Line 17: |
Line 17: |
|
| |
|
| =Text= | | =Text= |
| {{#Wiki_filter:ENCLOSURE 1 PROPOSED TECHNICAL SPECIFICATION REVISIONS BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 (TVA BFNP TS 215)/agggPP0535 8 pgp>QOCK 050@gal t 0' | | {{#Wiki_filter:ENCLOSURE 1 PROPOSED TECHNICAL SPECIFICATION REVISIONS BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 (TVA BFNP TS 215) |
| PROPOSED CHANGES UNIT 1 1J LIMITING CONDITIONS FOR OPERATION F 11 FIRE PROTECTION SYSTEMS SURVEILLANCE REQUIREMENT 4.11 FIRE PROTECTION SYSTEMS 3.The class A sunervised detector alarm circuits will be tested once earth two months at the local panels.4.The circuits between the local panels in 4.1I.C.'3,and the main control room will be tested monthly.5.Smoke detector sensitivity will be checked annually.D.ROVING FIRE HATCH D ROVING FIRE 1'1ATCB A roving fire watch will tour each area in which automatic fire supnression systems are to be installed (as described in,the"Plan for Evaluation, Repair, and Return to Service of Hrowns Ferry Units 1 and 2," Section X)at intervals no greater than 2 hours.A keycloclc recording type system shall be used to monitor the routes of the roving fire watch.The patrol will be discontinued as the automatic suppression systems are installed and made"operable for, each specified area.A monthlv walk-through bv the Safety Engineer will.'e made to visually inspect the plant fire protection system for signs of damage, deterioration, or abnormal conditions which could'jeopardize proper, operation of, the system.321 e
| | / |
| PROPOSED CHANGES UNIT 2
| | agggPP0535 8050 pgp >QOCK @gal t |
|
| |
|
| LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT 3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS 3.The class A sunervised detector alarm circuits will be tested on'e.each two months at the local panels.4.The circuits between the local panels in, 4.11.C.3 and the.main control room will be tested monthly.5.Smoke detector sensitivity mill be checked annually.D.ROVING FIRE HATCH'D,~ROVING FIRE NATCH A'roving fire watch will tour each area in which automatic fire supnression systems are to be installed (as described in the"Plan for Evaluation, Repair, and Return to Service.of Browns Ferry Units 1 and 2," Section X)at intervals no greater than'2 hours.A lceyclock recording type system shall be ,used to.monitor the routes of the roving fire watch.The patrol will be discontinued as the automatic suppression | | 0 |
| 'systems are installed and made'operable for.each snecified area.A monthly walk-through by.the Safety Engineer will be made to visually inspect the plant fire protection system for signs of damage, deterioration, or abnormal conditions which could"jeopardize nroper.operation of the svstem.321 PROPOSED CHANGES UNIT 3 h li LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT 3.11 FIRE PROTECTION SYSTEMS 4.11 I FIRE PROTECTION SYSTEMS'.The class A sunervised detector alarm circuits will be tested once each two months at the local panels.4.The circuits betwee'n the local panels in 4.11';C.3 and the main control room will be tested monthly.5.Smoke detector sen'sitivity vill be checlced annually.D.'OVING FIRE HATCH 1 A roving fire watch vill tour each area in which automatic fire supnression systems are to be installed (as described in the"Plan for Evaluation, Repair, and Return to Service of Browns Ferry Units 1 and 2," Section X)at intervals no greater than 2 hours.A Iceyclock recording type system shall be used to monitor the routes of the roving fire watch.The patrol vill be discontinued as the automatic suppression systems are installed and made operable for.each sn ec if ied area.'DE ROVING FIRE NATCH A monthly walk-through by.the Safety Engineer vill.'e made to, visually inspect the plant Are protection system for signs of damage, deterioration, or-abnormal conditions vhich could"jeopardize nrooer-operation of the system.353 1 Description and Justification (TVA BFNP TS 215)Delete the por tion of Technical Specifioation (T.S.)Surveillance 4.11.C.5 which requires annual sensitivity check of smoke detectors in accordance with manufacturer instruction for units 1, 2 and 3.Some types of smoke detectors used at Browns Ferry lack current vendor information and test equipment for checking sensitivity because the type of detector is no longer being produced.This situation prevents.strict, application of T.S.4.11.C.5 to this type of detector and resulted in'a violation (Office of Inspection and Enforcement Inspection Report number 50-260/85-28)
| | ' |
| ~The proposed T.S.amendment will not eliminate or modify any protective functions nor permit any new operational conditions since it only deletes an inappropriate restriction on the surveillance requirement; It does not'reate the possibility of a new kind of acoident or significantly increasethe probability or consequences of an accident previously evaluated since no equipment modifications, instruction changes or oper ational changes are made.Furthermore, this change does not result in the significant reduction of any safety margin since it is administrative in natur'e and does not alter the intent of the surveillance requirement.
| | |
| Therefore, the'mendment will not adversely effect plant safety. | | PROPOSED CHANGES UNIT 1 |
| Il) | | |
| Fnclosure 3 Determination of No Significant Hazards Consideration=.(TVA BFNP TS 215)The proposed amendment would delete from the technical specifications (T.S.)of the operating license, the phrase,"in accordance with manufacturer~s-instruction" from the requirement to annually check smoke=detector sensitivity. | | 1J LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT F 11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS |
| This is not possible in all cases due to the fact that some smoke detector models are no longer in production and there is an unavailability of vendor supplied test equipment. | | : 3. The class A sunervised detector alarm circuits will be tested once earth two months at the local panels. |
| The proposed T.S.amendment will not eliminate or modify any protective funotions nor permit any new operational conditions since it only deletes an inappropriate restriction on the surveillance requirement. | | : 4. The circuits between the local panels in 4.1I.C.'3,and the main control room will be tested monthly. |
| Zt does not create the possibility of a new kind of accident or significantly increase the probability or consequences of an accident previously evaluated since no equipment modifications, instruction changes or operational changes are made.Furthermore, this change does not result in the significant reduction of any safety margin since it is administrative in nature and does'ot alter the intent of the surveillance requirement. | | : 5. Smoke detector sensitivity will be checked annually. |
| Therefore, TVA proposes to determine that the requested amendment does not involve a significant hazards consideration.}} | | D. ROVING FIRE HATCH D ROVING FIRE 1'1ATCB A roving fire watch will tour A monthlv walk-through bv each area in which automatic the Safety Engineer will. |
| | fire made to visually inspect |
| | 'e supnression systems are to be installed (as described the plant fire protection in,the "Plan for Evaluation, system for signs of damage, Repair, and Return to Service deterioration, or abnormal of Hrowns Ferry Units 1 and 2," conditions which could Section X) at intervals no greater 'jeopardize proper, operation than 2 hours. A keycloclc of, the system. |
| | recording type system shall be used to monitor the routes of the roving fire watch. The patrol will be discontinued as the automatic suppression systems are installed and made "operable for, each specified area. |
| | 321 |
| | |
| | e PROPOSED CHANGES UNIT 2 |
| | |
| | LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT 3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS |
| | : 3. The class A sunervised detector alarm circuits will be tested on'e. each two months at the local panels. |
| | : 4. The circuits between the local panels in, 4.11.C.3 and the. main control room will be tested monthly. |
| | : 5. Smoke detector sensitivity mill be checked annually. |
| | D. ROVING FIRE HATCH 'D, ~ ROVING FIRE NATCH A'roving fire watch will tour A monthly walk-through by each area in which automatic .the Safety Engineer will fire supnression systems are be made to visually inspect to be installed (as described the plant fire protection in the "Plan for Evaluation, system for signs of damage, Repair, and Return to Service deterioration, or abnormal |
| | .of Browns Ferry Units 1 and 2," conditions which could Section X) at intervals no greater "jeopardize nroper.operation than '2 hours. A lceyclock of the svstem. |
| | recording type system shall be |
| | ,used to .monitor the routes of the roving fire watch. The patrol will be discontinued as the automatic suppression |
| | 'systems are installed and made |
| | 'operable for. each snecified area. |
| | 321 |
| | |
| | PROPOSED CHANGES UNIT 3 |
| | |
| | h li |
| | |
| | LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT 3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS I |
| | '. The class A sunervised detector alarm circuits will be tested once each two months at the local panels. |
| | : 4. The circuits betwee'n the local panels in 4.11';C.3 and the main control room will be tested monthly. |
| | : 5. Smoke detector sen'sitivity vill be checlced annually. |
| | D. 'OVING FIRE HATCH 'DE ROVING FIRE NATCH 1 |
| | A roving fire watch vill tour A monthly walk-through by vill. |
| | each area in which automatic .the Safety Engineer made to, visually inspect |
| | 'e fire supnression systems are to be installed (as described the plant Are protection in the "Plan for Evaluation, system for signs of damage, Repair, and Return to Service deterioration, or- abnormal of Browns Ferry Units 1 and 2," conditions vhich could Section X) at intervals no greater "jeopardize nrooer- operation than 2 hours. A Iceyclock of the system. |
| | recording type system shall be used to monitor the routes of the roving fire watch. The patrol vill be discontinued as the automatic suppression systems are installed and made operable for. each sn ec ified area. |
| | 353 |
| | |
| | 1 Enclosure 2 Description and Justification (TVA BFNP TS 215) |
| | Delete the por tion of Technical Specifioation (T.S.) Surveillance 4.11.C.5 which requires annual sensitivity check of smoke detectors in accordance with manufacturer instruction for units 1, 2 and 3. |
| | Some types of smoke detectors used at Browns Ferry lack current vendor information and test equipment for checking sensitivity because the type of detector is no longer being produced. This situation prevents. strict , |
| | application of T.S. 4.11.C.5 to this type of detector and resulted in 'a violation (Office of Inspection and Enforcement Inspection Report number 50-260/85-28) ~ |
| | The proposed T.S. amendment will not eliminate or modify any protective functions nor permit any new operational conditions since an inappropriate restriction on the surveillance requirement; it only deletes It does not |
| | 'reate the possibility of a new kind of acoident or significantly increase the probability or consequences of an accident previously evaluated since no equipment modifications, instruction changes or oper ational changes are made. Furthermore, this change does not result in the significant reduction of any safety margin since it is administrative in natur'e and does not alter the intent of the surveillance requirement. Therefore, will not adversely effect plant safety. the'mendment |
| | |
| | Il |
| | ) |
| | |
| | Fnclosure 3 Determination of No Significant Hazards Consideration=. |
| | (TVA BFNP TS 215) |
| | The proposed amendment would delete from the technical specifications (T.S.) of the operating license, the phrase, "in accordance with manufacturer~s-instruction" from the requirement to annually check smoke = |
| | detector sensitivity. This is not possible in all cases due to the fact that some smoke detector models are no longer in production and there is an unavailability of vendor supplied test equipment. |
| | The proposed T.S. amendment will not eliminate or modify any protective funotions nor permit any new operational conditions since an inappropriate restriction on the surveillance requirement. |
| | it only deletes Zt does not create the possibility of a new kind of accident or significantly increase the probability or consequences of an accident previously evaluated since no equipment modifications, instruction changes or operational changes are made. Furthermore, this change does not result in the significant reduction of any safety margin since it is administrative in nature and does'ot alter the intent of the surveillance requirement. Therefore, TVA proposes to determine that the requested amendment does not involve a significant hazards consideration.}} |
Proposed Tech Spec Changes Deleting Requirement to Check Smoke Detector Sensitivity in Accordance W/Mfg Instructions. Description & Justification & Determination of NSHC EnclML18030A905 |
Person / Time |
---|
Site: |
Browns Ferry |
---|
Issue date: |
11/20/1985 |
---|
From: |
TENNESSEE VALLEY AUTHORITY |
---|
To: |
|
---|
Shared Package |
---|
ML18030A904 |
List: |
---|
References |
---|
NUDOCS 8512020535 |
Download: ML18030A905 (17) |
|
|
---|
Category:TECHNICAL SPECIFICATIONS
MONTHYEARML18039A8811999-09-28028 September 1999 Proposed Tech Specs Re Increased MSIV Leakage Rate Limits & Exemption from 10CFR50,App J ML18039A8241999-07-28028 July 1999 Proposed Tech Specs Providing TS for Operation of Oscillation PRM Upscale Trip Function in Aprm,Which Is Part of Power Range Neutron Monitoring Sys ML18039A8001999-06-0303 June 1999 Proposed Tech Specs,Reducing Allowable Value Used for Reactor Vessel Water Level - Low,Level 3 for Several Instrument Functions ML18039A6991999-02-22022 February 1999 Proposed Tech Specs & Bases Pages Incorporating NRC Approved TS Change 354,requiring Oscillation PRM to Be Integrated Into Approved Power uprate,24-month Operating Cycle & Single Recirculation Loop Operation ML18039A6601998-12-15015 December 1998 Proposed Tech Specs,Revising pressure-temp Curves to Extend Validity of Curves to 32 EFPY ML18039A5041998-09-0808 September 1998 Proposed Tech Specs Providing TS for Operation of Oscillation Power Range Monitor Upscale Trip Function in Aprm,Which Is Part of Power Range Neutron Monitoring Sys ML18039A5001998-09-0404 September 1998 Proposed Tech Specs Re Use of Containment Overpressure for ECCS Pump Net Positive Suction Head Analyses ML18039A4791998-08-14014 August 1998 Proposed Tech Specs Pages Re Amends to Licenses DPR-33, DPR-52 & DPR-68 to Change Ts.Proposed Changes Decrease Frequency of once-per-cycle Instrument Calibrations by Substituting 24 Months for 18 Months ML18039A4611998-07-31031 July 1998 Proposed Tech Specs B 3.6-2,B 3.6-7 & B 3 3.7-2 for Power Uprate Operation Omitted Pages ML18039A4481998-07-17017 July 1998 Proposed Tech Specs,Adding LCO 3.4.10 & Accompanying TS Bases Provisions from Improved TS-362 Conversion Package as Adapted for Power Uprate Conditions ML18039A4091998-06-26026 June 1998 Proposed Tech Specs Section 3.4,allowing Units 2 & 3 to Operate at Uprated Power Level of 3458 Mwt ML18039A4021998-06-19019 June 1998 Proposed Tech Specs (TS) Converting from Existing Custom TS to Improved TS ML18039A3921998-06-12012 June 1998 Proposed Tech Specs Change 390,decreasing Frequency of once-per-cycle SRs by Substituting 24 Months for 18 Months in Affected TS SRs ML20249A5661998-06-10010 June 1998 Proposed Tech Specs Section 5.0,revising Administrative Controls ML20248C5151998-05-27027 May 1998 Proposed Tech Specs Section 3.8.1,revising AC Sources- Operating ML18039A3181998-04-16016 April 1998 Proposed Rev 2 to Tech Specs Section 3.6, Containment Systems, Converting from Current TS to Improved TS ML18039A2711998-03-16016 March 1998 Proposed Tech Specs Re Power Uprate Operation ML18039A2671998-03-13013 March 1998 Proposed Tech Specs,Converting to Improved Std Ts,Per NUREG- 1433,rev 1, Std TS for GE BWRs (BWR/4). ML18039A2641998-03-12012 March 1998 Proposed Tech Specs ITS Section 3.8 Re Electrical Power Sys. ML18039A2611998-03-0303 March 1998 Proposed Tech Spec Changes TS 393 Re Reactor Vessel Pressure Temperature Curves ML20199E8051998-01-23023 January 1998 Proposed Tech Specs Section 5.0 Re Administrative Controls ML18039A2221997-12-30030 December 1997 Proposed Tech Specs Re RHR SW Pumps Required for multi-unit Operation & Cold Shutdown ML18039A2151997-12-23023 December 1997 Proposed Tech Specs Section 3.7 Re Plant Sys ML18039A2181997-12-22022 December 1997 Proposed Tech Specs Section 3.8 Re Electrical Power Sys ML18039A2101997-12-0404 December 1997 Proposed Tech Specs Pages Re TS Change 362,suppl 7 Re ITS Section 3.1, Reactivity Control Sys. ML18039A2071997-12-0404 December 1997 Proposed Tech Specs Pages Re Suppl 9 to TS Change 362, Including Rev Pages to Improved TS Section 3.5 ML18039A2011997-12-0303 December 1997 Proposed Tech Specs Section 3.9 Re Refueling Operations & Section 3.10, Special Operations. ML18039A1981997-12-0303 December 1997 Improved Tech Specs Pages Re Section 5, Administrative Controls. ML20199D5471997-11-14014 November 1997 Proposed Tech Specs Section 3.0, Limiting Condition for Operation (LCO) Operability & Section 4.0, Design Changes ML20199E1361997-11-14014 November 1997 Proposed Tech Specs Section 3.4 Re Reactor Coolant Sys ML20198Q4521997-11-0505 November 1997 Proposed Tech Specs,Incorporating Improved TS (ITS) Bases Revs & Changes to Supporting Documentation Resulting from Responding to NRC Questions ML18038B9611997-10-0101 October 1997 Proposed Tech Specs,Allowing Bfn,Units 2 & 3,to Operate at Uprated Power Level of 3458 Mwt ML18038B9361997-08-15015 August 1997 Proposed Tech Specs,Extending Existing 7-day EDG Allowed Outage Time to Fourteen Days ML18038B9061997-06-19019 June 1997 Proposed Tech Specs Supporting one-time 14-day Limiting Condition for Operation for Each EDG to Accommodate Pending Vendor Recommended Maint Activities ML20138J3781997-05-0101 May 1997 Proposed Tech Specs,Revising TS-362 Amend for Section 3.8, Electrical Power Sys Which Addresses NRC Review Comments ML18038B8651997-04-24024 April 1997 Proposed Tech Specs,Submitting Revised BFN TS Bases Section 3.5.N, References, Reflecting Updated LOCA Analyses for Units 2 & 3 ML20137U1691997-04-11011 April 1997 Proposed Tech Specs Re Pr Neutron Monitor Upgrade W/ Implementation of Average Pr Monitor & Rod Block Monitor TS (ARTS) Improvements & Max Extended Load Line Limit Analyses ML18038B8341997-03-12012 March 1997 Proposed Tech Specs Re Extended EDG Allowed Outage Time ML20136F7851997-03-0606 March 1997 Proposed TS Supporting Planned Replacement of Current Power Range Monitoring Portion of Existing Nms W/Ge Digital Nuclear Measurement Analysis & Control Power Range Neutron Monitor Retrofit Design ML20134G5401997-02-0505 February 1997 Proposed Tech Specs Revising Bases Section 3.7.A/4.7.A, Primary Containment, to Delete Wording Re Maintaining Drywell to Suppression Chamber Differential Pressure Constant for Duration of Drywell to Suppression Chamber ML20132B7401996-12-11011 December 1996 Proposed Tech Specs 2.2.A Re Safety/Relief Valve Setpoint Requirements for Reactor Coolant Sys Integrity ML20117P3341996-09-15015 September 1996 Proposed Tech Specs to Change Unit 3 TS LCO 3.6.F.1 in Order to Perform Repairs & Maint Necessary to Return RCS Recirculation Loop a to Operations ML18038B7541996-09-0606 September 1996 Proposed Conversion from Current TSs to Improved STS Consistent w/NUREG-1433,rev 1 ML20117G7121996-08-30030 August 1996 Proposed Tech Specs Re License Condition on Compliance W/Thermal Water Quality Stds ML20113B1951996-06-21021 June 1996 Proposed Tech Specs,Revising Change in SLMCPR & Bases Description of RHR Suppl Fuel Pool Cooling Mode ML20112G3891996-06-0606 June 1996 Proposed Tech Specs,Revising Section 6, Administrative Controls, to Be More Closely Aligned W/Requirements of Improved Std TSs ML20117H5231996-05-20020 May 1996 Proposed Tech Specs Implementing Guidance of GL 87-09 & NUREG-1433,Rev 1 ML20108D9021996-05-0303 May 1996 Proposed Tech Specs,Withdrawing Amend 219,temporary TS 343T, Rv Water Level Instrumentation & Amend 228,temporary TS 347T,250 Volt DC Control Power Supply Sys AOT for Unit 2 ML20107F9721996-04-14014 April 1996 Proposed Tech Specs,Revising Minimum Required Number of Operable Rv Water Level Trip Sys During Period That RCS Instrument Line Excess Flow Check Valve Surveillance Tests Being Performed ML20096C4401996-01-10010 January 1996 Proposed Tech Specs Re Implementation of 10CFR50,App J, Option B,Performance Based Testing 1999-09-28
[Table view] Category:TECHNICAL SPECIFICATIONS & TEST REPORTS
MONTHYEARML18039A8811999-09-28028 September 1999 Proposed Tech Specs Re Increased MSIV Leakage Rate Limits & Exemption from 10CFR50,App J ML18039A8241999-07-28028 July 1999 Proposed Tech Specs Providing TS for Operation of Oscillation PRM Upscale Trip Function in Aprm,Which Is Part of Power Range Neutron Monitoring Sys ML18039A8001999-06-0303 June 1999 Proposed Tech Specs,Reducing Allowable Value Used for Reactor Vessel Water Level - Low,Level 3 for Several Instrument Functions ML18039A6991999-02-22022 February 1999 Proposed Tech Specs & Bases Pages Incorporating NRC Approved TS Change 354,requiring Oscillation PRM to Be Integrated Into Approved Power uprate,24-month Operating Cycle & Single Recirculation Loop Operation ML18039A6601998-12-15015 December 1998 Proposed Tech Specs,Revising pressure-temp Curves to Extend Validity of Curves to 32 EFPY ML20206F8131998-12-0303 December 1998 Rev 12 to ODCM, for BFN ML18039A5041998-09-0808 September 1998 Proposed Tech Specs Providing TS for Operation of Oscillation Power Range Monitor Upscale Trip Function in Aprm,Which Is Part of Power Range Neutron Monitoring Sys ML18039A5001998-09-0404 September 1998 Proposed Tech Specs Re Use of Containment Overpressure for ECCS Pump Net Positive Suction Head Analyses ML18039A4791998-08-14014 August 1998 Proposed Tech Specs Pages Re Amends to Licenses DPR-33, DPR-52 & DPR-68 to Change Ts.Proposed Changes Decrease Frequency of once-per-cycle Instrument Calibrations by Substituting 24 Months for 18 Months ML18039A4611998-07-31031 July 1998 Proposed Tech Specs B 3.6-2,B 3.6-7 & B 3 3.7-2 for Power Uprate Operation Omitted Pages ML18039A4481998-07-17017 July 1998 Proposed Tech Specs,Adding LCO 3.4.10 & Accompanying TS Bases Provisions from Improved TS-362 Conversion Package as Adapted for Power Uprate Conditions ML18039A4091998-06-26026 June 1998 Proposed Tech Specs Section 3.4,allowing Units 2 & 3 to Operate at Uprated Power Level of 3458 Mwt ML18039A4021998-06-19019 June 1998 Proposed Tech Specs (TS) Converting from Existing Custom TS to Improved TS ML18039A3921998-06-12012 June 1998 Proposed Tech Specs Change 390,decreasing Frequency of once-per-cycle SRs by Substituting 24 Months for 18 Months in Affected TS SRs ML20249A5661998-06-10010 June 1998 Proposed Tech Specs Section 5.0,revising Administrative Controls ML20248C5151998-05-27027 May 1998 Proposed Tech Specs Section 3.8.1,revising AC Sources- Operating ML18039A3181998-04-16016 April 1998 Proposed Rev 2 to Tech Specs Section 3.6, Containment Systems, Converting from Current TS to Improved TS ML18039A2711998-03-16016 March 1998 Proposed Tech Specs Re Power Uprate Operation ML18039A2671998-03-13013 March 1998 Proposed Tech Specs,Converting to Improved Std Ts,Per NUREG- 1433,rev 1, Std TS for GE BWRs (BWR/4). ML18039A2641998-03-12012 March 1998 Proposed Tech Specs ITS Section 3.8 Re Electrical Power Sys. ML18039A2611998-03-0303 March 1998 Proposed Tech Spec Changes TS 393 Re Reactor Vessel Pressure Temperature Curves ML20199E8051998-01-23023 January 1998 Proposed Tech Specs Section 5.0 Re Administrative Controls ML18039A2401998-01-15015 January 1998 Bfnp Unit 2 Cycle 10 Power Ascension Test Program Start-Up Rept, for Period 970929-1105 ML18039A2221997-12-30030 December 1997 Proposed Tech Specs Re RHR SW Pumps Required for multi-unit Operation & Cold Shutdown ML18039A2151997-12-23023 December 1997 Proposed Tech Specs Section 3.7 Re Plant Sys ML18039A2181997-12-22022 December 1997 Proposed Tech Specs Section 3.8 Re Electrical Power Sys ML20217P5051997-12-0808 December 1997 Rev 10 to ODCM, Containing Markups to Rev 9 & 10 ML18039A2101997-12-0404 December 1997 Proposed Tech Specs Pages Re TS Change 362,suppl 7 Re ITS Section 3.1, Reactivity Control Sys. ML18039A2071997-12-0404 December 1997 Proposed Tech Specs Pages Re Suppl 9 to TS Change 362, Including Rev Pages to Improved TS Section 3.5 ML18039A2011997-12-0303 December 1997 Proposed Tech Specs Section 3.9 Re Refueling Operations & Section 3.10, Special Operations. ML18039A1981997-12-0303 December 1997 Improved Tech Specs Pages Re Section 5, Administrative Controls. ML20199D5471997-11-14014 November 1997 Proposed Tech Specs Section 3.0, Limiting Condition for Operation (LCO) Operability & Section 4.0, Design Changes ML20199E1361997-11-14014 November 1997 Proposed Tech Specs Section 3.4 Re Reactor Coolant Sys ML20198Q4521997-11-0505 November 1997 Proposed Tech Specs,Incorporating Improved TS (ITS) Bases Revs & Changes to Supporting Documentation Resulting from Responding to NRC Questions ML18038B9611997-10-0101 October 1997 Proposed Tech Specs,Allowing Bfn,Units 2 & 3,to Operate at Uprated Power Level of 3458 Mwt ML18038B9361997-08-15015 August 1997 Proposed Tech Specs,Extending Existing 7-day EDG Allowed Outage Time to Fourteen Days ML20210V1171997-07-29029 July 1997 Qualification Plan & Rept MIL-STD-462D,CS114,Conducted Susceptibility,Bulk Cable Injection Numac Reactor Bldg Vents Radiation Monitor TVA Bfn,Units 1,2 & 3 ML18038B9061997-06-19019 June 1997 Proposed Tech Specs Supporting one-time 14-day Limiting Condition for Operation for Each EDG to Accommodate Pending Vendor Recommended Maint Activities ML20138J3781997-05-0101 May 1997 Proposed Tech Specs,Revising TS-362 Amend for Section 3.8, Electrical Power Sys Which Addresses NRC Review Comments ML18038B8651997-04-24024 April 1997 Proposed Tech Specs,Submitting Revised BFN TS Bases Section 3.5.N, References, Reflecting Updated LOCA Analyses for Units 2 & 3 ML20137U1691997-04-11011 April 1997 Proposed Tech Specs Re Pr Neutron Monitor Upgrade W/ Implementation of Average Pr Monitor & Rod Block Monitor TS (ARTS) Improvements & Max Extended Load Line Limit Analyses ML18038B8341997-03-12012 March 1997 Proposed Tech Specs Re Extended EDG Allowed Outage Time ML20136F7851997-03-0606 March 1997 Proposed TS Supporting Planned Replacement of Current Power Range Monitoring Portion of Existing Nms W/Ge Digital Nuclear Measurement Analysis & Control Power Range Neutron Monitor Retrofit Design ML20134G5401997-02-0505 February 1997 Proposed Tech Specs Revising Bases Section 3.7.A/4.7.A, Primary Containment, to Delete Wording Re Maintaining Drywell to Suppression Chamber Differential Pressure Constant for Duration of Drywell to Suppression Chamber ML18038B8281997-01-31031 January 1997 Rev 1 to GE-NE-B13-01805-22, Internal Core Spray Line Flaw Evaluation Handbook for Browns Ferry Units 2 & 3. ML18038B8111997-01-22022 January 1997 Rev 0 to Browns Ferry Nuclear Plant,Surveillance Instruction,Inservice Insp Program,Unit 3. ML20132B7401996-12-11011 December 1996 Proposed Tech Specs 2.2.A Re Safety/Relief Valve Setpoint Requirements for Reactor Coolant Sys Integrity ML20117P3341996-09-15015 September 1996 Proposed Tech Specs to Change Unit 3 TS LCO 3.6.F.1 in Order to Perform Repairs & Maint Necessary to Return RCS Recirculation Loop a to Operations ML18038B7541996-09-0606 September 1996 Proposed Conversion from Current TSs to Improved STS Consistent w/NUREG-1433,rev 1 ML20117G7121996-08-30030 August 1996 Proposed Tech Specs Re License Condition on Compliance W/Thermal Water Quality Stds 1999-09-28
[Table view] |
Text
ENCLOSURE 1 PROPOSED TECHNICAL SPECIFICATION REVISIONS BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 (TVA BFNP TS 215)
/
agggPP0535 8050 pgp >QOCK @gal t
0
'
PROPOSED CHANGES UNIT 1
1J LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT F 11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS
- 3. The class A sunervised detector alarm circuits will be tested once earth two months at the local panels.
- 4. The circuits between the local panels in 4.1I.C.'3,and the main control room will be tested monthly.
- 5. Smoke detector sensitivity will be checked annually.
D. ROVING FIRE HATCH D ROVING FIRE 1'1ATCB A roving fire watch will tour A monthlv walk-through bv each area in which automatic the Safety Engineer will.
fire made to visually inspect
'e supnression systems are to be installed (as described the plant fire protection in,the "Plan for Evaluation, system for signs of damage, Repair, and Return to Service deterioration, or abnormal of Hrowns Ferry Units 1 and 2," conditions which could Section X) at intervals no greater 'jeopardize proper, operation than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. A keycloclc of, the system.
recording type system shall be used to monitor the routes of the roving fire watch. The patrol will be discontinued as the automatic suppression systems are installed and made "operable for, each specified area.
321
e PROPOSED CHANGES UNIT 2
LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT 3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS
- 3. The class A sunervised detector alarm circuits will be tested on'e. each two months at the local panels.
- 4. The circuits between the local panels in, 4.11.C.3 and the. main control room will be tested monthly.
- 5. Smoke detector sensitivity mill be checked annually.
D. ROVING FIRE HATCH 'D, ~ ROVING FIRE NATCH A'roving fire watch will tour A monthly walk-through by each area in which automatic .the Safety Engineer will fire supnression systems are be made to visually inspect to be installed (as described the plant fire protection in the "Plan for Evaluation, system for signs of damage, Repair, and Return to Service deterioration, or abnormal
.of Browns Ferry Units 1 and 2," conditions which could Section X) at intervals no greater "jeopardize nroper.operation than '2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. A lceyclock of the svstem.
recording type system shall be
,used to .monitor the routes of the roving fire watch. The patrol will be discontinued as the automatic suppression
'systems are installed and made
'operable for. each snecified area.
321
PROPOSED CHANGES UNIT 3
h li
LIMITING CONDITIONS FOR OPERATION SURVEILLANCE REQUIREMENT 3.11 FIRE PROTECTION SYSTEMS 4.11 FIRE PROTECTION SYSTEMS I
'. The class A sunervised detector alarm circuits will be tested once each two months at the local panels.
- 4. The circuits betwee'n the local panels in 4.11';C.3 and the main control room will be tested monthly.
- 5. Smoke detector sen'sitivity vill be checlced annually.
D. 'OVING FIRE HATCH 'DE ROVING FIRE NATCH 1
A roving fire watch vill tour A monthly walk-through by vill.
each area in which automatic .the Safety Engineer made to, visually inspect
'e fire supnression systems are to be installed (as described the plant Are protection in the "Plan for Evaluation, system for signs of damage, Repair, and Return to Service deterioration, or- abnormal of Browns Ferry Units 1 and 2," conditions vhich could Section X) at intervals no greater "jeopardize nrooer- operation than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. A Iceyclock of the system.
recording type system shall be used to monitor the routes of the roving fire watch. The patrol vill be discontinued as the automatic suppression systems are installed and made operable for. each sn ec ified area.
353
1 Enclosure 2 Description and Justification (TVA BFNP TS 215)
Delete the por tion of Technical Specifioation (T.S.) Surveillance 4.11.C.5 which requires annual sensitivity check of smoke detectors in accordance with manufacturer instruction for units 1, 2 and 3.
Some types of smoke detectors used at Browns Ferry lack current vendor information and test equipment for checking sensitivity because the type of detector is no longer being produced. This situation prevents. strict ,
application of T.S. 4.11.C.5 to this type of detector and resulted in 'a violation (Office of Inspection and Enforcement Inspection Report number 50-260/85-28) ~
The proposed T.S. amendment will not eliminate or modify any protective functions nor permit any new operational conditions since an inappropriate restriction on the surveillance requirement; it only deletes It does not
'reate the possibility of a new kind of acoident or significantly increase the probability or consequences of an accident previously evaluated since no equipment modifications, instruction changes or oper ational changes are made. Furthermore, this change does not result in the significant reduction of any safety margin since it is administrative in natur'e and does not alter the intent of the surveillance requirement. Therefore, will not adversely effect plant safety. the'mendment
Il
)
Fnclosure 3 Determination of No Significant Hazards Consideration=.
(TVA BFNP TS 215)
The proposed amendment would delete from the technical specifications (T.S.) of the operating license, the phrase, "in accordance with manufacturer~s-instruction" from the requirement to annually check smoke =
detector sensitivity. This is not possible in all cases due to the fact that some smoke detector models are no longer in production and there is an unavailability of vendor supplied test equipment.
The proposed T.S. amendment will not eliminate or modify any protective funotions nor permit any new operational conditions since an inappropriate restriction on the surveillance requirement.
it only deletes Zt does not create the possibility of a new kind of accident or significantly increase the probability or consequences of an accident previously evaluated since no equipment modifications, instruction changes or operational changes are made. Furthermore, this change does not result in the significant reduction of any safety margin since it is administrative in nature and does'ot alter the intent of the surveillance requirement. Therefore, TVA proposes to determine that the requested amendment does not involve a significant hazards consideration.