ENS 40522: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 02/15/2004 15:19 CST
| event date = 02/15/2004 15:19 CST
| last update date = 02/16/2004
| last update date = 02/16/2004
| title = Automatic Reactor Trip With Auxiliary Feedwater Actuation
| title = Automatic Reactor Trip with Auxiliary Feedwater Actuation
| event text = The following information was received from the licensee via facsimile:
| event text = The following information was received from the licensee via facsimile:
At 1519 [CDT] on 2-15-04, the plant was at 20 power, increasing load.  During the transfer from the bypass feedwater regulating valves to the main feedwater regulating valves, the main turbine tripped due to a P-14 S/G Hi-Hi level signal.  The P-14 signal also caused a Feedwater Isolation Signal (FWIS), which resulted in a Motor Driven Aux Feedwater Actuation (MDAFAS), and Steam Generator Blowdown Isolation Signal.
At 1519 [CDT] on 2-15-04, the plant was at 20 power, increasing load.  During the transfer from the bypass feedwater regulating valves to the main feedwater regulating valves, the main turbine tripped due to a P-14 S/G Hi-Hi level signal.  The P-14 signal also caused a Feedwater Isolation Signal (FWIS), which resulted in a Motor Driven Aux Feedwater Actuation (MDAFAS), and Steam Generator Blowdown Isolation Signal.

Latest revision as of 21:24, 1 March 2018

ENS 40522 +/-
Where
Callaway Ameren icon.png
Missouri (NRC Region 4)
Reporting
10 CFR 50.72(b)(2)(iv)(B), RPS Actuation

10 CFR 50.72(b)(3)(iv)(A), System Actuation
Time - Person (Reporting Time:+-1.02 h-0.0425 days <br />-0.00607 weeks <br />-0.0014 months <br />)
Opened: Hope Bradley
20:18 Feb 15, 2004
NRC Officer: Howie Crouch
Last Updated: Feb 16, 2004
40522 - NRC Website
Loading map...