ML17229A187: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 13: Line 13:
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE
| page count = 4
| page count = 4
| project =
| stage = Other
}}
=Text=
{{#Wiki_filter:CATEGORY1REGULATI!GINFORMATIONDISTRIBUTIONISTEM.(RIDE)ACCESSIONNBR:9701090061DOC.DATE:97/Ol/07NOTARIZED:NOFACIL:50-389St.LuciePlant,Unit2,FloridaPower6LightCo.AUTH.NAMEAUTHORAFFILIATIONSTALL,J.A.FloridaPower6LightCo.RECIP';NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)DOCKETI05000389
==SUBJECT:==
Respondsto961226telconrequesttoclarifycommitmentforinsulationremovalonboltedconnectionsinClass1systemsaVT-2visualexaminationsIAWw/paragraph(b)ofCodeCaseN-533.DISTRIBUTIONCODE:A047DCOPIESRECEIVED:LTRENCLSIZE:TITLE:ORSubmittal:Inservice/Testing/RelieffromASMCode-GL-89-04NOTES:RECIPIENTIDCODE/NAME'D2-3LAWIENS,L.INTERNAL:ACOCS-ABSTRACTRES/DET/EIBEXTERNAL:LITCOANDERSONNRCPDRCOPIESLTTRENCLRECIPIENTIDCODE/NAMEPD2-3PDAEOD/SPD/RABNRR/DE/EMEBOGC/HDS3RES/DET/EMMEBNOACCOPIESLTTRENCL110DENNOTETOALL"RIDS"RECIPIENTS:PLEASEHELPUSTOREDUCEWASTE!CONTACTTHEDOCUMENTCONTROLDESK,ROOMOWFNSD-5(EXT.415-2083)TOELIMINATEYOURNAMEFROMDISTRIBUTIONLISTSFORDOCUMENTSYOUDON'TNEED!TOTALNUMBEROFCOPIESREQUIRED:LTTR14ENCL.
FloridaPower&LightCompany,P.O.Box128,FortPierce,FL34954-0128January7,1997U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555L-97-410CFR50.410CFR50.55aRe:St.LucieUnit2DocketNo.50-389Inservice-Inspection(ISI)PlanSecondTen-YearIntervalASMECodeCaseN-533-SulementOnNovember19,1996,pursuantto10CFR50.55a,(Footnote6)and10CFR50.55a(a)(3),FloridaPowerandLightCompany(FPL)requestedapprovaltoincorporateCodeCaseN-533,AlternativeRequirementsforVT-2VisualExaminationofClassIInsulatedPressure-RetainingBoltedConnections,SectionXI,DivisionI,foruseintheSt.LucieUnit2Ten-YearInserviceInspectionProgram.TherequestwassubmittedbyFPLletterL-96-304.InatelephonecallonDecember26,1996,theNRCProjectManagerforSt.LucierequestedFPLtoclarifyitscommitmentforinsulationremovalontheboltedconnectionsinClass1systemsandVT-2visualexaminationsinaccordancewithparagraph(b)oftheCodeCase.Eachrefuelingoutage,FPLwillremovetheinsulationfromtheboltedconnectionsinClass1systemsandperformaVT-2visualexaminationinaccordancewithparagraph(b)oftheCodeCase.TheconnectionsarenotrequiredtobepressurizedduringthevisualexaminationandanyevidenceofleakagewillbeevaluatedinaccordancewithIWA-5250.Inadditiontotherequirementsofparagraph(a)oftheCodeCase,thesystempressuretestandVT-2visualexaminationwithinsulationinstalledonboltedjointsatnormaloperatingpressureandtemperature(NOP/NOT)willincludea4-hourholdtimeandwillbecompletedpriortoreturningtheunittoservice.Pleasecontactusifthereareanyadditionalquestions.Verytrulyyours,J.A,StallVicePresidentSt,LuciePlantJAS/GRMcc:RegionalAdministrator,RegionII,USNRCSeniorResidentInspector,USNRC,St.LuciePlantOgoo~p970i0900hi970i07PDRADQCK050003898PDRanFPLGroupcompany pgjI
}}
}}

Revision as of 13:38, 25 April 2018

Responds to 961226 Telcon Request to Clarify Commitment for Insulation Removal on Bolted Connections in Class 1 Systems & VT-2 Visual Examinations IAW W/Paragraph (B) of Code Case N-533
ML17229A187
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 01/07/1997
From: STALL J A
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-97-4, NUDOCS 9701090061
Download: ML17229A187 (4)


Text

CATEGORY1REGULATI!GINFORMATIONDISTRIBUTIONISTEM.(RIDE)ACCESSIONNBR:9701090061DOC.DATE:97/Ol/07NOTARIZED:NOFACIL:50-389St.LuciePlant,Unit2,FloridaPower6LightCo.AUTH.NAMEAUTHORAFFILIATIONSTALL,J.A.FloridaPower6LightCo.RECIP';NAMERECIPIENTAFFILIATIONDocumentControlBranch(DocumentControlDesk)DOCKETI05000389

SUBJECT:

Respondsto961226telconrequesttoclarifycommitmentforinsulationremovalonboltedconnectionsinClass1systemsaVT-2visualexaminationsIAWw/paragraph(b)ofCodeCaseN-533.DISTRIBUTIONCODE:A047DCOPIESRECEIVED:LTRENCLSIZE:TITLE:ORSubmittal:Inservice/Testing/RelieffromASMCode-GL-89-04NOTES:RECIPIENTIDCODE/NAME'D2-3LAWIENS,L.INTERNAL:ACOCS-ABSTRACTRES/DET/EIBEXTERNAL:LITCOANDERSONNRCPDRCOPIESLTTRENCLRECIPIENTIDCODE/NAMEPD2-3PDAEOD/SPD/RABNRR/DE/EMEBOGC/HDS3RES/DET/EMMEBNOACCOPIESLTTRENCL110DENNOTETOALL"RIDS"RECIPIENTS:PLEASEHELPUSTOREDUCEWASTE!CONTACTTHEDOCUMENTCONTROLDESK,ROOMOWFNSD-5(EXT.415-2083)TOELIMINATEYOURNAMEFROMDISTRIBUTIONLISTSFORDOCUMENTSYOUDON'TNEED!TOTALNUMBEROFCOPIESREQUIRED:LTTR14ENCL.

FloridaPower&LightCompany,P.O.Box128,FortPierce,FL34954-0128January7,1997U.S.NuclearRegulatoryCommissionAttn:DocumentControlDeskWashington,D.C.20555L-97-410CFR50.410CFR50.55aRe:St.LucieUnit2DocketNo.50-389Inservice-Inspection(ISI)PlanSecondTen-YearIntervalASMECodeCaseN-533-SulementOnNovember19,1996,pursuantto10CFR50.55a,(Footnote6)and10CFR50.55a(a)(3),FloridaPowerandLightCompany(FPL)requestedapprovaltoincorporateCodeCaseN-533,AlternativeRequirementsforVT-2VisualExaminationofClassIInsulatedPressure-RetainingBoltedConnections,SectionXI,DivisionI,foruseintheSt.LucieUnit2Ten-YearInserviceInspectionProgram.TherequestwassubmittedbyFPLletterL-96-304.InatelephonecallonDecember26,1996,theNRCProjectManagerforSt.LucierequestedFPLtoclarifyitscommitmentforinsulationremovalontheboltedconnectionsinClass1systemsandVT-2visualexaminationsinaccordancewithparagraph(b)oftheCodeCase.Eachrefuelingoutage,FPLwillremovetheinsulationfromtheboltedconnectionsinClass1systemsandperformaVT-2visualexaminationinaccordancewithparagraph(b)oftheCodeCase.TheconnectionsarenotrequiredtobepressurizedduringthevisualexaminationandanyevidenceofleakagewillbeevaluatedinaccordancewithIWA-5250.Inadditiontotherequirementsofparagraph(a)oftheCodeCase,thesystempressuretestandVT-2visualexaminationwithinsulationinstalledonboltedjointsatnormaloperatingpressureandtemperature(NOP/NOT)willincludea4-hourholdtimeandwillbecompletedpriortoreturningtheunittoservice.Pleasecontactusifthereareanyadditionalquestions.Verytrulyyours,J.A,StallVicePresidentSt,LuciePlantJAS/GRMcc:RegionalAdministrator,RegionII,USNRCSeniorResidentInspector,USNRC,St.LuciePlantOgoo~p970i0900hi970i07PDRADQCK050003898PDRanFPLGroupcompany pgjI