately doubled by the base springs, the horizontal loads in the building were reduced by SEISMIC DESIGN 3.7-21WATTS BARWBNP-110one-half. A plane strain analysis of the soil-structure system was then conducted for the SSE in the E-W and vertical directions to verify the reduction in the horizontal loads computed by the normal mode analysis. The input accelerations for the latter analysis were the top of rock acceleration records specified for the Watts Bar Nuclear Plant.The plane strain analysis was conducted using a 2-dimensional model of the soil-structure system in order to verify reducing the results obtained in the normal mode analysis. The model included soil-structure interaction effects, and cases were run with and without the pile group stiffness included in the soil properties. Damping factors of 10% of critical for the soil elements and 5% of critical for the base mat and CDWE Building elements were used in the plane strain analysis. The soil properties are linear and elastic.The time history accelerations specified for top of rock were applied at the base of the model, and the free field top of ground acceleration was compared to the lumped mass model top of ground motion. The plane strain analysis indicated the horizontal acceleration amplification through the soil and base springs in the lumped mass analysis was excessive and a reduction of the horizontal loads in the building by a factor of one-half was justified.

3.7.2.1.6 Category I Pile-Supported Structures - Evaluation and New Design/Modification Analyses (Set B and Set B+C) Additional Diesel Generator Building (ADGB)The original criteria for the ADGB design basis seismic analysis was based on NUREG-0800 and Regulatory Guide 1.60 ground design spectra. These criteria were incorporated into the FSAR after the issuance of NUREG-0847, WBNP Safety Evaluation Report, Supplement 2, 1984. In order to bring the ADGB in line with the other Category I structure, the structure has been reanalyzed in accordance with SetB and Set C criteria. The seismic responses (ARS, accelerations, displacements, forces and moments) defined by Set B and the envelope of Set B and Set C (Set B + C) are used in evaluating the adequacy of existing structures, as well as new designs and modifications.The 3-D lumped parameter model used for the ADGB is shown in Figures 3.7-15B and 3.7-15C, and the associated model properties are given in Tables 3.7-23B and 3.7-23C.Condensate Demineralizer Water Evaporator Building (CDWE)The CDWE Building does not house any safety-related systems and components. Therefore, Set B and Set C analyses were not performed.3.7.2.2 Natural Frequencies and Response Loads for NSSSThe natural frequencies of Westinghouse supplied components are considered in the system seismic analysis. The natural frequencies are listed in detail in the component stress reports.

3.7-22SEISMIC DESIGN WATTS BARWBNP-110 3.7.2.3 Procedures Used for Modeling 3.7.2.3.1 Other Than NSSSThe procedures used to formulate original analysis mathematical models of each Category I structure have been discussed in Sections 3.7.2.1.1 and 3.7.2.1.3. The mass of supported equipment was considered in the lumped masses at the points of support. The stiffness of supported equipment was not considered in the lumped mass model of the structure.For evaluation and new design or modification analyses, the stiffness and mass of a subsystem (supported equipment, a system, or a component) are included in the model if either Criteria 1 or 2 given below apply:

(1)0.01 < R m < 0.10 and 0.8 <

R f < 1.25 (2)R m > 0.1where,When the criteria given above for the inclusion of both stiffness and mass are not met the mass of a subsystem is included in the model if the subsystem is comparatively rigid in relation to the supporting structure and rigidly connected to the supporting structure.

3.7.2.3.2 For NSSS AnalysisThe first step in any dynamic analysis for a system or component supplied by Westinghouse is to model the structure or component, i.e., convert the real structure or component into a system of masses, springs, and dash pots suitable for mathematical analysis. Essentially, the procedure is to select mass points so that the displacements obtained will be a good representation of the motion of the system or component. Stated differently, the true inertia forces are not altered so as to appreciably affect the internal stresses in the structure or component.The mathematical model used for the dynamic analysis of the reactor coolant system is shown in Figure 5.2-1. Figure 5.2-2 shows the mathematical model of the reactor pressure vessel.

R mtotal mass of subsystemtotal mass of structure---------------------------------------------------------------

-=R ffundamental frequency of subsystemdominant frequency of structure-------------------------------------------------------------------------------------------------

-=

SEISMIC DESIGN 3.7-23WATTS BARWBNP-110The determination as to whether the structure or component is analyzed as part of a system analysis or independently as a subsystem is justified on a case by case basis.

3.7.2.4 Soil/Structure Interaction 3.7.2.4.1 Original Analysis (Set A)For Category I structures founded upon soils, the rock motion was amplified to obtain the ground surface motion by considering the soil deposit as an elastic medium and making a dynamic analysis of a slice of unit thickness using only the horizontal shearing resistance of the soil. The four artificial earthquakes mentioned in Section3.7.1.2 were considered as the input motion at top of rock. Once the time history of surface accelerations was known, a response spectrum was produced for the analysis of the soil-supported structure. The vertical surface motion was considered as two-thirds of the horizontal surface motion.The soil amplification analysis is affected by the variations of onsite soil measurements, slanted soil layers, soil density, and depth of the soil deposit.

Therefore, for structures supported on a soil deposit, the parameters of the soil deposit beneath the structure were varied to obtain a series of ground motion spectra. An envelope was drawn from these spectra resulting in the final ground motion spectrum used in analyzing the structure.By following the procedure outlined, the maximum amplification of the ground response was obtained and the peak width of the ground response spectrum was wide enough to allow for variations in the frequencies of the structure due to variations in soil parameters.

3.7.2.4.2 Evaluation and New Design or Modification AnalysesFor Category I structures founded upon soil, the top-of-rock motions were considered to be amplified (or attenuated) through the soil. The value of amplification and the change in frequency content of the excitation were determined by a soil column dynamic analysis that incorporates strain-dependent soil properties. Therefore, the soil properties beneath the structure were varied by the amounts given in Tables2.5-17A through 2.5-17D to obtain different soil surface motion time histories.For Set B analyses, the top-of-rock input motions are those defined by the Evaluation Site Design Response Spectra and Evaluation Site Design Time Histories of Section3.7.1. For Set C analyses, the input motions are defined by the Original Site Design Response Spectra and the Original Site Design Time Histories (Section 3.7.1).

3.7.2.5 Development of Floor Response Spectra 3.7.2.5.1 Original AnalysisResponse spectra for use in computing the response of structural appurtenances, or of equipment attached to Category I structures were produced by the time-history modal analysis technique. The four artificially produced accelerograms (Section3.7.1.2) were the input motion at top of rock. To obtain a set of response 3.7-24SEISMIC DESIGN WATTS BARWBNP-110spectra for one mass point for one direction of motion, the procedure outlined in Figure3.7-37 was used.Spectral values were computed for the periods using the distributions shown in Table3.7-1, in addition to the natural frequencies of the structure. In all time-history calculations a time interval of 0.010 second was used.Response spectra were computed for percentages of critical equipment damping of 0.5, 1.0, 2.0, 3.0, 4.0, 5.0 and 7.0. Response spectra were calculated for both the OBE and SSE; except, for those instances when the same percentage of critical structural damping was specified for both earthquakes, response was calculated for the OBE or SSE only (the SSE results equal twice the OBE).Horizontal response spectra were produced at ground level, at major floors, and at other points of interest within the structure for both east-west and north-south directions, except where symmetry justifies the use of one direction.For a direction in which torsion is considered, the time histories of accelerations used to produce the spectra will be computed where the maximum accelerations occur at that level (the farthest points on the structure from the shear center, on the axis perpendicular to motion).Unless otherwise noted, vertical response spectra were produced at ground and at major floor elevations. The response spectra for ground was used throughout that portion of the structure where no structural amplification occurred. For other points, values were interpolated linearly between adjacent floors.

3.7.2.5.2 Evaluation and New Design or Modification AnalysisResponse spectra for Set B and Set C analyses are produced by the time history modal analysis technique. For evaluation (Set B) analyses, the co-directional time history responses are either computed directly by simultaneous application of the directional seismic inputs or by the SRSS method. Set C co-directional responses are combined by the SRSS method only.OBE (Set B) and OBE (Set C) constant damping response spectra are computed for damping ratios of 1, 2, 4, 5 and 7%. Site-specific SSE and SSE spectra are computed for 2, 3, 5 and 7%. Site-specific SSE, OBE (Set B), OBE and SSE variable damping response spectra are also computed for both Set B and Set C in accordance with ASME Code Case N411.The ARS values were generated for the standard 75 spectral frequencies specified in Table 3.7.1-1 of the SRP plus the significant structure natural frequencies that are below the frequency limit of 33 Hz. For the ACB, FSAR Table 3.7-1 spectral frequencies were used for Set C analyses. A study comparing the spectra obtained from the use of SRP and FSAR frequencies concluded that the use of FSAR frequencies for ACB Set C analyses is adequate.

SEISMIC DESIGN 3.7-25WATTS BARWBNP-110Two solution methods were used to generate floor response spectra. These were time domain method of analysis and frequency domain method of analysis. For the time domain method of analysis, a time interval of 0.005 second was used for structural analysis, and time intervals of 0.005 and 0.0025 seconds were used for generation of floor response spectra. For the frequency domain method of analysis, a time interval of 0.01 second was used for structural analysis, and a time interval ranging from 0.01 to 0.0025 seconds was used for generation of floor response spectra. The final Set B and Set C ARS include + 15% and + 10% peak broadening, respectively, for structures other than the ERCW tunnels. For Set C analyses, because of identical OBE and SSE structural damping, OBE ARS accelerations are one-half the corresponding SSE values. New design/modification ARS are defined by the envelope of Set B and Set C ARS.The ERCW pipe tunnels are embedded in soil and their response follows the motion of the surrounding medium. The ARS at tunnel elevations were obtained from an envelope of the ARS generated from soil column analyses using the mean, upper, and lower bound soil shear moduli.Vertical response spectra are calculated at the building extremities for the basemat and for all major floor elevations.3.7.2.6 Three Components of Earthquake Motion 3.7.2.6.1 Original Analysis (Set A)The seismic responses of Category I structures were computed by assuming the vertical earthquake to occur simultaneously with each of the two major horizontal directions separately. The derivation of the site response spectra and the design time histories for horizontal and vertical motion has been detailed in Sections 3.7.1.1 and 3.7.1.2, respectively.

3.7.2.6.2 Evaluation and New Design/Modification Analyses (Set B and Set C)The seismic responses of the Category I structures are determined assuming that the three components of the earthquake occur simultaneously.When the response spectrum method is used for seismic analysis of structures, the maximum structural response due to each of the three components of earthquake motion is combined by the SRSS of the maximum co-directional responses caused by each of the three components of earthquake motion at a particular point of the structure.When the time history analysis method is used for Set B analysis of structures, the co-directional responses from each of the three components of earthquake motions are either combined algebraically at each time step or the maximum responses from each earthquake are combined by the SRSS method. For Set C time history analyses, only the SRSS method is used to combine co-directional responses.

3.7-26SEISMIC DESIGN WATTS BARWBNP-1103.7.2.7 Combinati on of Modal Responses 3.7.2.7.1 Other Than NSSS 3.7.2.7.1.1 Origin al Analysis (Set A)The responses of all Category I structures were computed by the response spectrum modal analysis method. The responses were calculated in each component mode. The total response was then calculated by determining the square root of the sum of the squares (SRSS) of the modal responses. For example, the total acceleration in any direction was calculated as:Similar expressions exist for the other responses.When the frequencies of two or more modes are found to be closely spaced (modes whose frequencies are within 10% of each other), the responses of these modes were combined in an absolute sum manner. The resulting total was treated as that of a pseudo-mode and combined with the remaining modes by the SRSS method.The stresses in the structures were calculated assuming the vertical earthquake to occur simultaneously with either horizontal earthquake. For example, a typical expression for the stress x, caused by a horizontal earthquake in the x-direction and a vertical earthquake in the y-direction, would be: 3.7.2.7.1.2 Evaluation and Ne w Design or Modi fication AnalysesThe response spectrum method was used to determine the seismic responses for the Category I structures. The most probable response is obtained as the square root of the sum of the squares from the individual modes.For Set B and Set C analyses, either the response spectrum or time history analysis methods were used to determine the seismic responses of Category I structures. When the response spectrum method was used, modal responses were combined in accordance with NRC Regulatory Guide 1.92, Rev. 1. Modal responses computed by the time history method were combined algebraically at each time step. For either analysis method, a sufficient number of modes were investigated to assure participation of all significant modes.

a T a 1 2 a 2 2a n 2+++= x xx xy+=

SEISMIC DESIGN 3.7-27WATTS BARWBNP-110 3.7.2.7.2 NSSS SystemThe total seismic response of systems and major components within Westinghouse scope of responsibility is obtained by combining the individual modal responses utilizing the SRSS method. For systems having modes with closely spaced frequencies, this method is modified to include the possible effect of these modes. The groups of closely spaced modes are chosen such that the difference between the frequencies of the first mode and the last mode in the group does not exceed 10% of the lower frequency. Combined total response for systems which have such closely spaced modal frequencies is obtained by adding to the square root sum of the squares of all modes the product of the responses of the modes in each group of closely spaced modes and a coupling factor . This can be represented mathematically as:Where, R T = total response R i = absolute value of response of mode iN = total number of modes consideredS = number of groups of closely spaced modes

M j = lowest modal number associated with group j of closely spaced modes N j = highest modal number associated with group j of closely spaced modes K z = coupling factor with R T 2 R i 2 i 1=N2 R K R KK 1+=N jKM j=N j 1-j 1=S+= K1'K'-'k k'+--------------------------------

2+1-='j j 1'j2-12= j' j 2 j t-------d+=

3.7-28SEISMIC DESIGN WATTS BARWBNP-110Where,j = frequency of closely spaced mode j (rad/sec)j = fraction of critical damping in closely spaced mode j t d = duration of the earthquake (sec.)An example of this equation applied to a system can be supplied with the following considerations. Assume that the predominant contributing modes have frequencies as given below:There are two groups of closely spaced modes, namely with modes 2, 3, 4 and 6, 7.

Therefore,S = 2 number of groups of closely spaced modes M 1 = 2 lowest modal number associated with group 1 N 1 = 4 highest modal number associated with group 1 M 2 = 6 highest modal number associated with group 2 N 2 = 7 highest modal number associated with group 2N = 8 total number of modes consideredThe total response for this system is, as derived from the expansion of the first equation under Section 3.7.2.7.2:3.7.2.8 Interaction of Non-Category I Structures With Seismic Category I StructuresAll interfaces between Category I and non-Category I structures were designed to withstand the displacement and/or dynamic loads produced by both the Category I and non-Category I structures and equipment. The Turbine Building and Service Buildings are the only non-Category I structures for which this section applies. The Turbine and Mode12345678Frequency5.08.08.38.611.015.516.020 R T 2 R 1 2 R 2 2 R 3 2R 8 2 2 R 2 R 3 23+++++= 2+R 2 R 4 24 2 R 3 R 4 34 2 R 6 R 7 67++

SEISMIC DESIGN 3.7-29WATTS BARWBNP-110Service Buildings were analyzed for a total lateral base shear computed as the product of the mass of the structure and the ground acceleration for the SSE. The total lateral shear was distributed in the height of the structure according to the provisions of the Uniform Building Code.

3.7.2.9 Effects of Parameter Va riations on Floor Response SpectraTo account for variations in structural frequencies owing to variations in material properties of the structure and soil and to approximations in modeling techniques used in seismic analyses, the computed floor response spectra are smoothed and peaks associated with the structural frequencies are broadened + 10% for Set A and Set C and + 15% for Set B.For the soil-supported structures in which floor response spectra were produced, the soil properties were varied to account for variations in soil properties. Soil-structure interaction was considered as discussed in Sections 3.7.2.1 and 3.7.2.4.

3.7.2.10 Use of Constant Vertical Load Factors 3.7.2.10.1 Other Than NSSS 3.7.2.10.1.1 Origin al Analysis (Set A)A vertical lumped mass dynamic analysis using the techniques outlined in Section3.7.2.1.1 was performed for all of the Category I structures to determine the vertical loads. The results for each horizontal earthquake analysis were separately added on an absolute basis to the loads from the vertical earthquake analysis. Static vertical load factors were not used unless the dynamic analysis indicated the structure behaved as a rigid body in the vertical direction.3.7.2.10.1.2 Evaluation and Ne w Design or Modification AnalysesThe Category I structures, when analyzed for vertical motion, used lumped-mass dynamic techniques as discussed in Section 3.7.2.1.2. For Evaluation Analyses (SetB), the co-directional time history responses are either computed by simultaneous application of the seismic input in three directions or by the SRSS method. For Set C, co-directional responses are combined by SRSS only. For systems and components the appropriate floor response spectra was used in the analysis. Static load factors were not used for either Set B or Set C analysis.

3.7.2.10.2 For NSSSStatic vertical load factors are not used as the vertical floor response load for the seismic design of safety-related systems and components within Westinghouse scope of responsibility.

3.7.2.11 Methods Used to A ccount for Torsional EffectsThe dynamic analysis of structures is discussed in Section 3.7.2.1. In original or SetA analyses, torsional effects were considered by using a lumped-mass cantilever beam 3.7-30SEISMIC DESIGN WATTS BARWBNP-110model to represent stiffness and inertial characteristics. The torsional moment of inertia, eccentricity, and mass moment of inertia were included in the analyses.In the process of preparing lumped-mass mathematical models for the Set A analyses, the location of both the center of rotation and center of mass for each floor were computed. Accelerations and deflections were calculated where their maximum values occurred (at the farthest points on the structure from the shear center, on the axis perpendicular to the direction of motion).For Set B and Set C analyses, modeling of torsional effects was refined by three-dimensional modeling.The models described above were subjected to seismic excitations and the resultant responses in the form of frequencies, mode shapes, moments, and forces were obtained.3.7.2.12 Comparison of R esponses - Set A versus Set BThe comparison of Set A and Set B responses showed that, in general, Set A responses were higher. In making the ARS comparisons, the applicable damping ratios of Set A and Set B were used. In certain frequency ranges, Set B responses were higher than Set A responses. An evaluation was performed on a building by building basis to assess the impact of Set B response. Adequacy of structures, systems, and components for Set B effects has been documented in calculations.As a sample comparison of Set A and Set B responses, the ARS comparisons for Auxiliary Control Building, which is a rock-supported structure, and for the Diesel Generator Building, which is a soil-supported structure, are presented. The ARS for north-south, east-west and vertical directions are compared. The comparison at Elevation 692.0 and Elevation 814.25 of the Auxiliary Control Building are presented in Figures 3.7-15D through 3.7-15I.

3.7.2.13 Methods for Seismic Analysis of DamsSince no dams are utilized to impound bodies of water to serve as heat sinks, this section is not applicable to this site.

3.7.2.14 Determination of Category I Structure Overturning Moments3.7.2.14.1 Original AnalysisFrom the dynamic analyses of the structures, the seismic moments, shears, and vertical loads were determined at the base of the structure. These loads were used in combination with other appropriate loads in determining total overturning effects as discussed in Section 3.8.

3.7.2.14.2 Eval uation and New De sign or Modification AnalysisFrom the dynamic earthquake, analyses total moments, shears, and vertical loads were computed.

SEISMIC DESIGN 3.7-31WATTS BARWBNP-110The earthquake moment, shear, and vertical load were used in combination with other appropriate loads in determining total overturning effects as discussed in Section 3.8.

3.7.2.15 Analysis Procedure for DampingThe damping values used in the dynamic earthquake analyses of Category I structures are given in Table 3.7-2.For Set A analysis, the Category I structural models were not coupled together, therefore, the structural damping values used in the seismic analyses are as shown in Tables 3.7-2 and 3.7-24.For Set B and Set C analyses, either composite modal damping or structural damping were used in the seismic analyses of Category I structures. The damping values used for the various structures and components are given in Tables 3.7-2 and 3.7-24. The damping used in the seismic analysis of systems and components are also given in Tables 3.7-2 and 3.7-24.Under the Westinghouse standard scope of supply and analysis, the lowest damping value associated with each element of the system is used for all modes.

3.7.3 Seismic

Subsystem Analysis 3.7.3.1 Seismic Analysis Me thods for Other Than NSSSThe seismic analysis of Category I piping systems is described in detail in Section3.7.3.8. In the analysis of piping subsystems there are two distinct approaches to seismic analysis. A detailed analysis is discussed in Section 3.7.3.8.2 and a simplified analysis is discussed in Section 3.7.3.8.3.The general seismic analysis of Category I equipment and components is discussed in Section 3.7.3.16. Additional details applicable for simplified analysis are discussed in Sections 3.7.3.5 and 3.7.3.10.The seismic analyses of HVAC and conduit/cable tray subsystems are discussed in Sections 3.7.3.17 and 3.10.3, respectively.The detailed seismic analyses of Category I subsystems is based upon dynamic analyses using the lumped mass normal mode method with idealized mathematical models. The inertial properties of the models are characterized by mass, eccentricity, and mass moment of inertia of each mass point. Mass points are located at carefully selected points in order to accurately model the subsystem as described in Section 3.7.3.3.1. The stiffness properties are characterized by the moment of inertia, area, torsion constant, Young's modulus, and shear modulus.The response of Category I subsystems are computed by the response spectrum modal analysis method for designs. All significant modes of vibration are considered 3.7-32SEISMIC DESIGN WATTS BARWBNP-110in determining the total response. Subsystem response is calculated in three orthogonal directions. Seismic responses of the Category I subsystems, equipment, and components are determined and combined in accordance with Sections 3.7.3.6 and 3.7.3.7. The damping ratios used in the dynamic analyses of the structures, subsystems, and equipment/components are shown in Table 3.7-2.

3.7.3.2 Determination of Nu mber of Earthquake Cycles 3.7.3.2.1 Category I Systems and Components Other Than NSSSDuring the design life of the plant (40 years), two earthquakes of OBE magnitude and one SSE are postulated to occur. This was based upon a study of seismic history in the Southern Appalachian Province over a 100-year period. Based on this study, each occurrence is conservatively assumed to have a time duration of 15 seconds of strong excitation.For Class A Category I components, an evaluation of predominant frequencies revealed that the most significant response of components is conservatively considered using an average frequency of 20 Hz. Therefore, the total number of cycles considered for the OBE and SSE are 600 and 300, respectively. The seismic qualification testing of Category I equipment considers the number of events and durations described above in accordance with IEEE 344-1975.ASME Section III Class 1 Piping Analysis - Since the piping in this scope has been reanalyzed in accordance with SRP requirements, the piping analysis has assumed the occurrence of 5 OBEs and 1 SSE. The number of peak stress cycles may be obtained from the synthetic time history used for the analysis (with a minimum duration of 10 seconds), or a minimum of 10 peak stress cycles per event assumed.

3.7.3.2.2 NSSS SystemWhere fatigue analysis of mechanical systems and components is required, Westinghouse specifies in the equipment specification that 20 occurrences of OBE having 20 cycles of maximum response for each occurrence, be analyzed. The fatigue analyses are performed as part of the stress report.

3.7.3.3 Procedure Used for Modeling 3.7.3.3.1 Other Than NSSS 3.7.3.3.1.1 Modeling of Piping Systems for De tailed Rigorous AnalysisThe continuous piping system is modeled as an assemblage of beams. The mass of each beam is lumped at the nodes connected by weightless elastic members, representing the physical properties of each segment. The pipe lengths between mass points are such that the adequate simulation of the dynamic characteristics of the piping system is ensured. All concentrated weights on the piping system such as main SEISMIC DESIGN 3.7-33WATTS BARWBNP-110valves, relief valves, pumps, motors, and effects of support mass on piping system when found to be significant are modeled as lumped masses unless isolated from the system by positive anchorage. The torsional effects of the valve operators and other line-mounted equipment with offset center of gravity with respect to center line of the pipe is included in the analytical model.

3.7.3.3.1.2 Mode ling of EquipmentFor seismic analysis, Seismic Category I equipment is represented by lumped mass systems which consist of discrete masses connected by weightless springs. The criteria used to lump masses are:

(1)The number of modes of a dynamic system is controlled by the number of masses used. The number of masses is chosen so that all significant modes are included. The modes are considered as potentially significant if the corresponding natural frequencies are less than 33 Hz. For modes greater than 33 Hz the rigid response contribution is considered.

(2)Mass is lumped at points where significant concentrated weight and continuous mass are located.

3.7.3.3.1.3 Modeling of HVAC, Conduit, and Cable Tray SubsystemsRuns of HVAC, conduit, and cable tray subsystems (including supports) are modeled by continuous or discrete mass models with the interconnecting elements represented by their effective stiffness properties. Additional lumped masses are applied at or near significant concentrated weights such as from fittings or other in-line or attached commodities. Significant concentrated weights are those which cannot be adequately represented by smearing their effect as part of the overall uniform mass. Mass eccentricities and torsional stiffnesses are considered. Where models are truncated, at least one span and the next support on either side of the contiguous span(s) and support(s) of interest for evaluation are modeled. Alternately, the contiguous span(s) and support(s) of interest are evaluated with one half of the adjacent spans on either side modeled with symmetry boundary conditions such that no artificial stiffening is introduced.A sufficient number of masses (or degrees of freedom) are modeled such that additional masses would not increase the predicted responses by more than 10%. Alternately, the number of masses are modeled to be at least twice as many as the number of modes with frequencies less than 33 Hz. The dynamic analysis considers all modes with significant mass participation such that inclusion of additional modes would not increase the predicted responses by more than 10%. Alternately, the dynamic analysis considers all modes up to 33 Hz and includes an additional check for any missing mass.3.7.3.3.2 Modeling of NSSS SubsystemsThe criteria and procedures used for model ing of NSSS subsystems is given in Section3.7.2.3.

3.7-34SEISMIC DESIGN WATTS BARWBNP-110 3.7.3.4 Basis for Sele ction of Frequencies 3.7.3.4.1 Other Than NSSSThe method used to analyze systems for dynamic loading is the modal response spectrum method.Frequencies of the subsystems are selected such that all significant modes of vibration are included in the analysis. Frequencies of simplified analysis models are determined by solutions of closed form expressions. Frequencies of detailed analysis models are determined by computerized solutions.The subsystem or component model is subjected to loadings in the form of accelerations that represent the seismic environment of its supports. Since the response spectrum employed is representative of the building elevation at the equipment/system location considered, structural amplifications are reflected in the spectra. Therefore, the input acceleration values taken from the building response spectra and utilized as input to the dynamic analysis of the subsystem or component assures the model is loaded in a representative manner and the proper amplifications determined. The subsystem or component was analyzed and designed for the amplified loading.

3.7.3.4.2 NSSS Basis for Sel ection of Forcing FrequenciesThe analysis of equipment subjected to seismic loading involves several basic steps, the first of which is the establishment of the intensity of the seismic loading. Considering that the seismic input originates at the point of support, the response of the equipment and its associated supports based upon the mass and stiffness characteristics of the system, will determine the seismic accelerations which the equipment must withstand.Three ranges of equipment/support behavior which affect the magnitude of the seismic acceleration are possible:

(1)If the equipment is rigid relative to the structure, the maximum acceleration of the equipment mass approaches that of the structure at the point of equipment support. The equipment acceleration value in this case corresponds to the low-period region of the floor response spectra.

(2)If the equipment is very flexible relative to the structure, the internal distortion of the structure is unimportant and the equipment behaves as though supported on the ground.

(3)If the periods of the equipment and supporting structure are nearly equal, resonance occurs and must be taken into account.In addition, an equipment/support system is considered to be rigid if the fundamental natural frequency is greater than 33 Hz.

SEISMIC DESIGN 3.7-35WATTS BARWBNP-1103.7.3.5 Use of Equivalent Static Load Method of Analysis 3.7.3.5.1 Other Than NSSSFor discussion of the equivalent static load method as applied to equipment/components, see Sections 3.7.3.10.1, 3.7.3.16.1, 3.7.3.16.2, and 3.7.3.16.3.For other Category I subsystems, the following discussion applies:

Simplified seismic analysis by the equivalent static load method may be used as an alternative to detailed computer analysis when the subsystem being analyzed is adequately represented by an effective one degree-of-freedom system with multi-mode effects accommodated by the use of a multi-mode factor. A modal participation factor of 1.0 is used for the equivalent static load method. If the subsystem is determined to be rigid (fundamental frequency > 33 Hz), then the acceleration of the building at the elevation of the subsystem attachment (floor zero period acceleration) is used with a multi-mode factor of 1.0; i.e., the subsystem is evaluated for rigid-body response. When no frequency evaluation of the subsystem is made, the peak acceleration of the applicable floor response spectrum is used multiplied by a multi-mode factor of 1.5 except where a lower factor is justified. When a frequency evaluation is made and the subsystem is determined to be flexible, the highest acceleration at or above the determined frequency is used for evaluation multiplied by a multi-mode factor of 1.5 except where a lower factor is justified. For HVAC, conduit, and cable tray subsystems a multi-mode factor of 1.2 has been justified.

3.7.3.5.2 Use of Equi valent Static Load Method of Analysis for NSSSThe static load equivalent or static analysis method involves the multiplication of the total weight of the equipment or component member by the specified seismic acceleration coefficient, which is established on the basis of the expected dynamic response characteristics of the component. Components which can be adequately characterized as a single-degree-of-freedom system are considered to have a modal participation factor of one. Seismic acceleration coefficients for multi-degree of freedom systems, which may be in the resonance region of the amplified response spectra curves, are increased by 50 percent to account conservatively for the increased modal participation.3.7.3.6 Three Components of Earthquake MotionSeismic responses of Category I subsystems, equipment, and components are analytically computed or simulated by qualification tests for the applicable Set A, B, and C seismic inputs in three orthogonal directions. The Set A, B, and C inputs for original analysis/qualification, evaluation, and new design/modification are described in Section 3.7.2.

3.7-36SEISMIC DESIGN WATTS BARWBNP-110 3.7.3.6.1 Pi ping SubsystemsThe seismic responses of Category I piping subsystems are determined assuming that the three components of the earthquake motion occur simultaneously. The maximum response due to each of the three components of earthquake motion is combined by SRSS of the maximum directional responses caused by each of the three components of earthquake motion.

3.7.3.6.2 HVAC Duct ing, Conduit, and Cable Tray Subsystems The seismic responses of HVAC ducting, cable tray, and conduit subsystems are determined by two dimensional seismic analysis and associated testing of representative duct, cable tray, and conduit spans. Seismic input in each major horizontal direction is applied separately but simultaneously with vertical input.

Horizontal and vertical responses are analytically combined by absolute summation.

3.7.3.6.3 Other Than NSSS Equipment and ComponentsThe seismic responses of Category I equipment and components were determined by analysis or test in accordance with the guidelines of IEEE 344-1971 for procurements initiated prior to September 1, 1974. After that date procurement, evaluation, and modification activities applied the guidance of IEEE 344-1975 to determine the seismic responses. Floor or wall mounted equipment and components and their supports and anchorage are seismically analyzed or tested by application of the required seismic response spectra described in Section 3.7.2.5, in a two-dimensional manner. Seismic input in each major horizontal direction is applied separately but simultaneously with vertical input. Horizontal and vertical responses are analytically combined by absolute summation.Seismic responses of line-mounted equipment and components are determined by device analysis or testing techniques from IEEE 344-1971 or IEEE 344-1975, as applicable. These techniques are applied in a two-dimensional manner relative to the three orthogonal local axes of the line-mounted equipment and component.

Calculated seismic response of the subsystem at the equipment and component location is maintained at a level which is less than or equal to the device seismic qualification level.3.7.3.7 Combinati on of Modal Responses 3.7.3.7.1 Other Than NSSSModal responses of the piping subsystems are combined in accordance with Regulatory Guide 1.92, Revision 1. Modal responses of other subsystems are analytically combined by the techniques described in Section 3.7.2.7.1 for structures.Category I equipment and components are seismically analyzed or tested by IEEE Standard 344-1971 or -1975 techniques, as described in Section 3.7.3.6. In accordance with these standards, modal responses are analytically combined by SEISMIC DESIGN 3.7-37WATTS BARWBNP-110SRSS techniques except for closely-spaced modes whose responses are combined by absolute summation.

3.7.3.7.2 Combination of Modal Responses of NSSSFor the NSSS procedure for the combination of modal responses see Section3.7.2.7.2.

3.7.3.8 Analytical Proce dures for Piping Other Than NSSS 3.7.3.8.1 GeneralThe analysis of classified fluid system components other than the reactor coolant system considers both static and dynamic loadings. The l oading combinations considered and the allowable stress limits are discussed in Section 3.9.3.1. Thermal expansion, dead load, and normal operational stresses due to system pressurization for Category I piping systems are analyzed in accordance with the ASME Boiler and Pressure Vessel Code,Section III, Division 1 Nuclear Power Plant Components, 1971 Edition up to and including the Summer 1973 Addenda. Non-nuclear safety classes of pipe are analyzed in conformance with ANSI B31.1, Power Piping Code, 1973 Edition up to and including Summer 1973 Addenda as shown in Table 3.2-5. In addition, TVA Class M (chilled water) piping conforms to ANSI B31.5, 1974. Stresses due to all loadings are appropriately combined with the seismic stresses in accordance with Code requirements.As permitted by NA-1140 of applicable ASME Code, the following sections of more recent editions and addenda of the ASME Boiler and Pressure Vessel Code and ASME Code Cases are used. All related requirements were met. (A)CODE EDITIONS AND ADDENDA (1)Stress Intensification Factors (a)1974 Code; used for Stress Intensification Factors for Class 2 and 3 piping.(2)Nozzle Dimensions (a)Figure NB-3686.1-1 for nozzle dimensions from the Summer 1975 Addenda.

3.7-38SEISMIC DESIGN WATTS BARWBNP-110 (3)Material Properties (a)1980 Edition - including Summer 1980 Addenda, Appendix I, Table I-4.0; for thermal conductivity and thermal diffusivity of materials.(b)1983 Edition - including Winter 1983 Addenda, Appendix I, TableI-5.0; for coefficient of Thermal Expansion of materials which are not available in the Code of Record.(c)1983 Edition - including Summer 1985 Addenda, Appendix I, Table I-6.0; for Modulus of Elasticity of materials which are not available in the Code of Record.(d)1983 Edition - including Summer 1985 Addenda, Appendix I, Tables I-1.1, I-1.2, I-1.3, I-2.1, I-2.2, I-3.1, I-3.2, I-7.1, I-7.2, I-7.3, and I-9.1 for materials which are not available in the Code of Record.(4)Stress Qualification (a)1980 Edition - up to and including Winter 1982 Addenda, SectionIII, Subsection NB; May be used for the stress qualification of Class 1 piping (NB-3600).(b)1974 Edition - Summer 1976 Addenda,Section III, Paragraph NB-3630 (d); used for Class 1 piping which can be analyzed per requirements of Subsection NC.(c)1974 Edition - Winter 1976 Addenda,Section III, Paragraph NC/ND-3611.2.(d)1977 Edition - Section III, Paragraph NC/ND-3652.3.(e)1974 Edition - Summer 1975 Addenda,Section III, paragraph NC/ND-3651.(f)1974 Edition - Section III, Paragraph NC/ND-3652.4.

(5)Welded Attachments (a)1980 Edition - Winter 1980 Addenda,Section III, Paragraph NB-4433 which permitted the use of continuous fillet or partial penetration welds for welded structural attachments (Lugs) to the pipe.

SEISMIC DESIGN 3.7-39WATTS BARWBNP-110 (6)Flange Qualification (a)1983 Edition - up to and including Winter 1983 Addenda, SectionIII; Used for Class 1 Flange qualification per NB-3658; Used for Class 2 and 3 Flange qualification per NC-3658 and ND-3658.(7)Relief and Safety Valve Thrust (a)1977 Edition - Winter 1978 Addenda,Section III, Paragraph NC/ND-3622.5 and Appendix O.(B)CODE CASES (1)Half-Coupling Branch Connections (a)Code Case N-313, November 28, 1986, Alternate Rules for Half Coupling Branch Connections,Section III, Division 1, Class 2.

(2)Response Spectra (a)Code Case N-411-1, February 20, 1986, Alternative Damping Values for Seismic Analysis of Classes 1, 2, and 3 Piping Systems,Section III, Division 1, may be used.

(3)Stress Qualification (a)Code Case 1606-1, December 16, 1974, Stress Criteria, SectionIII, Classes 2 and 3 Piping Subject to Upset, Emergency, and Faulted Operating Conditions.(b)Code Case N-319, July 13, 1981, Alternate Procedure for Evaluation of Stresses in Butt Welding Elbows in Class 1 Piping.

(4)Welded Attachments (a)Code Case N-122, January 21, 1982, Stress Indices for Integral Structural Attachments,Section III, Division 1, Class 1.(b)Code Case N-318-3, September 5, 1985, Procedure for Evaluation of the Design of Rectangular Cross Section Attachments on Class 2 or 3 Piping,Section III, Division 1.(c)Code Case N-391, November 28, 1983, Procedure for Evaluation of the Design of Hollow Circular Cross Section Welded Attachments on Class 1 Piping,Section III, Division 1.(d)Code Case N-392, November 28, 1983, Procedure for Evaluation of Design of Hollow Circular Cross Section Welded Attachments on Class 2 and 3 Piping,Section III, Division 1.

3.7-40SEISMIC DESIGN WATTS BARWBNP-110Category I piping is classified into two analytical categories. These categories are defined below. Rigorous Analysis (Detailed Seismic Analysis) -- A comprehensive computer-aided analysis of the piping system to ensure that the system design meets all the ASME Section III requirements for stress in the piping.Alternative (Simplified) Analysis -- A conservative method for locating supports and determining support loads, using computer generated data, hand calculations and/or computer aided analysis to ensure that the ASME Section III code requirements are met. Systems Rigorously AnalyzedTVA evaluates the necessity of performing a Rigorous Analysis on all piping systems and identifies the limits of the analysis using the following guidelines:

(1)Class A piping systems not analyzed by the NSSS vendor.

(2)TVA Class B, C and D lines 2-1/2inches in diameter and larger.

(3)Piping in Category I structures larger than 1-inch diameter that has a maximum operating temperature of 200

°F or greater and a maximum operating pressure of 275 psig or greater unless it is determined that there is not a potential for unacceptable pipe rupture interactions.

(4)Piping which, due to high temperature or other extraordinary loading conditions, cannot be supported using alternate analysis methods.Systems Analyzed by Alternate (Simplified) MethodsPiping requiring seismic qualification, but not requiring rigorous analysis as outlined above, may be evaluated according to the alternate methods.3.7.3.8.2 Detailed Seismic Anal ysis (Rigorous) for Piping SystemsA detailed seismic analysis is performed on applicable piping systems by the response spectrum method. Each pipe run is idealized as a mathematical model consisting of lumped masses connected by weightless elastic members. Lumped masses are located at carefully selected points in order to adequately represent the dynamic and elastic characteristics of the pipe system. Using the elastic properties of the pipe, the flexibility matrix for the pipe is determined. The flexibility calculations include the effects of the torsional, bending, shear, and axial deformations. The stiffness of curved members, valves, branch connections, etc., is also taken into consideration.Once the flexibility and mass matrices of the mathematical model are determined, the frequencies and mode shapes for all significant modes of vibration are determined. All modes having a period greater than 0.0303 seconds (natural frequencies < 33 Hz) are used in the analysis. The mode shapes and frequencies are solved in accordance with the following equation:

SEISMIC DESIGN 3.7-41WATTS BARWBNP-110where:K = Square stiffness matrix of the pipe loopM = Mass matrix for the pipe loop w n = Frequency for the n th mode n = Mode shape matrix of the n th modeAfter the frequency is determined for each mode, the participation factors can be calculated by the following equation:Where: njk = Participation factor for mode n in the jth direction of support zone k. jk = Displacement matrix of all nodes due to a unit displacement of the jth direction restrained degrees of freedom in support zone

k. Support zone = A set of restrained nodes which move together during a dynamic event.Using these results and the corresponding spectral accelerations of the mode for the direction and support zone being excited, the response for each mode is determined by the following equation:Where: (V in)jk = Displacement of mass for mode n for an earthquake in the j th direction of support zone k. in = Value associated with mass i in n Kw n 2-Mn 0=njk n T M jk n T M n------------------

=V injknjk in Sanjk w n 2--------------------------------

-=

3.7-42SEISMIC DESIGN WATTS BARWBNP-110 Sanjk = Spectral acceleration for mode n for an earthquake in the j th direction of support zone k.Using these results, the maximum displacements for each mode are calculated for each mass point in accordance with the following equation:where: (V in)j = Displacement of mass i for mode n for an earthquake in the jth directionNZ = Number of support zones used for the pipe loop. However, if ASME Code Case N-411 damping values are used then all supports are in a single support zone. The maximum displacements for each mode are calculated as follows:where: V in = maximum displacement of mass i for mode n.j = x, y, and zThe maximum displacement for each mass is determined by combining the maximum deflection for each mode by the method described in Section 3.7.3.7. The contribution from higher frequency modes (period less than 0.0303 seconds) are combined with lower frequency modes by the SRSS rule.With the displacements known, the associated member forces/moments can be obtained by standard structural techniques. The forces for each mode and each earthquake direction will be combined using the conventions described above.

3.7.3.8.3 Alternate (Simplified) Analysis for Piping SystemsSection 3.7.3.8.1 defines alternate analysis and specifies the piping for which it may be applied. Various methods are used to perform alternate analysis. These methods may involve the use of simple beam equations, computer generated data and/or computer assisted analysis. For each method, the following general requirements are observed.(1)Deadweight V inj V injk k 1=NZ=V in V in 2j=

SEISMIC DESIGN 3.7-43WATTS BARWBNP-110Supports are located such that adequate rigidity is assured and pipe sagging is minimized.

(2)SeismicSeismic effects are approximated using accelerations from the applicable building response spectra. Response spectra accelerations at the frequency computed for the piping system are used except that if the computed frequency is below the frequency corresponding to the peak of the response spectra, the peak accelerations are used. The response spectra accelerations are increased by at least 50 percent to account for multimode response, unless justification is provided for using a lesser increase.

(3)Thermal Expansion and Anchor MovementThermal expansion and anchor movement are evaluated using conventional hand calculation methods, the results of computer analysis of typical configurations and/or computer aided thermal flexibility analysis.

(4)Pipe StressPipe stress resulting from applicable load sources are evaluated and combined in accordance with applicable code requirements. Details of load combinations and stress limits are provided in Section 3.9.3.1.2.

(5)Support LoadsSupport loads resulting from applicable load sources are evaluated and combined as specified in Section 3.9.3.4.2. 3.7.3.8.4 Seismic Analysis of Piping Systems That Sp an Two or More Seismic Support Zones Such as Buildings, Portions of Buildings, or Primary ComponentsEach building, portion of building, or primary component may be considered a separate support zone. The worst enveloped response spectrum for which any portion of the pipe located in that zone is subjected is used to represent the input motion in that zone.For the evaluation of relative support motions in the seismic analysis of piping systems interconnecting two or more seismic support zones, the maximum relative movement between component supports is assumed and the piping system is subjected to movements through the piping system supports and restraints. Separate cases for each of the three orthogonal directions are considered. Support movements are based on the maximum of the floor movements immediately above and below the support location.

3.7-44SEISMIC DESIGN WATTS BARWBNP-110 3.7.3.9 Multiple Suppor ted Equipment and Component s with Distinct Inputs 3.7.3.9.1 Other Than NSSSThe criteria and procedures for seismic analysis of equipment and components supported at different elevations within a building and between buildings with distinct inputs are similar to those described for piping in Section 3.7.3.8.4. When the equipment is supported at two or more points located at different elevations in the building, the response spectrum for the most severe single point of attachment is chosen as the design spectra.The relative displacement between supports is determined from the dynamic analysis of the structure. The relative support point displacements are used for a static analysis to determine the additional stresses due to support displacements.

3.7.3.9.2 Multiple Supported NSSS Equipment an d Components with Distinct InputsWhen response spectrum methods are used to evaluate reactor coolant system primary components interconnected between floors, the procedures of the following paragraphs are used. There are no components in Westinghouse scope of analysis which are interconnected between buildings. The primary components of the reactor coolant system are supported at no more than two floor elevations.A dynamic response spectrum analysis is first made assuming no relative displacement between support points. The response spectra used in this analysis is the worst floor response spectra. Any devia tion from this position will be subject for NRC review on a case-by-case basis.Secondly, the effect of differential seismic movement of components interconnected between floors is considered statically in the integrated system analysis and in the detailed component analysis. Per ASME Code rules, this stress caused by differential seismic motion is clearly secondary for piping (NB 3650) and component supports (NF 3231). For components, the differential motion will be evaluated as a free end displacement, since, per NB3213.19, examples of a free end displacement are motions 'that would occur because of relative thermal expansion of piping, equipment, and equipment supports, or because of rotations imposed upon the equipment by sources other than the piping'. The effect of the differential motion is to impose a rotation on the component from the building. This motion, then, being a free end displacement and being similar to thermal expansion loads, will cause stresses which will be evaluated with ASME Code methods including the rules of NB 3227.5 used for stresses originating from restrained free end displacements.The results of these two steps, the dynamic inertia analysis and the static differential motion analysis, are combined absolutely with due consideration for the ASME classification of the stresses.

SEISMIC DESIGN 3.7-45WATTS BARWBNP-110 3.7.3.10 Use of Constant Vertical Load Factors 3.7.3.10.1 Use of Constant Load Factors for Equipment Other Than NSSSWith respect to equipment, static analysis for seismic loading is recognized as an acceptable approach with restrictions as follows:

(1)The analysis method is consistent with the 'static coefficient method' as prescribed in IEEE 344-1975, Paragraph 5.3. The peak acceleration values of the applicable floor response spectra are multiplied by a factor of 1.5 if natural frequencies are not determined. The increased acceleration values are used as equivalent static load factors applied to the entire mass of the equipment being evaluated. Lower multiplication factors (between 1.0 and 1.5) are only used as justified by frequency analysis.

(2)The static coefficient analysis method is used only for the evaluation of structural integrity of equipment. It is recognized that the static analysis method alone is not sufficient for the qualification of safety-related active equipment where the demonstration of operability is required.

3.7.3.10.2 Use of Constant Vertical Load Factors for NSSSConstant vertical load factors are not used as the vertical floor response load for the seismic design of NSSS safety-related systems and components.3.7.3.11 Torsi onal Effects of Eccentric Masses 3.7.3.11.1 Piping Other Than NSSSThe torsional effects of eccentric masses such as valve operators are modeled in the piping mathematical model as lumped masses at the free end of cantilevered rods with a length equal to the distance from the center of gravity of the mass to the pipe flow axis. The stiffness of the rod is used to simulate the valve extended structure flexibility.

3.7.3.11.2 Torsional Effects of Eccentric Masses of NSSSThe effect of eccentric masses, such as valves and valve operators, is considered, when applicable, in the seismic piping analyses. These eccentric masses are modeled in the system analysis and the torsional effects caused by them are evaluated and included in the total system response. The total response must meet the limits of the criteria applicable to the safety class of piping.

3.7.3.12 Buried Seismic Category I Piping SystemsBuried piping complies with the ASME Boiler and Pressure Vessel Code,Section III and is analyzed seismi cally as follows:The soil is considered to be a horizontal 1-layer system which responds to the earthquake by moving in a continuous sinusoidal plane wave and supported by a second layer or base material. The top layer is assumed to pick up accelerations from the base material.

3.7-46SEISMIC DESIGN WATTS BARWBNP-110Utilizing the average values for the shear wave velocity and density for the top layers, the ground deformation pattern in terms of wave length and amplitude is determined. The buried pipes are assumed to deform along with the surrounding soil layers.The average shear wave velocity of a single layer representation of a multi-layered soil system may be determined by:where, V ST = Average shear velocity in the top layers of soil, ft/sec V S = Shear velocity in each layer of soil, ft/sec h' = Depth of each layer of soil, fth = Total depth of top layers of soil, ftThe fundamental period of the single layer is calculated from the following equation:If the depth of the soil layer varies over the distance traversed by the buried pipe, both cases, for maximum and minimum depths, are considered.The maximum amplitude of the sine wave which represents the maximum displacement of the pipe is:Where:T = Fundamental period, secAccel = Amplified soil acceleration value, in/sec 2 V ST V s h'h---------------

-=T 4h V ST----------(seconds)

ADisplacement T 2------2 *(Accel)=

SEISMIC DESIGN 3.7-47WATTS BARWBNP-110The wave length, L, is calculated as:

L = V ST TThe bending moment resulting from the seismic disturbance, assuming the pipe follows the soil and deforms as a sine wave, is given byWhere:M = Maximum bending moment, in-lbE = Modulus of the pipe, psiI = Moment of inertia of the pipe, in 4A = Maximum amplitude, in.L = Wave length, in.The corresponding bending stress is obtained by dividing the moment by the section modulus of the pipe. The above bending stress is combined with bending stresses due to other loads according to the applicable loading combinations.The axial strain experienced by the pipe due to deformation of the soils is also evaluated. The axial strain due to seismic propagating waves is computed following the methods of Newmark [15] and [16], Yeh [18], and Keusel

[17], which assume the soil is linearly elastic and homogenous, the pipe behaves as a slender beam, and the buried member deforms with the surrounding soil (this implies the strain in the soil equals the strain in the member).The effect of soil strain from a seismic event on elbows or turns in a buried pipe system must be analyzed in greater detail than just calculating the axial strain. The effect of these strains on elbows/turns is more complex due to the pipe elbow/turn trying to resist the strain. The complexity is a function of the pipe and backfill soil properties.The basis for determining the effect of the strains on the piping elbows/turns is described by Shah and Chu

[19]. The Shah and Chu theory has been developed into an analysis procedure by Goodling

[20], [21], and [22]. The committee on Seismic Analysis of the ASCE Structural Committee on Nuclear Structures and Materials prepared a report "Seismic Response of Buried Pipes and Structural Components,"[23] which explains and amplifies the referenced methodology

[19] and analysis procedure [20], [21] and [22]. These references shall be used for analysis of the effects of axial strain on buried piping.

M 2 EIA L 22-----------------

-=

3.7-48SEISMIC DESIGN WATTS BARWBNP-110The magnitude of friction acting on the pipe used in the analysis depends on several factors, such as pipe surface conditions, contact pressure, soil strengths, etc. The friction force acting on the pipe is determined in accordance with Reference [24].Differential MovementDifferential movement between the piping and a structure/feature occurs from two sources. The first is vertical, which can be caused by differential soil consolidation below the pipe or structure/feature. The second source is horizontal movement due to differential movement during a seismic event.Where practical, seismic classed buried piping is routed to avoid areas of weak soils. Where weak soils are encountered, the bad material is removed and replaced by backfill. The backfill is placed to standards that ensure suitable bearing conditions; therefore, the transition from one material to another, i.e., in situ soil to backfill, should not be a problem. In lieu of the above, in some cases an analysis is performed to show that the pipe has sufficient strength to bridge the discontinuity and support the soil above the pipe without exceeding the allowable stress of the piping material.Category I buried piping which penetrates structures where fill settlement or seismic movements are expected to be high is protected from differential movement of the soil and structure by Category I concrete slabs or encasements. The slab or encasement is supported by a bracket on the structure on one end and on undisturbed or Class A backfill at the other end. Bearing piles are used if required to support the slab. The encased pipes are insulated to prevent bonding between the pipes and concrete. For details of the slab at the intake pumping station and the encasement at the Diesel Generator Building, refer to Section 3.8.4.4. For seismic classed buried piping that penetrates structures in areas where very little fill is involved and seismic movements are low, protection from differential movement of the soil and structure is provided by an oversized opening in the structure. The annular space between the pipe and opening is filled with a resilient material. The first support inside the structure is located to allow for relative movement of the pipe and structure. The soil-structure interface is treated as an anchor, and stresses are limited to code allowables. Soil consolidation is determined in conformance with criteria given in Section 2.5.4.10 (static settlement) and 2.5.4.8 (dynamic settlement- soil liquefaction). The ERCW piping was evaluated for potential settlement due to soil liquefaction as discussed in Section 2.5.4.8. The potential settlements used for the evaluation were determined in the liquefaction evaluation using the strain criteria specified by the NRC staff which are shown on Figures 2.5-571 through 2.5-575. The effect of these potential settlements was evaluated for the entire length of pipe and also at all building interfaces. The evaluation of the effect of these potential settlements was done in two phases.The first phase was a preliminary screening which involved calculations to identify areas of the pipe which may undergo excessive settlement. In the preliminary SEISMIC DESIGN 3.7-49WATTS BARWBNP-110screening, the boundaries of the pipe system, the pipe sizes, and pipe materials were determined. Because of the size and length of pipe involved, a 60 foot length was chosen as sufficient to model the system. A fixed-fixed end model was assumed to describe the piping for the initial calculations. Using the standard equation for maximum deflection for a fixed-fixed end model:M = Resultant momentL = Span length E = Young's modulus I = Moment of inertia The settlement can be determined if the resulting-moment were known. ASME Code Section III (1977 edition) states that the effects of any single nonrepeated anchor movement is governed by Equation 10A:

i = Stress intensification factorZ = Section modulus

S c= Allowable stress at room temperatureTo expand this equation to include thermal effects (assumingMc=0) would involve adding it to Equation 11 (1971 ASME III Code, Summer 1973 Addenda, NC-3652.3) thus;Since the pipe sizes and materials are known, and the stress intensification factor can be calculated, the resultant moment at any point on the pipe can be determined. Thus the potential settlement can be found by using the standard equation for the fixed-fixed end model. The results from these prelim inary screening calculations were used in conjunction with the potential settlement evaluation, Section 2.5.4.8, to identify potential areas of excessive settlement, either at the buildings or along the pipeline.The second phase of the evaluation consisted of making rigorous piping analyses at the potential areas of excessive settlement. There were three areas along the pipeline with apparent problems that were modeled into the TPIPE piping analysis program. These areas were modeled for a distance on both sides of the potential high settlement area. The areas that were modeled were: (1) from the intake pump station to boring SS-131; (2) from boring SS-141 to boring SS-90; and (3) from boring SS-163 to boring

SS-159.At these areas the potential settlements were used as input in the phase II analysis to give the most conservative results. In all cases, the stress levels are below the ASME Code allowable for settlement induced loads (Reference 1977 ASME Code).

Y max ML 232EI-----------

-=iM Z------3.0 S C iM Z------3.0 S C S A+ S A=allowable stress for expansion 3.7-50SEISMIC DESIGN WATTS BARWBNP-110Cement-mortar lined carbon steel pipe is used in the buried portion of the ERCW yard piping system. The reason for the mortar lining is given in Section 9.2.1.6. The seismic qualification of the cement-mortar lining is provided by testing. This testing is described below.A full-scale testing program consisting of laboratory tests, field tests, and vibration measurements was conducted for seismic qualification of the cement-mortar lined carbon steel pipes. A total of 100 feet of 30-inch diameter pipe, 20 feet of 18-inch diameter pipe, and a 90-degree elbow of 30-inch diameter were lined. Pipe sections tested were: one 30-foot pipe of 30-inch diameter, one 40-foot pipe of 30-inch diameter, one 90-degree elbow of 30-inch diameter with a 5-foot pipe welded to each end, 14 two-foot sections of 30-inch diameter, and 10 two-foot sections of 18-inch diameter. Cement-mortar samples were taken from the mixer before lining application began. Density and moisture content tests were performed on the compacted backfill material surrounding the pipe for field tests. Lining materials and procedures were conforming to American Water Works Association Standard C602-76, 'Cement-Mortar Lining of Water Pipelines - 4 Inches and Larger - In Place.'Cement-mortar specimens were tested for compressive, tensile, and flexural strength, modulus of elasticity, and density. The two-foot pipe sections were subjected to three-edge-bearing, cyclic loading, torsion, drop, and impact tests. The 30-foot pipe was subjected to bending, cyclic loading, and drop tests. The 90-degree elbow was subjected to bending tests. The 40-foot pipe was installed in a trench and after backfilling it was subjected to a dynamic loading of 36,000 pounds at 28 hertz (Hz) from a vibratory roller with a smooth drum of 60-inch diameter by 84-inch width. Two accelerometers were mounted on two of the 30 inch pipes to monitor vibrations experienced by the pipes during the 100-mile trip from the Phipps Bend construction site near Kingsport, Tennessee, to Singleton Materials Engineering Laboratory near Knoxville, Tennessee. The vibrations of the 30 foot pipe (bottom) and a two-foot section (top) were measured and recorded on tape for later analyses. It was expected that the difference in dimension and difference in physical location of the pipes would result in different vibration magnitudes and frequency contents. Comparison between the recorded vibrations and the design earthquake was also made.The acceleration time histories and their corresponding Fourier amplitude spectra at certain high acceleration locations on the record were processed. The acceleration time histories are recorded data and the Fourier amplitude spectra are calculated from the recorded data. This transform of data from time domain to frequency domain reveals the frequency content of the vibration data. The maximum acceleration experienced by the bottom pipe (30 feet long) was 0.6g and that experienced by the top pipe (two-foot section) was 2.1g.

Both values are higher than the SSE accelerations for the design of TVA nuclear plants. The recorded maximum peak-to-peak accelerations were 1.2 g and 3.8 g, respectively. Dominant frequencies ranged from 15 to 70 Hz, mostly concentrated in the range of 15 to 50 Hz.For most large earthquakes the dominant frequencies are in the range of 0.5 to 10 Hz. Lower frequencies indicate that a buried pipe would experience less number of cycles SEISMIC DESIGN 3.7-51WATTS BARWBNP-110of vibration during real earthquakes. Since a pipe has to move with its surrounding soil, vibration amplification due to structure properties is minimal.No crack due to vibration was found in any of the lining after unloading. It is concluded that the linings had experienced more severe vibrations than any recorded earthquakes in terms of magnitude and number of cycles. The vibration measurements were considered as effective as shaking table tests.The three-edge-bearing tests showed that the cement-mortar linings were flexible. The lining underwent considerable cracking prior to separation and falling of the linings. Linings only fell after the formation of the plastic hinges in the steel.The testing program covers a much broader range in types of loading than earthquake loadings. They simulated dead load (loading from roller without vibration, three-edge-bearing test, torsion, and bending tests), low frequency load (cycle tests), large dynamic load at 28 Hz (loading from roller with vibration), large acceleration load with a major frequency content of 0-100 Hz (vibration measurements during shipping), line load with very short duration (drop test), and point load with very short duration (impact test).From these tests, it is concluded that the test loadings applied to the cement-mortar lining were much more severe and broad-ranged than the design seismic loadings.

Therefore, the cement-mortar lining in the underground ERCW pipes is seismically qualified.

3.7.3.13 Interaction of Other Pipi ng with Seismic Category I PipingThe analysis of a Category I piping system may be terminated at the interface of a nonnuclear safety class piping run by either of the following methods.

(1)Terminate the analysis at an in-line anchor designed to prevent transfer of rotations and deflections. The design of the anchor will be sufficient to accommodate reactions from all adjacent piping runs.

(2)Extend the analysis and support of the Category I system far enough into the nonnuclear safety class system to ensure that the effects of this adjacent system have been imposed on the Category I system.Normally, a valve serves as a seismic-nonseismic boundary in a fluid system. The valve capability to maintain a pressure boundary in the event of a seismic event is assured by seismically designing piping on the nonclassified side as described above.

3.7.3.14 Seismic Analyses for Fuel Elements, Control Rod Assemblies, Control Rod Drives, and R eactor InternalsFuel assembly component stresses induced by horizontal seismic disturbances are analyzed through the use of finite element computer modeling. The time history floor response based on a standard seismic time history normalized to SSE levels is used as the seismic input. The reactor internals and the fuel assemblies are modeled as spring and lumped mass systems or beam elements. The seismic response of the fuel 3.7-52SEISMIC DESIGN WATTS BARWBNP-110assemblies is analyzed to determine design adequacy. A detailed discussion of the analyses performed for typical fuel assemblies is contained in References [7] and [9].The Control Rod Drive Mechanisms (CRDM) are seismically analyzed to confirm that system stresses under seismic conditions do not exceed allowable levels as defined by the ASME Boiler and Pressure Vessel Code Section III for 'upset' and 'faulted' conditions. Based on these stress criteria, the allowable seismic stresses in terms of bending moments in the structure are de termined. The CRDM is mathematically modeled as a system of lumped and distributed masses. The model is analyzed under appropriate seismic excitation, and the resultant seismic bending moments along the length of the CRDM are calculated. These values are then compared to the allowable seismic bending moments for the equipment, to ensure adequacy of the design.The seismic qualification of Watts Bar reactor vessel internals is demonstrated using a generic basis for a four loop plant. The generic basis or analysis consists of generic design response spectra and generic reactor vessel supports which envelope the analogous specific Watts Bar values.The generic seismic analysis of the reactor internals is conducted in accordance with the guidelines specified in Regulatory Guide 1.92. The seismic analysis determines the response of the reactor internals to OBE and SSE vertical and horizontal seismic shock components. The horizontal and vertical seismic analysis use the modal response spectrum method and the WECAN general purpose finite element program to determine the internals response. The method used to obtain the combined response of the modal spectral responses is square-root-of-the-sum-of-the squares (SRSS).The effect of closely spaced modes is considered using the Ten Percent Method (Regulatory Guide 1.92, Paragraph 1.2.2); however, the effect has been shown to be insignificant. The maximum or total seismic response value of the reactor internals is obtained by taking the SRSS of the maximum values of the co-directional responses due to the three components of earthquake motion. In general, this combination is made in the Stress Analysis section of the particular structural component.When appropriate (e.g., simple beam analysis) LOCA and SSE loads are combined on a reactor internals structural component basis per the SRSS method, the resultant stress intensities calculated. For more complex structural geometries (e.g., core barrel shell) the stress components due to LOCA and SSE are combined either by absolute sum or SRSS, preserving the appropriate signs. These stress components are used to determine the stress intensity for the structural component. For the LOCA, the maximum stresses from the time history response are used. Since the seismic stresses are calculated using response spectrum techniques, the responses are unsigned; therefore, when the LOCA and SSE stresses are combined, the most unfavorable sign convention for the SSE is assumed. Th e horizontal and vertical seismic models contain 118 and 27 active dynamic degrees of freedom, respectively. Results from the modal analysis of the horizontal and vertical systems indicates, in general, 17 and 3 modes present with frequencies less than 33 Hz.

SEISMIC DESIGN 3.7-53WATTS BARWBNP-110In developing the seismic model of the reactor vessel and internals, a systematic approach was used to ensure that basic fundamental frequencies, i.e., both component and system frequencies are described and inherent in the mathematical models. The approach used to verify the mathematical modeling of reactor vessel and internals was to compare and require that the system frequencies and mode shapes from the mathematical models to be in agreement with plant test and scale model test data.In determining the seismic response of the reactor system due to the excitation of unidirectional shock spectrum, those modes contributing to the first 80-90% of total system mass was considered in the solution.Hydrodynamic mass effects, for both horizontal and vertical directions, was included in the reactor vessel-internals system models. The numerical values for the various hydrodynamic masses effects within the reactor system is based on scale model and plant tests and applicable analytical expressions, e.g., Fritz, Fritz & Kiss, etc.The effect of significant nonlinearities in the reactor system, i.e., gaps between reactor vessel and internals on the seismic response is considered in the system analysis. The nonlinearities due to the gaps are included by determining an effective stiffness at the gap location. The validity of this approach has been investigated and found to be conservative for the frequency response range of the reactor internals.The structural damping values used in the system seismic analysis are in accordance with Regulatory Guide 1.61; i.e., 2 and 4 percent for OBE and SSE, respectively.In addition, the stiffness of the primary piping and the stiffness of reactor vessel supports are considered in the analysis. Coupling effects between the horizontal and vertical directions are insignificant and are not considered in the analysis. The frequency response for the Watts Bar reactor vessel internals system is enveloped by the frequency response of the four loop reactor internals which uses the generic vessel support stiffness. The generic frequency response of four loop reactor internals results in acceleration values on the generic response spectra curve. The generic spectra envelopes the specific Watts Bar spectra by a considerable margin and therefore, the loads for the four loop generic analysis envelope the loads for Watts Bar. Consequently, seismic qualification of the Watts Bar reactor internals is demonstrated since the four loop reactor internals have been qualified on a generic basis.

3.7.3.15 Analysis Procedure for DampingThe specific percentages of critical damping value used for Category I structures, systems, and components are provided in Tables 3.7-2 and 3.7-24.

3.7.3.16 Seismic Analysis and Qualificat ion of Category I Equipment Other Than NSSSAll seismic Category I floor or wall-mounted mechanical and electrical equipment was analyzed or tested and designed to withstand seismic loadings in the horizontal and vertical directions. The floor response spectra obtained from the analysis of structures 3.7-54SEISMIC DESIGN WATTS BARWBNP-110were used in the analyses. Each procurement specification for equipment contained the particular floor response spectra curve for the floor on which the equipment is located. Depending on the relative rigidity and/or the complexity of the equipment being analyzed, the vendor could use one of the following four methods to qualify the equipment:

(1)Dynamic analysis method, (2)Simplified dynamic analysis method, (3)Equivalent static load method, (4)Testing method.The basis used for selection of the appropriate accelerations used in the above paragraph is described in further detail in Section 3.7.3.16.2. Table 3.7-25 identifies how each Seismic Category I item was qualified.Equipment is considered to be rigid for seismic design if the first natural frequency is equal to or more than 33 cycles per second.The Watts Bar Category I electrical and mechanical equipment seismic qualification program is consistent with the guidance provided by the NRC Standard Review Plan (NUREG-0800), Revision 2, July 1981, Section 3.10, acceptance criteria for plants with Construction Permit applications docketed before October 27, 1972. The equipment has been seismically qualified either in direct co mpliance with IEEE Std. 344-1975/Regulatory Guide 1.100 (equipment procured after September 1, 1974), or in accordance with a program which provided as a minimum, qualification to the requirements of IEEE 344-1971 and in addition addressed the guidelines of SRP 3.10.

3.7.3.16.1 Dynamic An alysis Method For Equi pment and ComponentsEquipment that is rigid and rigidly attached to its support structure was analyzed for a g-loading equal to the acceleration of the supporting structure at the appropriate elevation.For nonrigid, structurally simple equipment, the dynamic model consisted of one mass and one spring. Keeping the values of the mass and the spring constant, the natural period of the equipment was determined. The natural period, together with the appropriate damping value, was used to enter the appropriate acceleration response spectrum to obtain the equipment acceleration in units of g's. The corresponding inertia force was obtained by multiplying the weight times the acceleration.If the equipment is structurally complex to the extent that a single-degree-of-freedom- system model does not adequately represent the action of the structure to dynamic loads, then a multi-degree-of-freedom model was used with a complete multi-degree- of-freedom analysis. Enough modes were considered to adequately represent the response of the equipment.

SEISMIC DESIGN 3.7-55WATTS BARWBNP-110 3.7.3.16.2 Simplified Dy namic Analysis Method For Equipment and ComponentsIn the simplified dynamic analysis method, the acceleration value corresponding to the maximum shown on the response spectrum curve is used in qualifying the equipment. The forces on the equipment are determined by multiplying the equipment weight times the acceleration. This provides an acceptable method of analysis providing one of the following criteria is met:

(1)The item of equipment is simple enough to be adequately modeled by a simple one-degree-of-freedom spring-mass system.

(2)The item of equipment is not simple but its fundamental frequency is greater than the rigid frequency. The rigid frequency is defined as that frequency of the floor response spectrum above which there is no acceleration amplification.

(3)The item of equipment is not simple and its fundamental frequency is lower than the rigid frequency but its other frequencies are higher than the rigid frequency.If the equipment can be shown to meet one of these criteria, any amplification due to internal dynamics will not cause stresses greater than those obtained by using the peak value of the floor response spectrum. All of the equipment listed in Table 3.7-25 as having been analyzed by the simplified dynamic analysis method has been reviewed to verify that it meets one of these criteria.The method described above is conservative since the maximum acceleration, regardless of the frequency of the equipment, is used.3.7.3.16.3 Equivalent Static Load MethodThe description of equivalent load method and its applicability are detailed in Section3.7.3.5.

3.7.3.16.4 Testing MethodEquipment that did not lend itself to mathematical modeling and structural analysis to determine no loss of function was evaluated by actual vibration testing. The seismic qualification of mechanical equipment, instrumentation and electric equipment are described in Sections 3.9 and 3.10, respectively.

3.7.3.16.5 Equipment and Com ponent Mounting ConsiderationsSeismic loads for vendor-supplied floor or wall mounted Category I equipment and fluid system component (equipment/component) assemblies and their TVA-designed supports and/or anchorages are determined with consideration of the damping values and stiffness of each. Damping values for these equipment/component assemblies and their bolted or welded structural steel supports and/or anchorages are as indicated in Table 3.7-2. Most of the TVA-designed supports and/or anchorages are effectively rigid; e.g., they do not result in significant amplification of the building structure seismic 3.7-56SEISMIC DESIGN WATTS BARWBNP-110input. When a TVA-designed support and/or anchorage is not effectively rigid a coupled analysis of the equipment and/or component assembly and its support and/or anchorage is performed using composite modal damping response spectrum analysis techniques.Examples of vendor-supplied floor or wall mounted mechanical equipment/ component assemblies include: tanks, heat exchangers, diesel generator sets, air handling units, chiller units, compressor assemblies, fan assemblies, and pumps. Electrical equipment assemblies include: transformers, battery racks, instruments and control (I/C) cabinets, I/C panels, and I/C racks.Seismic loads for line-mounted Category I equipment/components and their mountings are determined from analysis of the subsystems on which they are mounted. The line-mounted equipment/component is tested or analyzed using device qualification techniques as described in Section 3.7.3.6.3. Mass and stiffness characteristics of the equipment/components are included in the subsystem analysis when significant to its seismic response. For example, Section 3.7.3.11.1 describes the modeling of valves in Category I piping subsystems. The subsystem response at the equipment/component location is kept below the device qualification level of the equipment/component. Local mounting brackets for line-mounted equipment/components are seismically qualified with the equipment/component (as part of the device) or they are designed to be effectively rigid. In this case, effectively rigid means the local mounting brackets do not result in significant amplification of the seismic input from the subsystem. Examples of line-mounted mechanical and electrical equipment/components include: valves, HVAC dampers, and locally-mounted I/C devices of all types.The techniques described in this section ensure compatibility of the seismic loads for qualification of the Category I equipment/components and the predicted seismic responses of structures and subsystems to which they are mounted.

3.7.3.17 Seismic Analysis and Design of HVAC Duct and Duct Support SystemsThis section addresses the analysis and design of Category I and I(L) (see Sections 3.2.1 and 3.2.2.7) HVAC duct and duct support subsystems.3.7.3.17.1 Description of HVAC Duct and Du ct Support SubsystemsHVAC duct and duct support subsystems consist of continuous runs of round and rectangular sheet metal ducts multiple supported along their lengths by structural steel support frames or rod hangers. Scheduled pipe and pipe supports functionally used for an HVAC purpose are treated as piping subsystems in accordance with Section 3.9.For purpose of analysis, an HVAC duct and duct support subsystem is regarded as any continuous portion of a total duct run and its supports which may be conservatively modeled for evaluation of the loads and stresses within the portion of interest. Significant mass and mass eccentricities of in-line or attached mechanical and electrical components are accounted for in the subsystem model to represent their SEISMIC DESIGN 3.7-57WATTS BARWBNP-110effects in structural qualifications of the ducts and duct supports in accordance with Sections 3.7.3.17.2 through 3.7.3.17.6. Qualification of the in-line or attached Category I mechanical or electrical equipment and components are in accordance with Sections 3.7.3.6, 3.7.3.16.5, 3.9, and 3.10.3.7.3.17.2 Applicable Codes, Standards, and SpecificationsThe following codes, standards, and specifications are applicable to various portions of the HVAC duct and duct support subsystems:

(1)SMACNA High Velocity Duct Construction Standards, 2nd Edition, 1969 (2)ANSI/ASME N-509 Standard, "Nuclear Power Plant Air Cleaning Units and Components," 1976 (3)ASTM Standards (4)AISI Specifications for the Design of Cold-Formed Steel Structural Members, 1986 Edition (5)AISC Specifications for the Design, Fabrication, and Erection of Structural Steel for Buildings, 7th and 8th Editions except welded construction is in accordance with Item 7 below.

(6)Manufacturer's Standardization Society of the Valve and Fittings Industry, Standard Practice MSS-SP-58, "Pipe Hangers and Supports - Materials and Design," 1967 Edition (7)American Welding Society, AWS D1.1 Structural Welding Code (See Section 3.8.1.2, Item 4)

(8)American Welding Society, AWS D1.3 Structural Welding Code for Sheet Metal (9)American Welding Society, AWS D9.1 Specifications for Welding Code for Sheet Metal (10)NRC Regulatory Guide 1.52, "Design, Testing, and Maintenance Criteria for Post Accident Engineered-Safety-Feature Atmosphere Cleanup System Air Filtration and Adsorption Units of Light-Water-Cooled Nuclear Power Plants," Revision 2.

3.7.3.17.3 Loads a nd Load CombinationsHVAC duct and duct support subsystems are designed for the following loads:DL- Dead loadsOBE- Operating basis earthquake loads SSE- Safe shutdown earthquake loads 3.7-58SEISMIC DESIGN WATTS BARWBNP-110 T o- Thermal effects and loads during normal operating or shutdown conditions based on the most critical transient or steady-state conditions T a- Time varying thermal loads under conditions generated by the design basis accident condition and including T oNote: The maximum value of T a need not be considered simultaneously with the DBA if time phasing evaluation shows that less than T a maximum occurs during the DBA transient.

P o- Operating pressure in the duct P j- Accident pressure external to the duct due to jet impingement loads from a pipe break. The ducts shall be protected against possible P j loadings; therefore, this load need not be considered.

P a- Compartmental pressure loads resulting from a design basis accidentDBA- Design basis accident dynamic loads due to pressure transient responseF - Airflow induced dynamic loads acting on turning vanes inside the ducts (dependent on the mean airflow velocity)These loads are considered in the following combinations for the duct and duct support elements of the subsystems:3.7.3.17.4 Analysis and Design ProceduresExisting HVAC duct and duct support subsystems that were originally analyzed and designed to Set A seismic response spectra are reevaluated to Set B response spectra as the basis for their qualification. New designs and modification designs to existing subsystems are based on the envelope of Set B+C response spectra.

3.7.3.17.5 Structural Acceptance CriteriaThe various elements of the HVAC duct and duct support subsystems are qualified for structural acceptance based on allowable stress criteria.Allowable stresses for the duct supports are specified in Table 3.7-26.

Allowable stresses for the ducts involve a number of specialized considerations to address both overall and local stresses. Overall stress allowables for duct plate DuctsDuct Support(1)DL + P o + F + OBE(1) DL + OBE(2)DL + P o + T o + F + OBE(2) DL + T o + OBE(3)DL + P o + T o + F + SSE(3) DL + T o + SSE(4)DL + P o + T a + F + OBE + DBA + P a (4) DL + T a + OBE + DBA(5)DL + P o + T a + F + SSE + DBA + P a (5) DL + T a + SSE + DBA SEISMIC DESIGN 3.7-59WATTS BARWBNP-110(membrane) elements are developed based on AISI equations. These equations are modified where necessary to adjust for large height-to-thickness and width-to-thickness ratios beyond the normal AISI limits. These adjustments are based on correlations to results of testing, large displacement finite element analyses, and/or industry literature. Additional specialized considerations are made for local stress evaluations. Stress evaluations of the duct stiffeners (including companion-angles) and bolting between these stiffeners are based on AISC allowables. Stress evaluations of the tinners rivets connecting the companion-angles to the duct plate are based on correlation to test results.In general, unfactored duct stress allowables are used in evaluations of loading combination (1). These stress allowables are multiplied by 1.5 in evaluations of loading combinations (2), (3), (4), and (5). Critical elements of the duct necessary to maintain overall cross section stability are limited to 0.90 F y except shear is limited to 0.52 F y and buckling is limited to 0.90 F cr. Local plate stresses are maintained within 0.90 F y for mid-plane membrane stresses although surface stresses may exceed yield. The effective cross section of a duct is evaluated based on the post-buckled membrane strength of the duct panels between stiffeners.

3.7.3.17.6 Materials and Quality ControlSome HVAC sheet metal materials installed prior to March 1990 were not always specified and controlled sufficiently to assure known mechanical properties. Samples of these materials were taken from the installed ducts and tested to determine their mechanical properties. The following mechanical properties are used for designs with these materials:HVAC duct sheet metal materials specified after March 1990 and the associated mechanical properties used for designs are as follows:Duct Construction TypeYield Strength, F yTensile Strength, F uSMACNA rectangular (ASTM A525/A527 galvanized sheet)33 ksi45 ksiSpecially formed round or rectangular welded (ASTM A570 sheet)30 ksi49 ksiSpiral-welded pipe (ASTM A211) 30 ksi40 ksiSMACNA round spiral-lockor longitudinal-lock 20 ksi37 ksi 3.7-60SEISMIC DESIGN WATTS BARWBNP-110HVAC structural steel supports are fabricated of ASTM A36 or equivalent or stronger material and are evaluated as having mechanical properties of F y=36 ksi and F u=58 ksi.All steel materials used in the fabrication of HVAC ducts and duct supports are evaluated with a Young's Modulus of E=29 x 10 3 ksi except for those areas within the Reactor Building where reductions must be taken due to extreme accident thermal

conditions.

3.7.3.18 Seismic Qualificat ion of Main Control Room Suspended Ceiling and Air Delivery Components Flexible ducting, triangular ducts, and air bar linear diffusers deliver air flow from the sheet metal ducts located above the Main Control Room (MCR) suspended ceiling to the air space below the ceiling. These air delivery components have been seismically qualified to ensure position retention and structural integrity such that pressure boundary and air flow delivery is maintained during and after the Safe Shutdown Eathquake (SSE). Seismic qualification of the suspended ceiling and the air delivery components has been accomplished by rigorous time history analysis using the ANSYS computer code. The analysis models non-linear reponse due to gaps, friction, ceiling support wires, and geometric effects of the ceiling grid work. The seismic time histories correspond to the Control Building response to the Set B SSE at the floor elevation above the suspended ceiling. The combined time histories were then adjusted to account for +

15 percent frequency uncertainty. A factor of safety of at least 1.3 for seismic qualification of the ceiling and air delivery components was demonstrated by increasing the time history motions by 30 percent and verifying that the seismic demand is less than the capacity of the ceiling grid members (including air bars), support wires, and flexible and triangular ducts. The ceiling grid member and support wire capacities are based on classical structural analysis formulas. The flexible and triangular duct capacities were based on analysis for potential failure modes, industry precedents, and the analytical determination that the ceiling grid work remains stable. Other suspended ceiling components, including luminous panels, were shown to retain their position during and after the SSE. Specified MaterialYield Strength, F yTensile Strength, F uASTM A527 galvanized steel sheet with ASTM A446 Grade A (minimum) base metal 33 ksi45 ksiASTM A570 Grade 30 (minimum) steel sheet (also used for ASTM A211 spiral-welded pipe)30 ksi49 ksi SEISMIC DESIGN 3.7-61WATTS BARWBNP-110 3.7.4 Seismic Instrumentation ProgramSeismic instrumentation is provided in order to assess the effects on the plant of earthquakes which may cause exceedance of the Operating Basis Earthquake (OBE=0.09g horizontal and 0.06g vertical ground acceleration). The seismic monitoring system (SMS) is not safety-related, nor does it have any effect on safety-related systems or components. The components of the SMS are selected to emphasize accuracy and reliability. The Instrumentation program is described in the following subsections. 3.7.4.1 Comparison with Regulatory Guide 1.12The instrumentation is described in Section 3.7.4.2 below and meets the requirements of Regulatory Guide 1.12., Rev 1.3.7.4.2 Location and Descri ption of InstrumentationThe seismic instrumentation locations are shown in Figures 3.7-39 through 3.7-45.Instrumentation consists of the following:

(1)A strong motion triaxial accelerometer at each of the following locations: (a)Elevation 702.78, Unit 1 Reactor Building, on the floor slab in the annulus between the Shield Building and the Steel Containment Vessel as shown in Figure 3.7-39.(b)Elevation 756.63, Unit 1 Reactor Building, on the floor slab as shown in Figure 3.7-40.(c)Elevation 742.0, Diesel Generator Building, on the base slab as shown in Figure 3.7-41.These accelerometers are connected to digital recorders (See Item 3). The recording system is located in the Control Building. The full scale range of the transducers is 0 to 1.0g with a bandwidth of 0 Hz to 50 Hz and a temperature effect of less than 2% per 100°F change (2)A triaxial strong motion accelerograph with a range of 0g to 2g at Elevation 757 in the Auxiliary Building contains an internal. battery backup and is capable of digitally recording a minimum of 25 minutes of data with a minimum of 3 seconds of pre-event memory. An internal seismic trigger with a bandwidth of 0.1 to 12.5 Hz actuates the recording system when a threshold acceleration level is sensed.

3.7-62SEISMIC DESIGN WATTS BARWBNP-110 (3)A seismic instrumentation panel board located at Elevation 708 in the Control Building as shown in Figure 3.7-42. The panel board houses a centralized SMS consisting of a recorder panel, a central controller assembly, a display panel, an alarm panel, and a printer panel. A description of each item mounted on the panel board is given below. (a)Two recorder panels containing a total of three digital recorders capable of 18-bit resolution. The three strong motion accelerometers of Items 1a, 1b, and 1c above provide input to the recorders. Each digital recorder contains three channels and is capable of recording a minimum of 25 minutes of data with a minimum of 3 seconds of pre-event memory. Each recorder has an internal trigger with a bandwith of 0.1 to 12.5 Hz which constantly monitors its interconnected triaxial accelerometer. When one of the recorders senses a seismic event, an interconnected network causes the other recorders to trigger and record data at the same time to ensure time-synchronized event-data files. The trigger threshold is set to initiate recording when the acceleration at the containment foundation exceeds 0.01g. A signal is also sent to the alarm panel to indicate that the system is recording (See Item 3c). The recorders can operate for up to 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> on internal batteries. (b)A central controller consisting of an industrial computer and custom software which provides a user interface in a multi-task operating system that supports simultaneous acquisition and interrogation. That controller is powered by 120V AC power. The central controller retrieves data files from the digital recorders after an event and performs automatic analysis on the data. The event analysis capabilities include calculation of the spectral content of the recorded data and comparison to the site OBE design basis response spectrum. The results of the analysis are displayed on the LCD display panel, sent to a printer, and saved to disk for later off-line analysis. The central controller's software capabilities also include automatic event alarm and annunciation, as well as configurable built in tests of the components comprising the centralized system. (c)An alarm panel containing visual alarms to locally indicate that a seismic event has been recorded, that the OBE site design response spectrum has been exceeded in a damaging frequency range, and to indicate either loss of AC or DC power. The seismic event alarm is triggered by the recorder panels; while the OBE exceedance alarm (See Item 4) is triggered by the cental controller. Activation of either SEISMIC DESIGN 3.7-63WATTS BARWBNP-110event alarm or exceedance alarm also causes corresponding windows on an annuciator panel in the Main Control Room to illuminate.(d)A display panel to provide a visual display for operation of the centralized system. (e)A printer panel to provide a permanent copy of operational data and event analysis results.

(4)Annunciator lights mounted on a window box located on Panel 1-M-15, Main Control Room, Control Building, as shown by reference in Figure 3.7-43. The messages displayed on the annunciator windows in the Main Control Room are 'Seismic Recording Initiated,' 'OBE Spectra Exceeded,' and 'Seismic Instrumentation Loss of Power.' The basis for the selection of the Reactor Building for installation of seismic instrumentation is that it is the rock-supported building most important to safety. The basis for the selection of the Diesel Generator Building is that it is the soil-supported building most important to safety. The basis for the selection of the Auxiliary Building is that it is a rock-supported structure outside containment.Steps for utilization of the data recorded by the above described instrumentation are provided in Sections 3.7.4.4 and 3.7.4.5 below.

3.7.4.3 Control Room Operator NotificationThe operator receives three annunciation signals in the Main Control Room. These annunciations are independent of each other. The first annuncia tion is 'Seismic Instrumentation Loss of Power,' which serves to provide warning of equipment operability problems under normal conditions as well as following a seismic event. The next annunciation is provided by the recorder panel described in Item 3a, Section 3.7.4.2, which informs the operator that a seismic event is being recorded. This annunciation indicates that one of the triggers for the digital recorders sensed seismic motion in excess of 0.01g. The final annuciation signal ('OBE Spectra Exceeded') is recieved later and is provided by the central controller described in Item 3b, Section 3.7.4.2, and is only received if the event-analysis software indicates that the site OBE site design response spectrum has been exceeded in a potentially damaging frequency range, i.e., at any frequency between 2 to 10 Hz, or the design response spectral velocity has been exceeded between 1 to 2 Hz. The basis for establishing the OBE design response spectrum for the levels at which control room operator notification is required is that the design of structures, systems, and components for loading combinations, which include OBE, is to code allowable stress levels which are well within the elastic limit of the materials.

3.7-64SEISMIC DESIGN WATTS BARWBNP-110 3.7.4.4 Controlled Shutdown Logic The operator will utilize input from multiple sources to determine the need for a controlled shutdown following the seismic event. The decision for a controlled shutdown will be based primarily on an assessment of the actual damage potential of the event. The event analysis data from the SMS will be reviewed to confirm the 'OBE Spectra Exceeded' alarm. The operator may also confirm that ground motion was sensed by plant personnel and/or confirm the occurrence of the seismic event with the National Earthquake Center. Walkdowns of key plant structures, systems, and components will be performed following the seismic event. The walkdowns will be performed using the guidance of Reference [26], and will include checks of the neutron flux monitoring sensors and containment isolation system. If the 'OBE Spectra Exceeded' alarm is confirmed by analysis and the event is confirmed by plant personnel, data from these other sources will be used to determine the best manner in which to proceed with plant shutdown. If a seismic event occurs which does not result in an OBE exceedance (as determined either by annunciation or subsequent analysis), a plant walkdown may be performed to confirm plant condition, however plant shutdown will not be required unless it is determined to be necessary by the operator based on consideration of available information. The assessment of the damage potential will be made using the OBE Exceedance Criteria developed by the Electric Power Research Institute (EPRI). [25], [26], [27], [28], [29], and [30] As noted above, the indication of damage potential will be provided by event analysis software installed on the centralized SMS described in Section 3.7.4.2. The analysis will be performed for the uncorrected accelerograms recorded from the strong motion triaxial accelerometer located on the base slab in the annulus of the Unit 1 Reactor Building (Item 1a of Section 3.7.4.2). Use of the uncorrected accelerograms is known to be conservative. The basis for the use of the seismic motion on the base slab of this structure is that the site OBE design response spectrum is defined at top-of-rock, which corresponds to the base slab location. An engineer will confirm the event analysis results from the SMS. The EPRI OBE Exceedance Criteria uses two indicators of damage potential. The first indicator of damage potential is specified as the cumulative absolute velocity (CAV), of the accelegram. A meaningful usage of the CAV requires that the recorded data be obtained by an accelerometer mounted in the free-field. As noted above, the OBE design spectrum for WBN is defined as occurring at top-of-rock (i.e., foundation level of the rock supported structures); whereas, freefield is defined as top-of-soil at sufficient distance from nearby structures to preclude interference/interaction effects. The SMS does not have a free-field accelerometer. Therefore, the shutdown logic adopted will concede CAV exceedance and base the decision on the need for a controlled shutdown solely on the second indicator, as discussed below.In the absence of data from a free-field accelerometer, the second indicator is an evaluation of the frequency at which the OBE spectrum is exceeded. This criterion is based on research indicating that exceedances above a frequency of 10 Hz are not damaging to nuclear plant structures, systems and components. Two measures of damage potential are used for this second indicator. The OBE design response spectrum is considered exceeded if the 5% damped response spectra generated for SEISMIC DESIGN 3.7-65WATTS BARWBNP-110any one of the three components of the uncorrected accelerograms form the Containment Building base slab is larger than:

(1)The corresponding OBE design response spectral acceleration in a frequency range between 2-10 Hz, or, (2)The corresponding OBE design response spectral velocity for frequencies between 1-2 Hz. Basing shutdown logic on the actual damage potential reduces shutdown risk by avoidance of unnecessary shutdowns while ensuring that the operator has the information on plant status necessary to make in informed shutdown decision.3.7.4.5 Comparison of Measured and Predicted Responses The steps to be followed after the initiation of a controlled shutdown due to OBE exceedance are discussed in the following sections.

3.7.4.5.1 Retrieval of Data The digital records for the Reactor Building and Diesel Generator Building accelerometers and the strong motion accelerograph in the Auxiliary Building will be retrieved. The accelerometers and the accelerograph will be recalibrated to confirm the accuracy of the recorded area.

3.7.4.5.2 Evaluation of Recorded Earthquake Corrected accelerograms and corresponding response spectra, will be prepared for event data recorded by the aforementioned accelerometers and accelerograph. The response spectra for the recorded motion at Elevation 757 in the Reactor Building, Elevation 745 in the Diesel Generator Building, and Elevation 757 in the Auxiliary Building will be compared to the corresponding design spectra for the OBE.The structural response of these buildings to the recorded earthquake will be compared with the OBE design structural response, and if less, no further analysis will be required. If the structural response of these buildings to the recorded earthquake is greater than the OBE design structural response, then floor response spectra, for the same mass points in these buildings as used in the equipment design, will be produced for use in evaluation of mechanical and electrical equipment response.REFERENCES (1)'Dynamic Effects of Earthquake on Engineering Structures,' Tennessee Valley Authority, Report No. 8-194, August 1939.

(2)Hayashi, Satoshi, 'Analysis and Design of Earth Structures and Foundations,' Syllabus for Earthquake Engineering Fundamentals, August 22 through September 2, 1966, Engineering Extension, Department of Engineering, University of California, Los Angeles.

3.7-66SEISMIC DESIGN WATTS BARWBNP-110 (3)Whitman, R. V. 'Analysis of Foundation Vibrations,'Vibration in Civil Engineering, 1966, Buttersworth, London.

(4)Sequoyah Nuclear Plant Final Safety Analysis Report, Tennessee Valley Authority, Docket Numbers 50-327 and 50-328.

(5)Richard, F. E., Jr., J. R. Hall, Jr., R. D. Woods, Vibrations of Soils and Foundations, Prentice-Hall, Incorporated, 1970, New Jersey.

(6)N. M. Newmark, 'Design Criteria for Nuclear Reactors Subjected to Earthquake Hazards,' Proceedings, IAEA Panel on Seismic Design and Testing of Nuclear Facilities, Japan Earthquake Engineering Promotion Society, Tokyo, May 1967.

(7)T. L. Gesinski, 'Fuel Assembly Safety Analysis For Combined Seismic and Loss-of-Coolant Accident,' WCAP-7950, July 1972.

(8)E. L. Vogeding, 'Seismic Testing of Electrical and Control Equipment,' WCAP-7817, and Supplement I, December 1971.

(9)Gessinki, L. and D. Chaing, 'Safety Analysis of the 17x17 Fuel Assembly for Combined Seismic and Loss-of-Coolant Accident', WCAP-8288, January1974.

(10)Nuclear Regulatory Commission (NRC) Regulatory Guide 1.60, December 1973.(11)Nuclear Regulatory Commission (NRC)

Regulatory Guide 1.61, October 1973.(12)Nuclear Regulatory Commission (NRC) Regulatory Guide 1.92, February1976.

(13)Nuclear Regulatory Commission (NRC) Regulatory Guide 1.84, Revision 25, May 1988.(14)Deleted (15)Newmark, N.M., "Problems in Wave Propagation in Soil and Rock," Proceeding International Symposium on Wave Propagation and Dynamic Properties of Earth Materials, Albuquerque, New Mexico, 1968.

(16)Newmark, N.M., "Earthquake Response Analysis of Reactor Structures," Nuclear Engineering and Design, Volume 20, 1972, pages 303-322.

(17)Kuesel, T.T., "Earthquake Design Criteria for Subways," ASCE, Journal of the Structural Division, Vol. 95, No. ST6, Proceeding Paper 6616, June 1969, pages 1213-1231.

SEISMIC DESIGN 3.7-67WATTS BARWBNP-110 (18)Yeh, G.C.K., "Seismic Analysis of Slender Buried Beams," Bulletin of the Seismological Society of America, Volume 64, No. 5, October 1974, pages 1551-1562.

(19)Shah, H.H., and Chu, S.L., "Seismic Analysis of Underground Structural Elements," ASCE, Journal of the Power Division, Vol. 100, No. P01, Proceeding Paper 10648, July 1974, pages 53-62.

(20)Goodling, E.C., "Flexibility Analysis of Buried Piping," Joint ASME/CSME Pressure Vessels and Piping Conference, Montreal, Canada, June25-30,1978.

(21)Goodling, E.C., "Buried Piping - An Analysis Procedure Update," International Symposium on Lifeline Earthquake Engineering, Fourth U.S. National Conference on Pressure Vessels and Piping Technology, ASME, Portland, OR, 1983.

(22)Goodling, E.C., "Seismic Stresses in Buried Elbows," ASCE National Convention, Boston, MA, 1979.

(23)"Seismic Response of Buried Pipes and Structural Components," ASCE Structural Division Committee on Nuclear Structures and Materials, ASCE, New York, NY, 1983.

(24)Iqbal, M.A. and Goodling, E.C., "Seismic Design of Buried Piping," Second ASCE Specialty Conference of Structural Design of Nuclear Plant Facilities, New Orleans, LA, 1975.

(25)EPRI Report NP-5930, "A Criterion for Determining Exceedance of the Operating Basis Earthquake," July 1988.

(26)EPRI Report NP-6695, "Guidelines for Nuclear Plant Response to an Earthquake," December 1989.

(27)EPRI Report TR-100082, "Standardization of the Cumulative Absolute Velocity," December 1991.

(28)EPRI Report TR-104239, "Seismic Instrumentation in Nuclear Power Plants for Response to OBE Exceedance: Guideline for Implementation" June 1994.

(29)NRC Memorandum from Stuart A. Treby, OGC, to Goutam Bagchi, NRR, concerning "Interpretation of Part 100, Appendix A Regarding: Proposed Guidelines for Determining when Operating Basis Earhtquake is Exceeded," dated May 3, 1988.

(30)Nuclear Regulatory Commission Regulatory Guide 1.166, "Pre-Earthquake Planning and Immediate Nuclear Power Plant Operator Post-earthquake Actions," March 1997.

3.7-68SEISMIC DESIGN WATTS BARWBNP-110NOTES:(1) Spectral values were computed for the periods/frequencies shown above in addition to the natural frequencies of the structure.(2) Except for the Auxiliary-Control Building where Set A periods were used in Set C analysis.Table 3.7-1 Periods for Spectral Values (1)SET ARange of Periods, T (sec)Increment, T (sec)0.03 to 0.100.11 to 0.300.32 to 0.500.55 to 1.00.0050.0100.0200.050SET B AND SET C (2)FrequencyRange(hertz)Increment(hertz)0.2 - 3.03.0 - 3.6 3.6 - 5.05.0 - 8.08.0 - 15.0 15.0 - 18.0 18.0 - 22.0 22.0 - 34.0.10.15

.20.25.50 1.0 2.0 3.0 SEISMIC DESIGN 3.7-69WATTS BARWBNP-110 Notes:(1) Damping value of 7% may be used when stress levels are at or near yield.(2) Damping value of 5% may be used when stress levels are at or near yield.(3) Not addressed.(4) Includes TVA-designed supports and anchorage for equipment and component assemblies.

(5) Design is based on SSE only.(6) OBE loads are assumed to be 1/2 of SSE loads.(7) N-411-1--Damping values from ASME Code Case N-411-1.

(8) For Set B, OBE and SSE are site-specific OBE and SSE Table 3.7-2 Structural Damping Ratios Used In Analysis of Category I Structures, Systems and ComponentsCATEGORY I STRUCTURES Set A OBE SSE Set B(8) OBE SSE Set C OBE SSEReactor Building - Interior Concrete Structure Steel Containment Vessel Shield Building 2 1 2 5 (1) 1 5 (1)4 2

4 7 4 7 2 1 2 5(1) 1 5(1)Additional Diesel Generator BldgN/A N/A475 5Other Concrete Structures5 5 (1)475 5(1)Refueling Water Storage Tank22242 2 Other Welded Steel Structures (4)2 2 (2)242 2 (2)Other Bolted Steel Structures(4)5 5 (1)475 5(1)CATEGORY I SYSTEMS AND COMPONENTS Set A OBE SSE SET B(8) OBE SSE Set B+C OBE SSEPiping - 12" or Larger Less than 12" Optional (Code Case) 0.5 0.5 N/A 1 1 N/A 2 1 Note 7 3 2 Note 7 2 1 Note 7 3 2 Note 7Cable Tray454747 ConduitNote 524747 HVAC - Companion Angle Pocket Lock Welded Duct Note 6 Note 6 Note 3 7 7 Note 3 4 7 2 7 7 4 4 7 2 7 7 4Equipment/Components232323 3.7-70SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-2a Deleted SEISMIC DESIGN 3.7-71WATTS BARWBNP-110Table 3.7-2b Deleted 3.7-72SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-3 Supporting Media for Category I Structures Rock-Supported Structures (Set A, Set B, and Set C Analyses) Structure Shear Wave Velocity of Bedrock, fps Shield BuildingInterior Concrete Structure

Auxiliary-Control Building Steel Containment Vessel North Steam Valve Room ERCW Intake Pumping Station590059005900 590059005900Soil-Supported Structures Structure Shear Wave Velocities (fps)

(1) Set A Analysis Set B and Set C Analyses Diesel Generator Building1650Note 2 Waste-Packaging Area1650 N/A Refueling Water Storage Tank1008Note 2 ERCW Pipe Tunnels1150Note 2Pile-Supported Structures Structure Shear Wave Velocities (fps)

(1) Set A Analysis Set B and Set C Analyses Condensate DemineralizerWaste Evaporator Building761N/AAdditional Diesel Generator BuildingN/ANote 2NOTES:(1) Shear wave velocities are defined at zero shear strain.

(2) Shear wave velocities for Set B and Set C analyses are related to the soil layer, overburden, shear strain, etc. See Section 2.5 for a description of the supporting media dynamic soil properties.

SEISMIC DESIGN 3.7-73WATTS BARWBNP-110Table 3.7-4 Shield Building Structural Properties ( Set A )E = 545,000 K/FT 2G = 218,000 K/FT 2 Element No.Length Ft Area Ft 2Moment of Inertia. Ft 4Mass Pt.No.WeightKips 1 6.6711942435 x 10 3 1 789.83 2 2.2711942435 x 10 3 2 556.11 3 4.0611942435 x 10 3 3 710.40 4 4.0611742435 x 10 3 4 704.40 5 4.0611742398 x 10 3 5 710.40 6 4.0611942398 x 10 6 6 974.30 7 6.9211942435 x 10 3 71590.40 810.8811942435 x 10 3 81298.50 9 3.6211942435 x 10 3 9 648.3410 3.6211942435 x 10 310 649.2411 3.6311942435 x 10 311 608.0312 3.3311332202 x 10 312 565.9313 3.3311332202 x 10 313 566.7814 3.4311332202 x 10 314 570.5315 3.4211482250 x 10 315 573.4316 3.4211482250 x 10 316 574.2917 3.4311482250 x 10 317 622.7918 4.2811942435 x 10 318 750.4319 4.2811942435 x 10 319 750.4320 4.2511942435 x 10 3201500.902112.5711942435 x 10 3212251.302212.5711942435 x 10 3222252.202312.5811942435 x 10 3232253.102412.5811942435 x 10 3242253.102512.5811942435 x 10 3256893.50 3.7-74SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-4a Lumped-Mass Model Properties of Shield Building Model (Set B and Set C) (Page 1 of 3)

Elevation (ft)Masses(k-sec 2/ft)Mass Momentof Inertias(10 4xk-ft-sec 2) J z Axial Area(ft 2) A Shear Areas (ft 2)A x = A yMoment of Inertias (10 4 x ft 4) J I xx = I yy 852.1(Note 1)42.521194597487243.5 839.569.9728.521194597487243.5 826.969.9728.521194597487243.5 814.369.9428.521194597487243.5 802.169.9228.521194597487243.5 789.846.6119.011194597487243.5 785.623.31 9.511194597487243.5 781.323.31 9.511194597487243.5 777.019.34 8.391148574450225 773.617.84 7.261148574450225 770.117.81 7.261148574450225 766.717.72 7.231133567440.4220.2 763.317.60 7.16Note 1: Horizontal Mass = 214.1Vertical Mass = 134.3 SEISMIC DESIGN 3.7-75WATTS BARWBNP-1101133567440.4220.2 760.017.58 7.161133567440.4220.0 756.618.88 7.701194597487243.5 753.020.16 8.211194597487243.5 749.420.13 8.211194597487243.5 745.840.3316.451194597487243.5 734.949.3920.151194597487243.5 728.030.2612.341194597487243.5 723.922.06 9.011174587479.6239.8 719.821.88 8.941174587479.6239.8 715.822.06 9.011194597487.6243.5 711.717.27 7.041194597487 243.5 709.524.5310.001194597487 243.5 702.818.30 7.46Table 3.7-4a Lumped-Mass Model Properties of Shield Building Model (Set B and Set C) (Page 2 of 3) 3.7-76SEISMIC DESIGN WATTS BARWBNP-110Dome Vertical SDOF OscillatorMass = 79.81 (k-sec 2/ft)Spring Stiffness = 806 x 10 3 (k/ft)Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio = 0.15+X = EAST

+Y = NORTHTable 3.7-4a Lumped-Mass Model Properties of Shield Building Model (Set B and Set C) (Page 3 of 3)

SEISMIC DESIGN 3.7-77WATTS BARWBNP-110Table 3.7-5 Shield Building Natural PeriodsCYLINDRICAL SHELLDOMETranslation MotionVertical MotionVertical MotionMode No.Period(Seconds)Participation Factor Period(Seconds)Participation Factor Period(Seconds)Participation Factor 10.18681.3260.06711.232 0.063 2.237 20.09510.046 0.040 -2.213 30.05520.580 0.033 1.207 40.03130.008 0.026 -0.676

5 0.020 1.281 SEISMIC DESIGN 3.7-78WATTS BARWBNP-110Table 3.7-5a Steel Containment Vessel Element PropertiesE = 4,176,000 K/Ft 2 G = 1,670,400 K/Ft 2 Element No. Length, Ft Area (Ft 2) TorsionConstant (Ft 4) North-South Motion East-West MotionMoment of Inertia(Ft 4) Shear FactorMoment of Inertia(Ft 4) Shear Factor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 1.00 6.22 6.50 8.00 9.0011.00 9.50 3.50 6.00 4.50 5.00 9.50 9.50 9.50 9.50 3.50 2.5012.00 12.46 9.54 9.00 9.00 3.0041.5545.5545.55 41.5541.5541.55 41.5541.5545.16 45.1645.1645.16 45.1645.1645.16 45.1641.3041.30 41.30 24.4024.5024.46 28.23137 x 10 3152 x 10 3152 x 10 3137 x 10 3137 x 10 3137 x 10 3137 x 10 3137 x 10 3149 x 10 3149 x 10 3149 x 10 3149 x 10 3149 x 10 3149 x 10 3149 x 10 3149 x 10 3137 x 10 3129 x 10 3108 x 10 3456 x 10 2268 x 10 2 81 x 10 2 36 x 1068.7 x 10 375.3 x 10 375.3 x 10 368.7 x 10 368.7 x 10 368.7 x 10 368.7 x 10 368.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 368.3 x 10 364.5 x 10 354.0 x 10 322.8 x 10 313.4 x 10 340.5 x 10 218.2 x 10 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

2 2 2 268.7 x 10 375.3 x 10 375.3 x 10 368.7 x 10 368.7 x 10 368.7 x 10 368.7 x 10 368.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 374.7 x 10 368.3 x 10 364.5 x 10 354.0 x 10 322.8 x 10 313.4 x 10 340.5 x 10 218.2 x 10 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

2 2 2 2

SEISMIC DESIGN 3.7-79WATTS BARWBNP-110 Table 3.7-5b Steel Containment Vessel Mass Point PropertiesElevations, FtTotalHorizontalWeight,Kips TotalVerticalWeight,Kips Weightof Inertia WR 2K-ft2 Eccentricity Used in Dynamic Analysis, Ft 703.78 710.00 716.50 724.50 733.50 744.50 754.00 757.50 763.50 768.00 773.00 782.50 792.00 801.50 811.50 814.50 817.00 829.00 841.46 851.00 860.00 869.00 872.00 91.87 147.60 227.64 393.44 335.23 424.10 220.28 158.12 310.98 145.52 222.08 407.87 295.51 318.18 216.89 69.60 192.21 302.84 183.10 114.66 155.67 84.00 23.25 91.87 147.60 227.64 393.44 335.23 409.28 190.94 137.75 288.44 125.07 191.02 367.35 254.97 283.31 205.01 64.17 185.28 302.84 183.10 114.66 155.67 84.00 23.25 305 X 10 3 491 X 10 3 754 X 10 3 1,301 X 10 3 1,108 X 10 3 1,402 X 10 3 728 X 10 3 523 X 10 3 1,028 X 10 3 481 X 10 3 734 X 10 3 1,349 X 10 3 977 X 10 3 1,052 X 10 3 717 X 10 3 229 X 10 3 630 X 10 3 933 X 10 3 485 X 10 3 227 X 10 3 192 X 10 3 386 X 10 2 186 X 10 0.0 2.43 0.995 0.0 -0.033 0.57 -1.53 -0.82 0.99 1.23 0.25 -0.13 -0.105 -0.052 -0.075

-0.036 0.0 0.0 0.0 0.0 0.0 0.0 0.0 3.7-80SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-5c Lumped-Mass Model Properties of Steel Containment Vessel ModelElevation (ft) Masses(K-sec 2/ft)Mass Momentof Inertias(10 2 k-ft-sec 2)Axial Area(ft 2)Shear Areas (10 2 x ft 2)Moment of Inertias(10 2 x ft 4)M x = M y M z J zA A x = A y J I yy = I xx 872.00.720 0.5828.2314.11 3.64 1.82 869.02.610 11.9924.4612.23 80.98 40.49 860.04.830 59.5424.5012.25268.0134.0 851.03.560 70.4124.4 12.2 456.0 228.0 841.55.690 150.7041.3020.651080.0540.0 829.09.400 289.6741.3020.651290.0645.0 817.05.96 0 195.8941.3020.651356.0682.5 814.52.1628.49 71.0245.1622.581439.0746.6 811.06.746.37 222.7045.1622.581439.0746.6 801.509.888.80 326.7145.1622.581439.0746.6 792.0 9.18 7.92303.4345.1622.58 1439.0746.6 782.512.6711.41418.8245.1622.581439.0 746.6 773.0 6.83 5.93228.0345.1622.581439.0746.6 768.0 4.52 3.88149.4345.1622.581439.0746.6 763.5 9.66 8.96319.32 SEISMIC DESIGN 3.7-81WATTS BARWBNP-110Dome Vertical SDOF OscillatorMass = 6.74 (k-sec 2/ft)Spring Stiffness = 287 x 10 3 (k/ft)Steel PropertiesModulus of Elasticity = 4,176,000 k/ft 2Poisson's Ratio = 0.25

+X = EAST

+Y = NORTH45.1622.581493.0746.6757.5 4.91 4.28162.3641.5520.771373.7686.8754.0 6.84 5.93226.2041.5520.771373.7686.8744.513.1712.71435.4741.5522.771373.7686.8733.510.4110.41 344.1941.5520.771373.7686.8724.512.2212.22 403.9841.5520.771373.7686.8716.57.077.07234.2245.5522.771516.0752.9710.04.564.56152.5545.5522.771516.0752.9703.82.852.8594.8141.5520.771374.0686.8Table 3.7-5c Lumped-Mass Model Properties of Steel Containment Vessel ModelElevation (ft) Masses(K-sec 2/ft)Mass Momentof Inertias(10 2 k-ft-sec 2)Axial Area(ft 2)Shear Areas (10 2 x ft 2)Moment of Inertias(10 2 x ft 4)M x = M y M z J zA A x = A y J I yy = I xx SEISMIC DESIGN 3.7-82WATTS BARWBNP-110Table 3.7-6 Interior Concrete Element Properties E C = 720000 K/Ft 2 G C = 288000 K/Ft 2 East-West Motion North-South Motion Element No.Length, Ft Area, Ft 2 Torsion Constant, Ft 4Moment of Inertia, Ft 4 Shear Factor Moment of Inertia, Ft 4 Shear Factor 1 2 3 4 5 6 7 8 9 10 11 12 13 1412.2210.00 9.96 9.96 5.36 5.35 6.73 6.73 6.73 6.73 6.73 6.7211.8211.82177921071796 1796 880 880115411541154 115411541154 816 8161840 x 10 31700 x 10 31610 x 10 31610 x 10 3249 x 10 3249 x 10 3151 x 10 3151 x 10 3151 x 10 3151 x 10 3151 x 10 3151 x 10 31510 x 10 31510 x 10 31024 x 10 31849 x 10 31829 x 10 31829 x 10 3990 x 10 3990 x 10 3707 x 10 3707 x 10 3707 x 10 3707 x 10 3707 x 10 3707 x 10 3755 x 10 3755 x 10 3 1.76 1.70 1.49 1.49 1.07 1.07 2.02 2.02 2.02 2.02 2.02 2.02 2.00 2.001021 x 10 31281 x 10 31271 x 10 31271 x 10 3320 x 10 3320 x 10 31047 x 10 31047 x 10 31047 x 10 31047 x 10 31047 x 10 31047 x 10 3755 x 10 3755 x 10 3 1.79 2.27 2.20 2.20 1.75 1.75 1.98 1.98 1.98 1.98 1.98 1.98 2.00 2.00 SEISMIC DESIGN 3.7-83WATTS BARWBNP-110Table 3.7-6a Lumped-Mass Model Properties of Interior Concrete Structure-Horizontal Model - Set B and Set C (Page 1 of 2)

Elevation (ft)

Masses(K-sec 2/ft)Mass Momentof Inertias(10 4 k-ft-sec 2) J z Shear Center(ft)e x e y Shear Areas(ft 2)A x A yMoment of Inertias(10 3 x ft 4)I xx I yy J 819.0 38.9 4.2 0.0 0.0 335408 7556251510 807.8 45.5 8.3 0.0 0.0 335408 7556251510 796.0123.713.0-33.673.064452001070655 840 789.3 58.4 8.0-33.673.064452001070655 840 782.6 58.4 8.0-33.673.064452001070655 840 775.8 58.4 8.0-33.673.064452001070655 840 769.1 58.4 8.0-33.673.064452001070655 840 3.7-84SEISMIC DESIGN WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio= 0.15

+X = EAST

+Y = NORTH Elevation (ft)

Masses(K-sec 2/ft)Mass Momentof Inertias(10 4 k-ft-sec 2) J z Shear Center(ft)e x e y Shear Areas(ft 2)A x A yMoment of Inertias(10 3 x ft 4)I xx I yy J 762.4 58.4 8.0-33.673.064452001070655 840 755.6 89.818.4 28.210.90575540 555800 250 750.3 40.0 4.4 28.210.90575540 555800 250744.9135.2 14.7-0.250.85 915580114014601650 735110 12.6-0.250.85 915580114014601650 725114.5 15.2 3.631.761075835117014551830 715160.2 23.2 0.540.13 9401185965 8251815 702.81160 230 0.0 0.0 Table 3.7-6a Lumped-Mass Model Properties of Interior Concrete Structure-Horizontal Model - Set B and Set C (Page 2 of 2)

SEISMIC DESIGN 3.7-85WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio= 0.15

+X = EAST

+Y = NORTHTable 3.7-6b Lumped-Mass Model Properties of Interior Concrete Structure-Vertical Model - Set B and Set CElevation (ft) Masses(k-sec 2/ft)Mass Momentof Inertia(10 4k-ft-sec 2)Location of Centroid(ft)Areas(ft 2)Jd x d y A 819.6 38.9 4.2 0.0 0.0 816 807.8 45.5 8.3 0.0 0.0 816 796.0123.713.0-4.2 0.611154 789.3 58.4 8.0-4.2 0.611154 782.6 58.4 8.0-4.2 0.611154 775.8 58.4 8.0-4.2 0.611154 769.1 58.4 8.0-4.2 0.611154 762.4 58.4 8.0-4.2 0.611154 755.6 89.818.416.600.29 880 750.3 40.0 4.416.600.29 880744.9 135.214.78.560.601796 735 110 12.68.560.601796 725 114.515.26.520.982107 715 160.223.20.250.081779 702.81160 230 SEISMIC DESIGN 3.7-86WATTS BARWBNP-110Table 3.7-7 Interior Concrete Structure - Mass Point Properties (Set A )

Point No. Total Wt. Kips Equip. Wt. Kips WR 2 K-Ft 2Eccentrictiy, Ft E-W Motion Eccentrictiy, Ft N-S Motion 1820335887.48 x 10 60.0 3.8 2453916194.89 x 10 60.0 7.2 33574 8944.07 x 10 60.0 11.0 4435212114.74 x 10 60.0- 3.4 51288 5781.41 x 10 60.0-12.6 6545133975.92 x 10 60.0 21.6 71879 7142.56 x 10 60.0 43.7 81879 7142.56 x 10 60.0 43.7 91879 7142.56 x 10 60.0 43.7101879 7142.56 x 10 60.0 43.7111879 7142.56 x 10 60.0 43.712398317344.16 x 10 60.0 17.7131464 142.67 x 10 60.0 0.0141253 5881.34 x 10 60.0 0.0 SEISMIC DESIGN 3.7-87WATTS BARWBNP-110Table 3.7-8 Interior Concrete Structure - Normal Modes of Vibration ( Set A )East-West MotionNorth-South MotionVertical MotionMode No. Frequency, cps(Period, sec)Participation FactorFrequency, cps(Period, sec)ParticipationFactorFrequency, cps(Period, sec)ParticipationFactor1 8.81(0.114) 1.665 4.96 (0.202) 1.60022.68 (0.044)1.408223.82 (0.042)-0.950 9.64 (0.104) 2.329314.88(0.067) 0.032422.91 (0.044)-0.852524.88 (0.040) 0.887632.34 (0.031) 1.760 3.7-88SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-9 Auxiliary Building Element Properties (Set A, Set B, And Set C)

E C =590,000 k/ft 2; G C = 236,000 k/ft 2 (For Set A)

E C = 590,000 k/ft 2; G C = 252,800 k/ft 2 (For Set B and Set C)North-South MotionEast-West MotionElevationLength(ft)Area(ft 2)TorsionConstant(ft 4)Moment of Inertia(ft 4)Shear Area(ft 2)Moment of Inertia(ft 4)Shear Area(ft 2)692.00699.62 707.25711.50719.88 728.25736.50745.75 755.50771.50781.50 800.50814.257.627.63 4.258.388.37 8.259.259.75 16.00 10.004.00 15.00 13.7511,17211,172 11,1728,4108,410 7,9027,3407,340 5,6094,2694,269 1,495 7812,893x10 42,893x10 42,893x10 42,125x10 42,125x10 42,302x10 42,640x10 42,640x10 42,746x10 41,820x10 41,820x10 4286x10 4233x10 411,914x10 411,914x10 411,914x10 48,570x10 48,570x10 48,178x10 48,052x10 48,052x10 45,961x10 43,782x10 43,782x10 41,037x10 4601x10 44,9684,968 4,9682,2442,244 2,1082,1742,174 1,5031,2421,242 432 3195,728x10 45,728x10 45,728x10 45,708x10 45,708x10 44,801x10 44,645x10 44,645x10 44,469x10 42,460x10 42,460x10 4672x10 4 86x10 44,8604,860 4,8603,5923,592 3,3402,8672,867 2,3101,6091,609570201 SEISMIC DESIGN 3.7-89WATTS BARWBNP-110Table 3.7-9a Auxiliary Building Nodal Coordinates (Set B And Set C)Elev.Y-Coord CM ModeX-Coord CR ModeX-CoordinateCM&CR ModeZ-Coord H-ModelV-Model814.25-213.750.00-230.28-218.360.00800.50-207.420.00-178.72-205.680.00785.50-135.510.00-84.47-139.180.00781.50-154.650.00-84.47-139.180.00771.50-96.660.00-67.32-123.150.00755.50-140.460.00-79.42-158.350.00745.75-156.750.00 3.7-90SEISMIC DESIGN WATTS BARWBNP-110-79.42-158.350.00736.50-145.280.00-84.25-160.350.00728.50-155.670.00-85.92-162.520.00719.88-149.550.00-85.92-162.520.00711.50-137.020.00-65.17-161.350.00707.25-125.610.00-65.17-161.350.00699.62-158.000.00-65.17-161.350.00692.00Fixed base-65.17-161.350.00Table 3.7-9a Auxiliary Building Nodal Coordinates (Set B And Set C)

SEISMIC DESIGN 3.7-91WATTS BARWBNP-110Table 3.7-10 Auxiliary Building Mass Point Properties (Set A, Set B, Set C)EAST-WEST MOTION NORTH-SOUTH MOTION VERTICAL MOTION ElevationTotal Weight (kips) Equip. & Added Soil Weight (kips) Total Weight kips Equip. & Added Soil Weight (kips) Total Weight kips Equip. & Added Soil Weight (kips) WR 2(K-Ft 2)699.621820924712032045822279170532.22 x 10 8707.251803619251968135702160554942.64 x 10 8711.502946144663045054553249675012.90 x 10 8719.881862035342171866322443193472.11 x 10 8728.252347328862455939722551049233.02 x 10 8736.5021840 89521840 89521840 8952.52 x 10 8745.7513131 90513131 90513131 9051.91 x 10 8755.5025921 27325921 27325921 2733.85 x 10 8771.5020797 14620797 14620797 1463.36 x 10 8781.507311 07311 0 7311 00.97 x 10 8785.507870 3997870 399 7870 3990.90 x 10 8800.504676 414676 41 4676 410.45 x 10 8814.255023 3525023 352 5023 3520.30 x 10 8 SEISMIC DESIGN 3.7-92WATTS BARWBNP-110Table 3.7-11 Auxiliary Building Natural Periods (Set A)North-South Motion East-West Motion Vertical MotionModel No. Frequency(cycles/sec.)Mass Participation FactorFrequency(cycles/sec.)Mass ParticipationFactorFrequency(cycles/sec.) Mass ParticipationFactor18.17-2.157x10 36.051.324x10 323.25 -2.300x10 3217.60 0.897x10 310.111.762x10 3324.84 0.747x10 316.000.645x10 3418.77-0.696x10 3

SEISMIC DESIGN 3.7-93WATTS BARWBNP-110Table 3.7-12 North Steam Valve Room Element PropertiesEc = 720000 k/Ft 2 Gc = 300000 K/Ft 2North-South DirectionEast-West DirectionElement No. Length (Ft) Area(Ft 2) TorsionConstant (Ft 4)Moment of Inertia (Ft 4)ShearFactorMoment of Inertia (Ft 4)Shear Factor 19.375830 4423 1021171.232890895.32 29.375 830 4423 1021171.232890895.32 39.375830 4423 1021171.232890895.32 49.375830 4423 1021171.232890895.32 57.0001960422400 2355001.005427001.00 68.580317 1352 205871.611397592.64 78.420318 1263 194711.491511773.03 87.000 373 1717 223391.391599003.55 95.000593 6160 334621.972161002.03105.000593 6160 334621.972161002.03118.000400 1861 285281.331844014.05125.250230 422 178951.831109632.21 3.7-94SEISMIC DESIGN WATTS BARWBNP-110*Includes the weight of contained fill material for mass points 1-4.Revised by Amendment 51Table 3.7-13 North Steam Valve Room Mass Point PropertiesTotal Weight (Kips)*Mass Point No.N-S DirectionE-W Direction 119762796 219762796 319762796427233443 511491369 6 658 658 7 475 475 8 477 477 9 552 55210 473 47311 331 33112 330 330 3.7-95SEISMIC DESIGN WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio= 0.15

+X = EAST

+Y = NORTHTable 3.7-13a Lumped-Mass Model Properties of North Steam Valve Room (NSVR) - Horizontal Model (SET B, Set C)Elevation(ft)Masses(K-sec 2/ft)Mass Momentof Inertia(10 3 k-ft-Sec 2) Shear Center(ft)Shear Areas(ft 2)Moment of Inertias(10 3 x ft 4)J K J Y e x e y A X A Y J Ix-x Iy-y777763753738 72815.39 28.430.7527.829.90.601.691.521.16 0.48 3.75 10.87 10.438.54 3.25 8.72 8.68 6.18 1.494.143.69 3.83-1.32106319110130257295 259228 43.8 60.8 54.9 89.1 21.5 38.2 18.7 14.6102.3 177.6132.4 71.9 3.7-96SEISMIC DESIGN WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio= 0.15

+X = EAST

+Y = NORTHTable 3.7-13b Lumped-Mass Model Properties of North Steam Valve Room (NSVR) - Vertical Model (Set B, Set C)

Elevationft)Masses(k-sec 2/ft)Mass Momentof Inertia(10 3 k-ft-sec 2)Location ofCentroid(ft)Areas(ft 2)J z d X d Y A77715.39 7.377.19-8.6836376328.4 13.341.20-5.9161375330.7512.782.54-8.7536973827.8210.72-.28-9.62358728 9.9 3.74 SEISMIC DESIGN 3.7-97WATTS BARWBNP-110Revised by Amendment 51Table 3.7-14 North Steam Valve Room Natural FrequenciesNorth-South MotionEast-West MotionVertical MotionCaseMode No.Frequency (Hz) Participation Factor Frequency (Hz) Participation Factor Frequency (Hz) Participation Factor 0.5 G 1 2 3 4 5 6 7 8 2.63 6.76 9.0311.2816.2522.22 24.3325.88-0.0465 0.2428 2.6640-0.6918 0.4464 0.2433 1.5204-1.3297 2.62 6.04 9.5911.3016.1220.04 22.3225.43-0.2666-0.9882 2.4961 1.7919 0.6909-0.9738 0.3151-0.0209 G 1 2 3 4 5 6 7 8 2.64 6.79 9.1911.2916.26 22.2524.5625.98-0.0476 0.2278 2.6917-0.7362 0.4458 0.2179 1.6430-1.5517 2.62 6.10 9.9611.3616.14 20.2522.3325.43-0.2543-0.9356 2.7548 2.2774 0.7316-1.0336 0.3650-0.021834.37---



1.7273----



1.5 G 1 2 3 4 5

6 7 8 2.65 6.81 9.3311.2916.27 22.2524.7626.12-0.0487 0.2154 2.7216-0.7817 0.4452 0.1981 1.6990-1.7493 2.63 6.1410.2811.4316.17 20.4722.3325.43-0.2444-0.8933-3.3180 2.8117 0.7708-1.0920 0.4278-0.0229 SEISMIC DESIGN 3.7-98WATTS BARWBNP-110Table 3.7-15 Pumping Station Element PropertiesEC = 590,000 k/ft 2; GC = 246,000 k/ft 2Motion about X-XMotion about Y-Y Element No.Length F Area Ft 2Moment ofInertia Ft 4Shear FactorMoment of Inertia Ft 4 ShearFactor110.2523381410 x 10 31.5653061 x 10 32.769 2 8.0028251833 x 10 31.8653248 x 10 32.155 3 10.0028251833 x 10 31.8653248 x 10 32.155 410.0028251833 x 10 31.8653248 x 10 32.155 510.0028251833 x 10 31.8653248 x 10 32.155 6 9.5028251833 x 10 31.8653248 x 10 32.155 711.0027471779 x 10 32.0053389 x 10 31.995 8 5.7526021774 x 10 32.1243305 x 10 31.889 9 6.501932 497 x 10 31.8072710 x 10 32.23810 6.501932 497 x 10 31.8072710 x 10 32.238 SEISMIC DESIGN 3.7-99WATTS BARWBNP-110Notes:1.x, y and z are local coordinate axes, i.e., x: vertical (global Z) y: transverse (global Y) z: longitudinal (global X)2. A x is the cross-sectional area, and A y and A z are the shear areas in the transverse and longitudinal directions respectively. J xx is torsional moment of inertia, and I yy, and I zz are the bending moments of inertia about the transverse and longitudinal axes respectively.3. E c for beam elements: 590000 k/ft 2Table 3.7-15a Intake Pumping Station Beam Element Properties (Set B, Set C) Moment of Inertia Elev.A x A y A z J xx I yy I zz<----------------------------ft 2------------------------><------------------------ft 4----------------------->754.001217 541.6 675.40.512x10 61337353294476739.502167 847.31319.71.13x10 63158004572896733.002167 847.31319.71.13x10 63158004572896726.502772 1297.31474.72.15x10 637301811745654720.753105 1639.41465.62.15x10 640701561763585709.753148 1520.51627.52.05x10 639034971904018700.253000 1302.01698.02.05x10 636749711896620690.253000 1302.01698.02.05x10 636749711896620680.252958 1260.11697.92.05x10 636014511889580670.252945 1248.71696.32.05x10 636546831860185662.252204 894.81309.21.89x10 629813361344534652.00 3.7-100SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-16 Pumping Station Mass Point Properties1/2 SSE PROPERTIES SSE PROPERTIES Mass Point No. Total Wt Kips Equip. &Water Wt Kips Total Wt Kips Equip. &Water Wt Kips 17871437878714378 27804399078043990 37448321074483210 47448321074543216 57262313074673335 68637435783064026 76856346763842995 83217115332171153 91884 0 1884 0 104593365245933652 SEISMIC DESIGN 3.7-101WATTS BARWBNP-110Table 3.7-16a Intake Pumping Station Nodal Weight Properties (Set B And Set C)WEIGHTSWEIGHTS MOMENTS OF INERTIAElev. Wx Wy Wz Wxx Wyy Wzz feet<---------------------- kips -------------------><------------------ 10 6 kips-ft 2 ------------------>754.001696169616960.388781.89422.2830 739.505046504650461.06266.53407.5965 733.002160216021600.606283.13293.7392 726.503595359533681.91823.78485.7031 720.756206620651232.35787.10569.4634 709.757709770955713.27266.58899.8615 700.257856785644932.77925.53758.3167 690.257994799444992.84495.51258.3574 680.257977797744692.83975.45738.2970 670.257543754351082.86766.27019.1378 662.257562756245642.50895.85418.3630 3.7-102SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-16b Intake Pumping Station Nodal Coordinates (Set B And Set C) (Feet Units)Elev.CM NodeCR NodeZ-CoordX-CoordY-CoordX-CoordY-Coord754.00 0.3823.150.0024.02739.50 0.0623.310.0025.41733.00 0.7421.550.0025.41726.50 0.0336.610.0042.40720.75-0.0131.200.0042.97709.75 0.0036.240.0044.71700.25 0.0033.21 SEISMIC DESIGN 3.7-103WATTS BARWBNP-1100.0045.54690.25 0.0033.040.0045.54680.25 0.0033.130.0046.00670.25 0.0034.300.0045.87662.25 0.0033.130.0038.01652.000.0038.01648.00 Fixed Base==>0.0043.00Table 3.7-16b Intake Pumping Station Nodal Coordinates (Set B And Set C) (Feet Units) 3.7-104SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-17 Pumping Station Natural Periods1/2 SAFE SHUTDOWN EARTHQUAKEMotion About X-X Motion About Y-Y Vertical Motion Mode No.Period (Sec)ParticipationFactor Period (Sec)ParticipationFactor Period (Sec)ParticipationFactor10.10851.45290.10911.3786 0.0420 1.2995 20.0353-0.67140.0374-0.56080.01454-0.4914 30.02540.3298 0.0222 0.26930.009390.2946SAFE SHUTDOWN EARTHQUAKEMotion About X-X Motion About Y-Y Vertical Motion Mode No.Period(Sec) ParticipationFactor Period(Sec)ParticipationFactor Period (Sec)ParticipationFactor10.1075 1.45790.1082 1.38300.0417 1.3035 20.0353-0.67500.0374-0.56520.0145-0.4958 30.0205 0.32590.0222 0.26710.00938 0.2924 SEISMIC DESIGN 3.7-105WATTS BARWBNP-110Table 3.7-18 Diesel-Generator Building Element PropertiesEC = 590,000 K/FT 2 GC = 236,000 K/FT 2North-South Motion East-West Motion Element No. Length, Ft. Area, Ft 2 Moment ofInertia, Ft 4ShearFactorMoment ofInertia, Ft 4 ShearFactor16.001060119 x 10 41.77235 x 10 42.3026.001060119 x 10 41.77235 x 10 42.3035.751162137 x 10 41.91252 x 10 42.1043.751259117 x 10 42.10225 x 10 43.0055.00 992 64 x 10 41.65190 x 10 46.5262.751259117 x 10 42.10225 x 10 43.00 3.7-106SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-19 Diesel-Generator Building Mass Point PropertiesMass PointTotal Weight Equipment Weight Weight Moment of Inertia (K-Ft 2)No.(Kips)(Kips)N-S MotionE-W MotionBase14,800650178 x 10 5273 x 10 51960-107 x 10 4212 x 10 42980-113 x 10 4215 x 10 433,250205223 x 10 4472 x 10 44920-57 x 10 4135 x 10 45800-48 x 10 4118 x 10 462,250-100 x 10 4223 x 10 4 SEISMIC DESIGN 3.7-107WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio = 0.15

+X = EAST

+Y = NORTH

  • Rocking Mass Moment of Inertia:

I X-X = 85.6 x 10 4 k-ft-S 2; IY-Y = 137.92 x 10 4 k-ft-S 2Table 3.7-19a LUMPED-MASS MODEL PROPERTIES of DIESEL GENERATOR BUILDING - HORIZONTAL MODEL (SET B and SET C)Elevation (ft) Masses(K-sec 2/ft)Mass Momentof Inertias(10 4 k-ft-sec 2) ShearCenter(ft)Shear Areas(ft 2)Moment of Inertias(10 3 x ft 4)J z e x e y A x A y JIy-y Iy-y 773.5107.58 27.85 0 10.49430.8 645.3 1295 868 1445 768.5--0 2.27182.7 635.9 996 711.51003 763.5--010.08434.7 642.1 1295 926.51333 759.75188.89 49.40 0 4.51562 589.6 1290 765.51653 754--0-17.1 697.05715.9717071522 2013 748--0-19.41729.1 765.8 17651731 2098 742 43.73 15.67 00Rigid Link Basemat540.87130.59*

3.7-108SEISMIC DESIGN WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio = 0.15

+X = EAST

+Y = NORTH

  • Rocking Mass Moment of Inertia:

I X-X = 85.6 x 10 4 k-ft-S 2; IY-Y = 137.92 x 10 4 k-ft-S 2Table 3.7-19b Lumped-Mass Model Properties Of Diesel Generator Building - Vertical Model (Set B And Set C)

Elevation (ft)Masses(K-sec 2/ft)Mass Momentof Inertia(10 4k-ft-sec 2)Location of Centroid(ft)Areas(ft 2)J z d x d y A 773.5107.58 27.85 0 10.141086.03 768.5--0 7.90 818.6 763.5--0 9.481076.8 759.75188.89 49.40 0 7.911151.6 754--0 -3.541413.02 748--0 -6.271494.9 742 43.73 15.67 Base540.87130.59*

SEISMIC DESIGN 3.7-109WATTS BARWBNP-110Table 3.7-19c Lumped-Mass Model Properties of Refueling Water Storage Tank - Seismic Model (Set B and Set C)

Elevation(ft)Masses(k-sec 2/ft) Mass Momentof Inertias(10 4 k-ft-sec 2)Axial Area(ft)Shear Areas (ft 2)Moment of Inertia(ft 4)M X=M Y M Z I X=I YJAA x A y J Ix-x Iy-y 767.20 0.96 0.96 --3.5511.8841.8841678 839 839 763.20 3.94 0.31 --3.5511.8841.8841678 839 839 759.66 7.86 .34 --4.2332.2462.246200010001000 755.85 8.17 0.37 --4.2332.2462.246200010001000 752.04 8.17 0.37 --

28.32*4.6432.4632.463219210961096 748.23 8.17 0.37 -4.6432.4632.463219210961096 744.42 8.23 0.43 --6.0073.1873.187283614181418 740.61 8.26 0.47 --6.0073.1873.187283614181418 736.80 8.29 0.50 --7.5073.9823.982354217711771 733.0 8.32 0.56 --7.5073.9823.982354217711771 729.20 4.16 28.98 1.242.4869.22**BaseCenter Sum: 72.52175.37 72.52 175.37 1.903.14x10 4 3.656.13x10 4 3.7-110SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-19c Lumped-Mass Model Properties of Refueling Water Storage Tank - Seismic Model (Set B and Set C)Young's Modulus E = 30,000 ksiShear Modulus G= 11,540 ksi

  • Sloshing-induced horizontal mass, M X = M Y = 28.32 k-sec 2/ft associated horizontal spring, K X = K Y = 76.2 k/ft**Seismic-induced vertical effective mass, M Z = 69.22 k-sec 2/ftassociated vertical spring K Z = 246120 k/ft SEISMIC DESIGN 3.7-111WATTS BARWBNP-110 Table 3.7-20 Diesel-Generator Building Natural Periods V S = 1150 FPS N-S Motion E-W Motion Mode No. KT = 147 x 10 4 K/FtKR = 300 x 10 7 K-Ft RAD Period, Second KT = 141 x 10 4 K/FtKR = 425 x 10 7 K-Ft RAD Period, Second 1 2 30.1540.1030.0290.1560.1110.035 V S = 1650 FPS N-S Motion E-W Motion Mode No. KT = 308 x 10 4 K/FtKR = 614 x 10 7 K-Ft RAD Period, Second KT = 294 x 10 4 K/FtKR = 887 x 10 7 K-Ft RAD Period, Second 1 2 30.1080.0720.0280.1100.0770.034 V S = 2150 FPS N-S MotionE-W Motion Mode No. KT = 517 x 10 4 K/FtKR = 1031 x 10 7 K-Ft RAD Period, Second KT = 493 x 10 4 K/FtKR = 1490 x 10 7 K-Ft RAD Period, Second 1 2 30.0850.0560.0280.0870.0590.033 3.7-112SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-21 Waste-Packaging Area Element PropertiesEC = 590,000 K/FT 2 GC = 236,000 K/FT 2North-South Motion East-West Motion Element No. Length (Ft) Area (Ft 2) Moment of Inertia (Ft 4)Shear FactorMoment of Inertia, Ft 4 Shear Factor19.00573.21841002.365565001.63 26.50573.21841002.365565001.63 36.50573.21841002.365565001.63 45.75573.21841002.365565001.63 55.75319.2 786301.593935002.56 65.75237.7 727001.952670001.91 75.75156.4 667283.891360001.25 SEISMIC DESIGN 3.7-113WATTS BARWBNP-110Table 3.7-22 Waste-Packaging Area Mass Point PropertiesMass Point Mo. Total Weight Kips Weight Moment of Inertia, K-ft 2 N-S Motion E-W MotionBase3108 6.04 x 10 5 2.08 x 10 6 1971 1.86 x 10 5 5.63 x 10 52629 1.79 x 10 5 5.43 x 10 53512 1.69 x 10 55.11 x 10 54418 1.13 x 10 5 4.10 x 10 55597 0.65 x 10 5 2.85 x 10 56535 0.60 x 10 5 1.74 x 10 57444 0.29 x 10 5 0.59 x 10 5 3.7-114SEISMIC DESIGN WATTS BARWBNP-110 anTable 3.7-23 Waste-Packaging Area Natural Periods SSE Mode No. N-S MotionKT =5.34 x 10 5 K/FtKR =6.02x10 7 K-Ft/RadPeriod, Second E-W MotionKT =8.30x 10 5 K/FtKR = 1.65 x 10 9 K-Ft/Rad Period, Second 1 20.313 0.108 0.116 0.065 1/2 SSE Mode No. N-S MotionKT =8.54x 10 5 K/FtKR = 4.24 x 10 8 K-Ft/RadPeriod, Second E-W MotionKT = 8.30 x 10 5 K/FtKR = 1.65 x 10 9 K-Ft/Rad Period, Second 1 20.143 0.072 0.116 0.065 SEISMIC DESIGN 3.7-115WATTS BARWBNP-110E = 720000 ksfE/G = 2.50Table 3.7-23a CDWE Building Soil Deposit Shear Moduli And Shear Wave VelocitiesSoil ProfileShear Modulus (ksf)Shear Wave Velocity (f/s)Average2409 761

-50% Variation 1205 538

+50% Variation3613 932Spring Constants for Pile GroupDirectionSpring Constant N-S Translation5.61 x 10 5 k/f E-W Translation5.31 x 10 5 k/f Rocking About E-W Axis1.61 x 10 9 k-f/rad Rocking About N-S Axis2.57 x 10 9 k-f/radVertical3.41 x 10 6 k/f Mass Point Properties - Lumped Mass Model Mass PointWeight(kips)Center of Gravity(f)Mass Moment About CG (k-f)Mass Moment About GeometricCenter (k-f) X Y XYXYZBase2669.5-1.054-0.829386095659047 3709096212599558111 742.3 0.0 0.0 220746331660 220746331660530274 22031.9-1.850 0.050357010612045 357455611943932527 3 742.3 0.0 0.0 220746331660 220746331660530274 4 1120.3 0.600 0.0 227799346548 227126346548570708Element Properties - Lumped Mass Model ElementLength(f) Area (f 2) Moment of Inertia (f 4) Torsion Constant (f

4) Shape Factor XYXY114.75370.0104513159798 57180001.692.22 214.0 370.0104513159798 57180001.692.22 313.0 370.0104513159798 57180001.692.22 414.0 370.0104513159798 57180001.692.22 3.7-116SEISMIC DESIGN WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio= 0.15

+X = EAST

+Y = NORTH

  • Rocking Mass Moments of Inertia:

El. 742': Ix-x = 13.9x10 4 k-ft-S 2; Iy-y = 9.1x10 4 k-ft-S 2 El. 736': Ix-x = 29.6 x 10 4 k-ft-S 2; Iy-y = 9.8 x 10 4 k-ft-S 2Table 3.7-23b Lumped-Mass Model Properties of Additional Diesel Generator Building - Horizontal ModelElevation(ft) Masses(K-sec 2/ft)Mass Moment of Inertias(10 4 k-ft-sec 2) ShearCenter(ft)Shear Areas(ft 2)Moment of Inertias(10 3 x ft 4)J z e x e y A x A y JIx-x Iy-y 773.25 61.9 6.61 1.464.01301.5531.8619.2545.0158.7766.5--1.913.37284.6517.6629.8502.6140.6759.75 88.411.30 1.48-7.05306.0499.8662.6488.3116.2750.875--1.26-8.12288.6479.0675.2502.9160.5742.0 32.5 4.96*

Rigid Link736.0260.039.4* (Basemat)

SEISMIC DESIGN 3.7-117WATTS BARWBNP-110Concrete PropertiesModulus of Elasticity = 576,000 k/ft 2Poisson's Ratio = 0.15

+X = EAST

+Y = NORTH

  • Rocking Mass Moments of Inertia:

El. 742': Ix-x = 13.9x10 4 k-ft-S 2; Iy-y = 9.1x10 4 k-ft-S 2 El. 736': Ix-x = 29.6 x 10 4 k-ft-S 2; Iy-y = 9.8 x 10 4 k-ft-S 2Table 3.7-23c Lumped-Mass Model Properties of Additional Diesel Generator Building - Vertical Model Elevation(ft)Masses(k-sec 2/ft)Mass Momentof Inertia(10 4 k-ft-sec 2)Location of Centroid(ft)Areas(ft 2)J z d x d y A773.25 61.9 6.61 2.58 4.4 833.3766.5--2.85 3.71802.2759.75 88.411.30 1.32-0.51805.8750.875--1.29-0.69767.6742.0 32.5 4.96* Rigid Link736.0(Basemat)260.039.4*

3.7-118SEISMIC DESIGN WATTS BARWBNP-110Notes: (1) Damping value used when stress levels are at or near yield. (2) An as option, for some cases or piping response spectrum seismic analysis, variable damping of 5% to 10 hertz decreasing linearly to 2% at 20 hertz and remaining at 2% to 33 hertz was used for both OBE and SSE as described in ASME Code Case N-411.Table 3.7-24 Damping Ratios For Fluid System Piping and Their Supports Analyzed by NSSS VendorDamping Ratio Percentage of Critical Viscous Damping ItemOBESSE Reactor Coolant Loop 11 Auxiliary Piping Systems(2)0.51Welded Steel Structures11-2 (1)Bolted Steel Structures22-5 (1) 3.7-119SEISMIC DESIGN WATTS BARWBNP-110Table 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 1 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarksReactor Coolant System Reactor VesselXSeeSection 5.2Full-length CRDM housingX" Part-length CRDM housingX" Reactor coolant pumpX" Steam generatorX" PressurizerX" Reactor coolant piping to pressure boundary X"RC system supportsX"Surge pipe and fittingsX" Bypass manifoldX

RC ThermowellsXSeeSection 5.2Safety valvesX" Relief valvesX" Valves to RC system boundary X"CRDM head adapter plugsXSee Section5.2 3.7-120SEISMIC DESIGN WATTS BARWBNP-110Chemical and Volume Control SystemRegenerative HXXSeeSection 3.9Letdown HXX" Mixed-bed demineralizerX" Cation bed demineralizerX" Reactor coolant filterX" Volume control tankX" Charging/high head safety injection pumpXXSeeSection 3.9Tests were run to determine natural frequency of the foundation system to meet seismic criteria.Seal water injection filterX" Excess letdown HXX" Seal water return filterX" Seal water HXX" Boric acid tanksX" Boric acid filterX" Boric acid transfer pumpX" Boric acid blenderX"Table 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 2 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks 3.7-121SEISMIC DESIGN WATTS BARWBNP-110Chemical and VolumeControl SystemReactor make up water storage tankXw/o exceeding 90% of yield stresses and/or loss of functionEmergency Core Cooling System AccumulatorsX" Boron injection tankX" BIT recirculation pumpX" Boron injection surge TankXSeeSection 3.9Residual Heat Removal System Residual heat removal/low head safety injection pump X"Residual heat exchangerX"Containment Spray System Spray additive tankX" Containment spray pumpX" Containment Isolation System ValvesXSeeSection 3.9Containment Cooling SystemTable 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 3 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks 3.7-122SEISMIC DESIGN WATTS BARWBNP-110FansXSeeSection 3.9Heat ExchangerX" Component Cooling System PumpsX" Heat exchangersX" Surge TankX" Spent Fuel Pool Cooling System Spent fuel pool heat exchangerX" Spent fuel pool pumpX" Boron Thermal Regeneration SubsystemModerating HXXSeeSection 3.9Letdown chiller HXX" Letdown reheat HXX" Thermal regeneration demineralizerX" Liquid Recycle and Waste SubsystemRecycle holdup tankXSeeSection 3.9 Per API 650Table 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 4 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks 3.7-123SEISMIC DESIGN WATTS BARWBNP-110Recycle evaporator feed pump X"Recycle evaporator feed demineralizer X"Recycle evaporator feed filterX"Recycle evaporatorX" R.C. drain tank HXX" Waste holdup tankX" Waste evaporator feed filterX" Waste evaporatorX" Spent resin storage tankX" Spent resin sluice pumpX" Spent resin sluice filter X" Floor drain tankX"ES room sump pumpX"Gas Handling Subsystem Gas compressorXXSeeSection 3.9Vibration tests were conducted to determine seismic capabilityGas decay tanksX"Table 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 5 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks SEISMIC DESIGN 3.7-124WATTS BARWBNP-110Emergency Diesel Fuel Oil SystemTransfer pumpsX" Fuel oil tanksX" Essential Raw Cooling Water System PumpsX" Fuel Handling System Fuel manipulator craneXSeeSection 3.9Fuel transfer tubeX" Underwater fuel conveyor car and rail system X"Fuel pool bridge craneX"Fuel Handling System Polar craneXSeeSection 3.9Crane supportsX" Refueling Water System Storage tankXw/o exceeding 90% of yield stresses and/or loss of functionAuxiliary Building Ventilation SystemTable 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 6 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks SEISMIC DESIGN 3.7-125WATTS BARWBNP-110ES air cooling units: Heat exchangerXw/o exceeding 90% of yield stresses and/or loss of function FanX" Penetration Room Filtration SystemFansX" Filters (HEPA and charcoal)X" Control Room Ventilation System FansX" FiltersX" Control Room Ventilation System Air Conditioning unitXSeeSection 7.1Heat exchangerX" Diesel Building Ventilation System FansXw/o exceeding 90% of yield stresses and/or loss of function Filters X"Main Steam SystemTable 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 7 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks SEISMIC DESIGN 3.7-126WATTS BARWBNP-110Isolation valvesX"Auxiliary Feedwater System Auxiliary feedwater pumps motordriven, steam turbine driven X"Condensate storage tankX"Steam Dump Systems Relief ValvesX" Safety ValvesX" Electrical Components and Systems 6.9 kV shutdown boards (engineered safe-guard buses)Xw/o exceeding 90% of yield stresses and/or loss of function6.9 kV to 480 V transformers (associated with engineered safeguard systems)

X"480 V shutdown boards (engineered safeguard systems buses)X"Test on prototype480-V motor-control centers (associated with engineered safeguard systems)X"Test on prototype125-Vdc vital batteriesX"Test on prototypeTable 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 8 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks SEISMIC DESIGN 3.7-127WATTS BARWBNP-110120-Vac vital inverters, (associatedwith vital instrument buses)XSeeSection 7.1125-Vdc battery boardsXSeeSection 7.1Tests on two panels selected at random120-Vac vital instrument power boards X"Electrical Components and Systems125-v dc switchgearXSeeSection 7.1Tests on prototype125-v dc battery chargersX"Test on one chargerSolid-state protection system cabinets X"Reactor trip switchgearX"Nuclear instrumentation system cabinets X"Process protection and control system cabinets X"Cable tray supports (associated with engineered safeguard system)X"Auxiliary relay racks X"Table 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 9 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks 3.7-128SEISMIC DESIGN WATTS BARWBNP-110Containment penetration assembliesXw/o exceeding 90% of yield stresses and/or loss of functionTest on one medium voltage penetration assembly plus test on a composite assembly comprised of 1 1000-v dc power and 600-v control and instrument cablesElectrical Components and Systems Emergency power boardXXw/o exceeding 90% of yield stresses and/or loss of functionInstruments and switches are testedDirect-current emergency lightingX"Test on prototypeDiesel generatorsX" Diesel generator control panelsX" Diesel generator sequencersX"Test on one panel Boric acid heat-tracing equipmentX" Balance of plant instrument cabinets and equipment contained thereinXw/o loss of functionEquipment contained within balance of plant instrument cabinetsXXw/o loss of functionContainment purge radiation monitorsXXw/o loss of functionTable 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 10 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks SEISMIC DESIGN 3.7-129WATTS BARWBNP-110Fuel handling area radiation monitorsXXw/o loss of functionSampling System

1. CabinetXw/o exceeding 90% of yield stresses and w/o loss of function 2. Tubing, valves, coolers, sample vesselsXw/o loss of functionElectrical Components and Systems Balance of plant field mounted instrumentsXXw/o loss of functionInstrument valves for field mounted instrumentsXw/o loss of functionInstrument lines for field mounted instrumentsXw/o exceeding code allowable stressesTable 3.7-25 Methods Used for Seismic Analyses of Category I Systems and Components (Page 11 of 11)Method of Analysis Category ISystems and ComponentsEquivalent Static LoadResponseSpectraAnalysisTime-HistoryAnalysisTestsApplicableStress orDeformationCriteriaRemarks 3.7-130SEISMIC DESIGN WATTS BARWBNP-110 Notes:(1) In applying the above load combinations for design, dead load and thermal effects may be combined directly, accounting for their signs. Seismic loads are reversing and their effects must be combined without sign with the other loads. The latter is also true for DBA loads. (See Section 3.7.3.17.3 for definition of loads and their combinations.)(2) But less than 0.52 F y for shear stresses, and less than 0.90 F cr for critical buckling stresses.Table 3.7-26 Allowable Stresses for Duct SupportsElementsLoad Combination(1)AllowablesComponent Standard Supports(1) and (2)(3), (4), and (5)Factor of Safety of 5against ultimate strength0.90 F y (F y = minimumspecified yield stress)or a minimum factor ofsafety of 2.5 against ultimate strengthSteel Structural Members and Connecting Welds (Linear Supports)(1)(2)(3) and (4)

AISC allowables1.5 x AISC allowables butless than 0.90 F y (2)1.6 x AISC allowables butless than 0.90 F y (2)(5)1.7 x AISC allowables butless than 0.90 F y (2)Anchorage in Hardened ConcreteExpansion Anchors(a) Shell Types (SSD & SDI)(b) Other Types (Wedge)(1), (2), (3),(4), and (5)Factor of Safety on minimum anchor ultimate tensile capacity 5 4 SEISMIC DESIGN3.7-131WATTS BARWBNP-110Figure 3.7-1 Set A and Set C Site Design Response Spectra Safe ShutdownEarthquake Rock-Supported Structures 1/2% Damping

SEISMIC DESIGN3.7-132WATTS BARWBNP-110Figure 3.7-2 Set A and Set C Site Design Response Spectra Safe ShutdownEarthquake Rock-Supported Structures 1% Damping SEISMIC DESIGN3.7-133WATTS BARWBNP-110Figure 3.7-3 Set A and Set C Site Design Response Spectra Safe ShutdownEarthquake Rock-Supported Structures 2% Damping SEISMIC DESIGN3.7-134WATTS BARWBNP-110Figure 3.7-4 Set A and Set C Site Design Response Spectra Safe ShutdownEarthquake Rock-Supported Structures 5% Damping SEISMIC DESIGN3.7-135WATTS BARWBNP-110Figure 3.7-4a Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (N-S) Rock Supported Structures 1% Damping SEISMIC DESIGN3.7-136WATTS BARWBNP-110Figure 3.7-4b Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (N-S) Rock Supported Structures 2% Damping SEISMIC DESIGN3.7-137WATTS BARWBNP-110Figure 3.7-4c Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (N-S) Rock Supported Structures 3% Damping SEISMIC DESIGN3.7-138WATTS BARWBNP-110Figure 3.7-4d Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (N-S) Rock Supported Structures 4% Damping SEISMIC DESIGN3.7-139WATTS BARWBNP-110Figure 3.7-4e Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (N-S) Rock Supported Structures 5% Damping SEISMIC DESIGN3.7-140WATTS BARWBNP-110Figure 3.7-4f Set B Site Specific Response Spectrum Safe Shutdown Earthquake (N-S) Rock Supported Structures 7% Damping SEISMIC DESIGN3.7-141WATTS BARWBNP-110Figure 3.7-4g Specific Design Response Spectrum Safe ShutdownEarthquake (E-W) Rock Supported Structures 1% Damping SEISMIC DESIGN3.7-142WATTS BARWBNP-110Figure 3.7-4h Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (E-W) Rock Supported Structures 2% Damping SEISMIC DESIGN3.7-143WATTS BARWBNP-110Figure 3.7-4i Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (E-W) Rock Supported Structures 3% Damping SEISMIC DESIGN3.7-144WATTS BARWBNP-110Figure 3.7-4j Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (E-W) Rock Supported Structures 4% Damping SEISMIC DESIGN3.7-145WATTS BARWBNP-110Figure 3.7-4k Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (E-W) Rock Supported Structures 5% Damping SEISMIC DESIGN3.7-146WATTS BARWBNP-110Figure 3.7-4l Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (E-W) Rock Supported Structures 7% Damping SEISMIC DESIGN3.7-147WATTS BARWBNP-110Figure 3.7-4m Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (Vertical) Rock Supported Structures 1% Damping SEISMIC DESIGN3.7-148WATTS BARWBNP-110Figure 3.7-4n Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (Vertical) Rock Supported Structures 2% Damping SEISMIC DESIGN3.7-149WATTS BARWBNP-110Figure 3.7-4o Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (Vertical) Rock Supported Structures 3% Damping SEISMIC DESIGN3.7-150WATTS BARWBNP-110Figure 3.7-4p Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (Vertical) Rock Supported Structures 4% Damping SEISMIC DESIGN3.7-151WATTS BARWBNP-110Figure 3.7-4q Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (Vertical) Rock Supported Structures 5% Damping SEISMIC DESIGN3.7-152WATTS BARWBNP-110Figure 3.7-4r Set B Site Specific Design Response Spectrum Safe ShutdownEarthquake (Vertical) Rock Supported Structures 7% Damping SEISMIC DESIGN3.7-153WATTS BARWBNP-110Figure 3.7-4s Comparisons of H1 Artificial Time History PSDF With Horizontal, 84thPercentile, and Minimum Required, 84th-Percentile Target PSDFs SEISMIC DESIGN3.7-154WATTS BARWBNP-110Figure 3.7-4t Comparisons of H2 Artificial Time History With Horizontal, 84thPercentile, and Minimum Required, 84th-Percentile Target PSDFs SEISMIC DESIGN3.7-155WATTS BARWBNP-110Figure 3.7-4u Comparisons of V Artificial Time History With Vertical, 84th Percentile, and Minimum Required, 84th- Percentile Target PSDFs SEISMIC DESIGN3.7-156WATTS BARWBNP-110Figure 3.7-5 Lumped Mass Model for Analysis of Cylindrical Shell SEISMIC DESIGN3.7-157WATTS BARWBNP-110Figure 3.7-5a Seismic Analysis Model for Shield Building (Set B and Set C)

SEISMIC DESIGN3.7-158WATTS BARWBNP-110Figure 3.7-6 Flow Chart of Operations for Response of the Dome SEISMIC DESIGN3.7-159WATTS BARWBNP-110Figure 3.7-7 Shell Model For Dome Analysis-Shield Building SEISMIC DESIGN3.7-160WATTS BARWBNP-110Figure 3.7-7a Seismic Analysis Hodel for Steel Containment Vessel (Set B and Set C)

SEISMIC DESIGN3.7-161WATTS BARWBNP-110Figure 3.7-7b Containment Vessel Lumped Mass Beam Model And Properties SEISMIC DESIGN3.7-162WATTS BARWBNP-110Figure 3.7-7c Sectional Elevation Of Steel Containment Vessel And Lumped Mass Model For Seismic Analysis SEISMIC DESIGN3.7-163WATTS BARWBNP-110Figure 3.7-8 Sectional Elevational Looking North Lumped Mass Model For Dynamic Analysis SEISMIC DESIGN3.7-164WATTS BARWBNP-110Figure 3.7-8a Seismic Analysis Model for Interior Concrete Structure (Set B and Set C)

SEISMIC DESIGN3.7-165WATTS BARWBNP-110Figure 3.7-8b Seismic Analysis Model for Interior Concrete Structure (Set B and Set C)

SEISMIC DESIGN3.7-166WATTS BARWBNP-110Figure 3.7-8c Dynamic Model For the Reactor Pressure Vessel (RPV)

SEISMIC DESIGN3.7-167WATTS BARWBNP-110Figure 3.7-8d Dynamic Model For the Reactor Coolant Loop 1 SEISMIC DESIGN3.7-168WATTS BARWBNP-110Figure 3.7-8e Dynamic Model For the Reactor Coolant Loop 2 SEISMIC DESIGN3.7-169WATTS BARWBNP-110Figure 3.7-8f Dynamic Model For the Reactor Coolant Loop 3 SEISMIC DESIGN3.7-170WATTS BARWBNP-110Figure 3.7-8g Dynamic Model For the Reactor Coolant Loop 4 SEISMIC DESIGN3.7-171WATTS BARWBNP-110Figure 3.7-9 Lumped Mass Model for Dynamic Analysis-Auxiliary Control Building SEISMIC DESIGN3.7-172WATTS BARWBNP-110 Figure 3.7-9a ACB Seismic Model (Set B and Set C)

SEISMIC DESIGN3.7-173WATTS BARWBNP-110Figure 3.7-10 Sectional Elevation of North Steam Valve Room and Lumped Mass Model for Seismic Analysis SEISMIC DESIGN3.7-174WATTS BARWBNP-110Figure 3.7-10a Lumped-Mass Stick Model for the NSVR Superstructure - YZ Plane SEISMIC DESIGN3.7-175WATTS BARWBNP-110Figure 3.7-10b Lumped-Mass Stick Model for the NSVR Superstructure - XZ Plane SEISMIC DESIGN3.7-176WATTS BARWBNP-110Figure 3.7-11 Sectional Elevation of Intake Pumping Station - Lumped Mass Model for Dynamic Analysis SEISMIC DESIGN3.7-177WATTS BARWBNP-110Figure 3.7-11a IPS Seismic Model SEISMIC DESIGN3.7-178WATTS BARWBNP-110Figure 3.7-12 Mathematical Model for Soil Structure Interaction SEISMIC DESIGN3.7-179WATTS BARWBNP-110Figure 3.7-13 Sectional Elevation of Diesel Generator Building Lumped Mass Model for Dynamic Analysis SEISMIC DESIGN3.7-180WATTS BARWBNP-110Figure 3.7-13a Seismic Analysis Model for Diesel Generator Building - YZ Plane SEISMIC DESIGN3.7-181WATTS BARWBNP-110Figure 3.7-13b Seismic Analysis Model for Diesel Generator Building - XZ Plane SEISMIC DESIGN3.7-182WATTS BARWBNP-110Figure 3.7-13c Lumped-Mass Stick Model for Refueling Water Storage Tank SEISMIC DESIGN3.7-183WATTS BARWBNP-110Figure 3.7-14 Mathematical Model for Dynamic Analysis of the Waste Packaging Area SEISMIC DESIGN3.7-184WATTS BARWBNP-110Figure 3.7-15 Deleted by Amendment 64 SEISMIC DESIGN3.7-185WATTS BARWBNP-110Figure 3.7-15a Condensate Demineralizer Waste Evaporator Building - Lumped Models for Normal Mode Analysis SEISMIC DESIGN3.7-186WATTS BARWBNP-110Figure 3.7-15b Seismic Analysis Model for Additional Diesel Generator Building - YZ Plane SEISMIC DESIGN3.7-187WATTS BARWBNP-110Figure 3.7-15c Seismic Analysis Model for Additional Diesel Generator Building - XZ Plane SEISMIC DESIGN3.7-188WATTS BARWBNP-110Figure 3.7-15d Auxiliary Control Building - Set A vs. Set B ARS Comparison - OBE North-South El. 692.00 SEISMIC DESIGN3.7-189WATTS BARWBNP-110Figure 3.7-15e Auxiliary Control Building - Set A vs. Set B ARS Comparison - BE East-West El. 692.0 SEISMIC DESIGN3.7-190WATTS BARWBNP-110Figure 3.7-15f Auxiliary Control Building - Set A vs. Set B ARS Comparison - OBE Vertical El. 692.00 SEISMIC DESIGN3.7-191WATTS BARWBNP-110Figure 3.7-15g Auxiliary Control Building - Set A vs. Set B ARS Comparison - OBE North-South El. 814.25 SEISMIC DESIGN3.7-192WATTS BARWBNP-110Figure 3.7-15h Auxiliary Control Building - Set A vs. Set B ARS Comparison - OBE East-West E1. 814.25 SEISMIC DESIGN3.7-193WATTS BARWBNP-110Figure 3.7-15i Auxiliary Control Building - Set A vs. Set B ARS Comparison - OBE Vertical E1. 814.25 SEISMIC DESIGN3.7-194WATTS BARWBNP-110Figure 3.7-16 Deleted - Amendment 64 SEISMIC DESIGN3.7-195WATTS BARWBNP-110Figure 3.7-17 Deleted - Amendment 64 SEISMIC DESIGN3.7-196WATTS BARWBNP-110Figure 3.7-18 Deleted - Amendment 64 SEISMIC DESIGN3.7-197WATTS BARWBNP-110Figure 3.7-19 Deleted - Amendment 64 SEISMIC DESIGN3.7-198WATTS BARWBNP-110Figure 3.7-20 Deleted - Amendment 64 SEISMIC DESIGN3.7-199WATTS BARWBNP-110Figure 3.7-21 Deleted - Amendment 64 SEISMIC DESIGN3.7-200WATTS BARWBNP-110Figure 3.7-22 Deleted - Amendment 64 SEISMIC DESIGN3.7-201WATTS BARWBNP-110Figure 3.7-23 Deleted - Amendment 64 SEISMIC DESIGN3.7-202WATTS BARWBNP-110Figure 3.7-24 Deleted - Amendment 64 SEISMIC DESIGN3.7-203WATTS BARWBNP-110Figure 3.7-25 Deleted - Amendment 64 SEISMIC DESIGN3.7-204WATTS BARWBNP-110Figure 3.7-26 Deleted - Amendment 64 SEISMIC DESIGN3.7-205WATTS BARWBNP-110Figure 3.7-27 Deleted - Amendment 64 SEISMIC DESIGN3.7-206WATTS BARWBNP-110Figure 3.7-28 Deleted - Amendment 64 SEISMIC DESIGN3.7-207WATTS BARWBNP-110Figure 3.7-29 Deleted - Amendment 64 SEISMIC DESIGN3.7-208WATTS BARWBNP-110Figure 3.7-30 Deleted - Amendment 64 SEISMIC DESIGN3.7-209WATTS BARWBNP-110Figure 3.7-31 Deleted - Amendment 64 SEISMIC DESIGN3.7-210WATTS BARWBNP-110Figure 3.7-32 Deleted - Amendment 64 SEISMIC DESIGN3.7-211WATTS BARWBNP-110Figure 3.7-33 Deleted - Amendment 64 SEISMIC DESIGN3.7-212WATTS BARWBNP-110Figure 3.7-34 Deleted - Amendment 64 SEISMIC DESIGN3.7-213WATTS BARWBNP-110Figure 3.7-35 Deleted - Amendment 64 SEISMIC DESIGN3.7-214WATTS BARWBNP-110Figure 3.7-36 Deleted - Amendment 64 SEISMIC DESIGN3.7-215WATTS BARWBNP-110Figure 3.7-37 Flow Chart for Development of Floor Response Spectra SEISMIC DESIGN3.7-216WATTS BARWBNP-110Figure 3.7-38 Deleted - Amendment 64 SEISMIC DESIGN3.7-217WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.7-39 Reactor, Auxiliary, and Control Bldgs. - Seismic InstrumentationLocation of Seismic Instruments and Peripheral Equipment SEISMIC DESIGN3.7-218WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.7-40 Reactor, Auxiliary, and Control BuildingsSeismic Instrumentation Location of Seismic Instruments and Peripheral Equipment SEISMIC DESIGN3.7-219WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.7-41 Diesel Genorator Building Seismic Instrumentation Location of Seismic Instruments and Peripheral Equipment SEISMIC DESIGN3.7-220WATTS BARWBNP-110Figure 3.7-42 Control Building Units 1 and 2 Seismic Instrumentation Location of Seismic Instruments and Peripheral Equipment SEISMIC DESIGN3.7-221WATTS BARWBNP-110Figure 3.7-43 Control Building Units 1 and 2 Seismic Instrumentation Locationof Seismic Instruments and Peripheral Equipment SEISMIC DESIGN3.7-222WATTS BARWBNP-110Security-Related Information - Withheld Under 10CFR2.390Figure 3.7-44 Powerhouse Reactor Unit 1 Seismic Instrumentation Location of Seismic Instruments and Peripheral Equipment SEISMIC DESIGN3.7-223WATTS BARWBNP-110Figure 3.7-45 Powerhouse Reactor Unit 1 Seismic Instrumentation Location of Seismic Instruments and Peripheral Equipment