ENS 43488: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 07/12/2007 16:30 CDT
| event date = 07/12/2007 16:30 CDT
| last update date = 07/12/2007
| last update date = 07/12/2007
| title = Unallowable Manual Actions Credited For Fire Safe Shutdown
| title = Unallowable Manual Actions Credited for Fire Safe Shutdown
| event text = During performance of NFPA-805, Transition Project Task SUP-1, 'Manual Action Compliance,' it was determined manual operator actions are being credited in IX/12-A Lower 4KV Room and XII/14-A Upper 4KV Room to achieve and maintain hot safe shutdown.  The manual actions are to provide temporary ventilation capability to the 4KV rooms to assume continued operability of vital switchgear.  The switchgear provides power to equipment needed to achieve and maintain hot shutdown.  These manual actions were specified in an Appendix R Section III.G.1/G.2 fire area; however, they do not meet the criteria for allowable manual actions specified in RIS 2006-10, 'Regulatory Expectations with Appendix R paragraph III.G.2 Operator Manual Actions.'  No system actuations occurred as part of this event.  
| event text = During performance of NFPA-805, Transition Project Task SUP-1, 'Manual Action Compliance,' it was determined manual operator actions are being credited in IX/12-A Lower 4KV Room and XII/14-A Upper 4KV Room to achieve and maintain hot safe shutdown.  The manual actions are to provide temporary ventilation capability to the 4KV rooms to assume continued operability of vital switchgear.  The switchgear provides power to equipment needed to achieve and maintain hot shutdown.  These manual actions were specified in an Appendix R Section III.G.1/G.2 fire area; however, they do not meet the criteria for allowable manual actions specified in RIS 2006-10, 'Regulatory Expectations with Appendix R paragraph III.G.2 Operator Manual Actions.'  No system actuations occurred as part of this event.  
The discovery of these manual actions is being reported as an unanalyzed condition as defined by 10 CFR 50.72(b)(3)(ii)(B) and has been entered into the site's corrective action program The alternate compensatory measure for these areas is to perform the specified manual actions.  An extent of condition review will be initiated that will encompass the remainder of the safe shutdown areas.  The results of the extent of condition will be documented in the site's corrective action program with compensatory measures being established as appropriate.   
The discovery of these manual actions is being reported as an unanalyzed condition as defined by 10 CFR 50.72(b)(3)(ii)(B) and has been entered into the site's corrective action program The alternate compensatory measure for these areas is to perform the specified manual actions.  An extent of condition review will be initiated that will encompass the remainder of the safe shutdown areas.  The results of the extent of condition will be documented in the site's corrective action program with compensatory measures being established as appropriate.   

Latest revision as of 21:16, 1 March 2018

ENS 43488 +/-
Where
Monticello Xcel Energy icon.png
Minnesota (NRC Region 3)
Reporting
10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition
Time - Person (Reporting Time:+-2.27 h-0.0946 days <br />-0.0135 weeks <br />-0.00311 months <br />)
Opened: Mark Kruse
19:14 Jul 12, 2007
NRC Officer: Pete Snyder
Last Updated: Jul 12, 2007
43488 - NRC Website
Loading map...