ML20004F119: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(No difference)

Revision as of 14:37, 29 January 2020

to Pump Inservice Testing Program
ML20004F119
Person / Time
Site: Oconee, Mcguire, McGuire  Duke Energy icon.png
Issue date: 06/08/1981
From:
DUKE POWER CO.
To:
Shared Package
ML20004F116 List:
References
PROC-810608, NUDOCS 8106160522
Download: ML20004F119 (15)


Text

-

_ ~

  • 6 e

(.

() DUKE POWER COMPANY

- McGUIRE NUCLEAR STATION PUMP INSERVICE TESTING PROGRAM ASME SECTION XI, SUBSECTION IEP The inservice testing of ASME Code Class 1, 2, and 3 pumps provided with an emergency power source will be tested as required by Section XI, Subsection IWP, of the ASME Boiler and Pressure Vcssel Code 1977 Edition and Addenda through summer 1978, except where specific written relief has been grcnted by the Commission. A description of the proposed inservice testing program, as well as specific requests for relief from code requirements determined to be impractical, is described by the following.

I. The following specific requests for relief from certain code requirements are to be appli:able for all pumps.

A) IWP-4120 requires the full scale range of each instrument to be three times the reference value or less. This was changed from four times the reference value in the edition of Section XI that was in effect prior to unit licensing. 10CFR, Section 50.55a(g)(4) states that design provisions are excluded from the requirement to upgrade to subsequent editions of Section XI. Since any cases where the three-times reference value criterion is not met would require design changes in instru-mentation, we will continue to apply the four-times reference value criterion, as interpreted in B) below, for instrument accuracy evaluation.

B) In several cases, instrumentation does not meet the four times reference value criterion. These cases predominantly involve suction pressure gauges where a larger range is required to accommodate varying conditions at the succion of the pump.

In all cases where the four-times reference value criterion cannotbemet,aninstrumenterrorevalu/ationisperformed to demonstrate that the overall accuracy of the differential pressure measurement is within the limits established by IWP.

C) Table IWP-3100-1 9atablishes the parameters that are to be measured. The r,revious edition of Section 11 specified that in a fixed zesistance system, either AP or Q was to be measured, not both. There are two systems that are tested using fixed resistance flow paths, with no flow indication provided. Based on the design change exclusion provided by 10CRF50.55a(g)(4), we will continue to apply the criterion that it is not required ta measure flow in a fixed resistance system.

D) IWP 4320 provides that the temperature of the pumped liquid be recorded. Since this value is not used in determining the acceptability of the pump, and has in fact been deleted from later revisions of the code, we do not plan to record this parameter.

REV. 2 8106160621

_3 II. The following Safety Class 1, 2, and 3 pumps (See Attachze*.c #1 for specific safety class and available instrumentation) will be tested in accordance with the intent of Subsection IWP of the ASME code:

NUCLEAR SERVICE WATER PUMPS (1A,1B)

CONTAINMENT SPRAY PUMPS (lA, IB)'

SAFETY INJE(; TION PUMPS (lA, IB)

MOTOR-DRIVEN AUX. FEEDWATER PUMPS (lA, IB)

TURBINE-DRIVEN AUX. FEEDWATER PLHP (NO.1)

CENTRIFUGAL CHARGING PUMPS (lA, IB)

COMPONENT COOLING PUMPS (lAl, lA2, 1B1, 1B2)

FUEL POOL COOLING PUMPS (lA, IB)

III. The following Safety Class 1, 2, and 3 pumps (See Attachment #1 for specific safety class and available instrumentation) will be tested in accordance with the intent of Subsection IWP, except for the request for relief for the specific requirements determined to be impractical as described below.

A) PUMP: BORIC ACID TRANSFER PUMPS (lA, 1B)

SAFETY CLASS: 3 FUNCTION: Boric Acid Tank recirculation, boric acid makeup and boric acid delivery to Centrifugal Charging pump suction TEST REQUIREMENT: 1. Measure pump bearing temperature during inservice testing.

i 2. Annually, run pump until bearing temperatures stabilize.

3. Observe proper lubricant level or pressure during inservice testing.

BASIS FOR RELIEF: There is no instrumentation installed to measure puip bearing temoerature. The subject pump / motor is of the completely enclosed " canned" type and therefore no meaningful temperature data can be obtained from pump surface temperature.

There is no lubricant level or pressure indication associated with the subject pumps as they are lubricated by the boric acid solution which they pump.

ALTERNATE TESTING: The inservice testing of the Boric Acid Transfer pumps will be in accordance with the intent of subsection IWP except for the following exceptions:

Bearing temperature will not be monitored and subsequently the pumps will not annually be run until temperature stabilization. The mechanical condition of the pumps will be determined from vibration data.

REV. 2

o .

I Lubricant level or pressure will not be j observed as they are not applicable to this pump design.

B) PUMP: CONTROL AREA CHILLED WATER PUMPS (CRA-P-1, CRA-P-2)

SAFETY CLASS: 3 FUNCTION: To provide chilled water to air handling .aits supplying control area air conditioning.

TEST REQUIREMENT: 1. Measure pump bearing temperature during inservice testing.

2. Annually run pumps until bearing temperatures stabilize.

BASIS FOR RELIEF: There is no instr.amentation installed to measure bearing temperature, and no meaningful data can be obtained from bearing housing surface tempera-ture measurements.

ALTERNATE TESTING: The inservice testing of the Control Area Chilled Water Pumps will be in accordance with the intent of Subsection IWP excapt that bearing temperature will not be monitored and subsequently the pumps will not be run annually until bearing temperatures stabilize. The mechanical condition of the subject pumps t:ill be determined from vibration data.

C) PUMP: BORON INJECTION RECIRCULATION PUMPS (1A,1B)

SAFETY CLASS: 3 FUNCTION: Recirculation of boric acid through Boron Injec-tion Tank.

, TEST REQUIREMENT: 1. Measure pump bearing temperature during inservice testing.

2. Annually run pump until bearing temperatures stabilize.
3. Observe proper lubricant level or pressure during inservice testing.

BASIS FOR RELIEF: There is no instrumentation installed to measure pump bearing temperature. The subject pump / motor is of the completely enclosed " canned" type and therefore no meaningful temperature can be obtained from pump surface temperature.

REV. 2

. There is no lubricant level or pressure associated with the subject pumps as they are lubricated by the boric acid solution which they pump.

ALTERNATE TESTING: The inservice testing of the Boron Injection Recirculation Pumps will be in accordance with the intent of subsection IWP except for the following exceptions:

Bearing temperature will not be monitored and subsequently the pumps will not annually be run until bearing temperatures stabilize.

The mechanical condition of the pumps will be determined from vibration data.

Lubricant level or pressure will not be '

observed as they are not applicable to

- this pump design.

~

IV. The following Safety Class 1, 2, and 3 pumps are provided with insufficient instrumentation to perform any meaningful testing in accordance with the intent of Subsection IWP and therefore the following alturnate testing methods, as well as requests for relief from compliance with Subsection IWP, are described by the following.

A) PUMP: D/GL JACKET WATER HEATER CIRCULATING PUMPS (lA,1B)

D/G JACKET WATER PUMPS (IA, IB)

- D/G INTERCOOLER WATER PUMPS (LA, IB)

D/G LUBE OIL FILTER PUMPS (IA, 1B)

D/G BEFORE AND AFTER LUBE OIL PUMPS (1A, 1B)

D/G FUEL OIL TRANSFER PUMPS (lA, 1B)

D/G FUEL OIL BOOSTER PUMPS (lA, IB)

SAFETY CLASS: 3 (All pumps)

FUNCTION: Diesel generator auxiliary support TEST REQUIREMENT: Test pumps in accordance with Subsection IWP l

BASIS FOR RELIEF: Pumps contain insufficient instrumentation (See l

Attachment #1) to perform any meaningful testing

! in accordance with the intent of Subsection IWP.

ALTERNATE TESTING: Monthly Diesel Generator starting and loading as required by McGuire Technical Specificatione is sufficient in assessing the hydraulic condition of the subject auxiliary pumps and demonstrating the capability of the individual components to perform their design function.

i The mechanical condition of the subject pumps l

i will be determined from vibration data to be gathered monthly, i

I, l

REV. 2 1

l

B) PUMP: D/G ROOM SUMP PUMPS (lA2, lA3,1B2, IB3) 7AFETY CLASS: 3 FUNCTION: Water removal from Diesel Generator rooms TEST REQUIREMENT: Test pumps in accordance with Subsection IWP BASIS FOR RELIEF: Pumps contain insufficient instrumentation.

(See Attachment #1) to perform any meaningful testing in accordance with Subsection IWP.

ALTERNATE TESTING: Due to the anticipated infrequent normal operation of these pumps, quarterly, each pump will be verified to be capable or performing theit design function of removing water from the sump at a rate greater than or equal to 419 gpm.

C) PUMP: GROUND WATER DRAINAGE PUMPS (A, B IN SUMP A; A, B IN SUMP B; A, B IN SUMP C)

SAFETY CLASS: 3 FUNCTION: Removal of station ground water ;aage TEST REQUIREMENT: Test pumps in accordance with Subsection IWP

( Pumps contain insufficient instrumentation (See BASIS FOR RELIEF:

Att_achment #1) to perform any meaningful testing in accordance with Subsection IWP.

ALTERNATE METHOD: No alternate testing proposed. The ability of these pumps to perform their design function is assured by observations that acceptable sump levels are being maintained during routine plant inspections.

D) PUMP: A/C SYSTEM COMPRESSOR OIL PUMPS (CRA-C-1, CRA-C-2)

SAFETY CLASS: 3 l

FUNCTION
Control Room area air conditioning chiller auxiliary support.

l TEST REQUIREMENT: Test pumps in accordance with Subsection IWP.

BASIS FOR RELIEF: Pumps contain insufficient instrumentation (See Attachment #1) to perform any meaningful testing in accordance with Subsection IWP.

l l

l l

REV. 2

(

-o --- .- .- -. . _ .

ALTERNATE TESTING: No alternate testing proposed. The ability of these pumps to perform their design function is assured by acceptable Control Room area ,

i chiller operation, as these chillers are in ,

l operation almost continuously during normal plant operation.

e

  • f 1

i a

b REV. 2

7 SAFETY RELATED CLASS 1, 2 AND 3 PUMPS PROVIDED WITH AN EMERGENCY POWER SOURCE A"

m I > b

.o g m e g g e

m a

- - e s m . m R - g

@ R, B

~

B

~

i M u ~ u a e n R 6 a

- g e 5 - e. e e . . m e a

m m

H e

m e

s e

A sW e sa 8 so

=

A 2

A PUMPS Nuclear Service Water Pumps (IA, IB) 3 MO NR X X X X(1) X X X HC-1574-1.1 l Containment Spray Pumps (IA, IB) 2 M0' NR X X X X(1) X(3) X(2) X MC-1563-1.1 Residual lleat Removal Pumps (lA, IB) 2 MO NR X X X X(1) X(3) X(2) X MC-1561-1.0 i'

Safety Injection Pumps (lA, 18) 2 MO NR X X X X(1) X X X MC-1562-3.0 M/D Aux. Feedwater Pumps (IA, 1B) 3 MO NR X X X X(1) X X X MC-1592-1.1 T/D Aux. Feedwater Pump (No. 1) 3 Mo X X X X X(1) X X X MC-1592-1.1 Cent. Charging Pumps (lA, 1B) 2 M0 NR X X NR X(1) X X X MC-1554-3.1 Component Cooling Pumps (lAl, lA2, 1B1, 1B2) 3 MO NR X X X X(1) X X X MC-1573-1.0 Fuel Pool Cooling Pumps (lA, IB) 3 MO NR X X X X(1) X X X MC-1570-1.0 Boric Acid Transfer Pumps (IA, IB) 3 M0 NR. X _

X NR X(1) - -

X MC-1554-5.0 Control Area Chilled Water Pumps (CRA-P-1,2) 3 MO NR X X X(1) X - X MC-1618-1.0 Boron Injection Recire. Pumps (lA, IB) 3 M0 NR X X X X(1) - -

X MC-1562-1.0 A/C System Compressor Oil Pump (CRA-C-1,2) 3 -

NR - - - - - -

X MC-1618-4.0 D/G Jacket Water lleater Circ. Pumps (lA, IB) 3 MO NR - - -

X(1) - -

X MC-1609-1.0, 1.1

~

REV. 2

Main Steam System: Main Steam Vent To Atmosphere Flow Disgram: MC-1593-1.0 Revision: 6 Change Order: 10 O

l l

i l

i 312 Rev. 2

MC-1592-1.0 G m C .

W G e m m e W M E m !O  % E E $ W -

5 " S 8 d

  1. E "

E "

Page 15 I VALVE 5 C $ 8 e

m E CATEGORY w Q d li1 5 2 s W 3 5 E G U M N M8 A B C D E NS OC REMARKS 1CA-111 3 B-6 X 4 GA M LC PC ICA-112 3 B-8 X 4 GA M LC PC ICA-59 3 0-1 X - '4 GA M LO PC

. MT ICA-60 3 G-1 X 4 GA AD 0 Q

]

MT ICA-61 2 H-1 X 4 CK SA 0 Q CT CT ICA-62A 2 I-1 X 4 GA EL 0 Q X CS 10 seconds maximum op. time _2 CT CT 1CA-66A 2 J-1 X 4 GA EL 0 Q X CS 10 seconds maximum op. time 2 MT ICA-65 2 K-1 X 4 CK SA 0 Q MT 1CA-64 3 L-4 X 4 GA AD 0 Q 1CA-63 3 L-6 X 4 GA M L0 PC ICA-55 3 C-2 X 4 GA M L0 PC MT 1CA-56 3 C-4 X 4 GA AD 0 Q 1

Rev. 2 j

0 $

5 0 p '

w 5 5 ,- I g $ 5 $ $ Page 16 ,

O M m A B "

a b E VALVE

  • " S 5 CATEGORY

$ e w $ $ I e- I VALVE 'S 8 d i G

E O H

d 0

NUMBER " " A B C D E NS OC

  • Z '-

REMARKS MT 1CA-57 2 C-6 X 4 CK SA 0 Q CT CT 1CA-58A 2 D-7 X 4 GA EL 0 Q X CS 10 seconds maximum op. time 2 CT CT 1CA-54A 2 G-7 X 4 GA EL 0 Q X CS 10 seconds maximum op. time 2 MT

, ICA-53 2 H-7 X 4 CK SA 0 Q MT ICA-52 3 K-7 X 4 GA A0 0 Q ICA-51 3 K-7 X 4 GA M L0 PC 1CA-43 3 C-12 X 4 GA M LO PC I MT ICA-44 3 C-11 X 4 GA AD 0 Q

< MT 1CA-45 2 C-9 X 4 CK SA 0 Q CT CT i ICA-46B 2 D-8 X 4 GA EL 0 Q X CS 10 seconds maximum op. time 2 CT CT ICA-50B 2 G-8 X 4 GA EL 0 Q X CS 10 sc:conds maximum op. time 2 MT 1CA-49 2 H-8 X 4 CK SA 0 Q Rev. 2

$ W 5 y C .

5 m .- 1 G E 5 5 13 5 0 W w 4 a 5 a b p,9e 17 t2 W  % =

  • a=
  • 5 VALVE C, '-

S _., W m M

$ e CATEGORY w y g 1 ,._

W p VALVE 3

o 8

o d

m b

8 z

0 e-d a

0 r

NUMBER A B C D E NS OC REMARKS MT 1CA-48 3 I-8 X 4 GA AD 0 Q ICA-47 3 K-8 X 4 GA M LO PC 4

1CA-39 3 0-13 X 4 GA M LO PC MT 1CA-40 3 G-13 X 4 GA AD 0 Q MT 1CA-41 2 H-13 X 4 CK SA 0 Q CT CT 1CA-42B 2 1-13 X 4 GA EL 0 Q X CS 10 seconds maximum op. time 2 CT CT 1CA-38B 2 J-13 X 4 GA EL 0 Q X CS 10 seconds maximum op. time 2 MT 1CA-37 2 I-13 X 4 CK SA 0 Q

MT L-10 0 1CA-36 3 X 4 GA AD Q 1CA-35 3 L-9 X 4 GA M L0 PC Rev. ?

2 2 2 1 2

. v d e d d d e R n n n t o o o e c c c l S e e e e 6 K s s s d 0 9 R 5 5 5 n 2 A 1 1 1 e 4 M < < < e

- e g

E b 8 R e 5 a e e s 5 P m m m 1 i i i a

- T T T h C e M l l

l v

o o o l s s s a I I I V YhEW# $# F R

F R

F R

F R

MWS CE T T hWeE MU T CQL T T CQL T T CQL T

MQL AhEMS I=E 0 0 0 -

L A mbF 5E E P P S A A A K EN *3$ G G G C 4

ma5 %G . 4 4 4 C

O S

N E

Y R

EO VG LE D AT VA C

X C

B A X X X X 2 3 3 3 1 1 1 1 mWIE$8 K K

H F

2 2 2 2

  • ]o B A A 3 4 8 5 9 3 3 2 3 2 ER 2 2 2 VE 2 .2 LB F F F F F AM N N N N N VU 1 1 1 I I N

)  ! ,  ;

0 W -

5 0 p 5 5 - n G E 5 5 0 5 Page 445 -

0 g m 4 g = g 3 1 VALVE E S = E EE U O a E u- E m E CATEGORY

$  % h h G $ $

VALVE $

" O E > E E U E N REMARKS NUMBER A B C D E NS OC not requirea for reactor shutdown / accident INI-154 2 I-2 X 1 GL AD C consequences 1NI-216 2 H-3 X 3/4 GL M C zu seconas maximum op. time CT Valve is de-energized during INI-1838 2 G-3 X 12 GA EL C Q op. per Tech. Specifications. 2 INI-210 2 D-7 X 3/4 GL M C Au seconos mau mum op. time CT Valve is de-energized during

! 1NI-152B 2 D-6 X X 4 GA EL C Q op. per Tech. Specifications.*

1NI-211 2 D-6 X 3/4 GL M C 1NI-416 2 D-5 X 1 GL M C

INI-420 2 0-5 ,

X 1 GL M C 1NI-390 2 D-4 X 1 GL M C INI-389 2 D-4 X l GL M C not requirea for reactor shutdown / accident INI-153 2 D-4 X 2 GL .AD C consequences 1NI-158 2 C-4 X 2 GL M LO PC 1

  • Leak test per Technical cnnci ri c, t in.- Peu ?

e i

VALVES: IVPIB, IVP2A, IVP3B, IVP A, IVP6B, IVP7A, IVP8B, IVP9A, IVP10A, IVPilB, IVP12A, IVP13B, IVP15A, IVP16B, IVPl7A, IVP183, IVP19A, IVP20B CATEGORY: A CLASS: 2 FUNCTION: Provide containment isolation TEST REQUIREMENT: Cycle and time valves every 3 months.

BASIS FOR RELIEF: Technical Specification 4.6.3.4 requires a lealc rate test on these valves whenever they are cycled. In addition, Technical Specification 4.6.1.9 places severe restrictions on the operational time and alignment permitted for this system during normal operation. Because of these re-strictions, it is not practical to cycle and time these valves quarterly.

ALTERNATE TESTING: Valves will be timed whenever the system is operated or whenever the valves are cycled, and the elapsed time

since the previous test has been 3 months or greater.

5 e

l l

[ 221a REV. 2 1

1 -,- . - . - . . . - .. - . - - - . - , . - - . . -

13 l .

i*

A N > g4 y E E E d . $ o f !a m . u n

e - e - e .

g d - d  % 3 e

- g 0 m - e n e , . m e m

% W W d h d C 8 b

m o M

o m - m s a >

PUMPS D/G Jacket Water Pumps (lA, IB) 3 MO NR - - -

X(1) - - X MC-1609-1.0, 1.1 X(1) X MC-1609-1.0, 1.1

_D/G Intercooler Water Pumps (lA, IB) 3 MO NR - - - - -

D/G Lube Oil Filter Pumps (lA, IB) 3 MO NR - - -

X(1) - -

X MC-1609-2.0, 2.1 D/G B&A Lube Oil Filter Pumps (IA, IB) 3 M0 NR - - -

X(1) - -

X MC-1609-2.0, 2.1 D/G Fuel Oil Transfer Pumps (IA, IB) 3 MO NR - - -

X(1) - -

X MC-1609-3.0, 3.1 D/G Fuel Oil Booster Pumps (lA, IB) 3 MO NR - - -

X(1) - -

X MC-1609-3.0, 3.1

,D/G Room Sump Pumps (IA2, lA3, 1B2, IB3) , 3_ QU NR - - - - - - X MC-1609-7.0 Ground Water Drainage Pumps (A, B in Sump A; i A, B in Sump B; A, B in Sump C) 3 -

NR - - - - - - -

MC-1581-1.0 l

1 NOTES

1. Vibration to be measured with portable instrumentation (Accuracy +20%).
2. Pump contains no bearings, but is close coupled, therefore motor bearings will be monitored.
3. Pump is close coupled, therefore motor lubricant level will be observed.

LEGEND 1

X - Instrumentation MC - Monthly

- - Instrumentation not available QU - Quarterly l NR - Not required for IWP Compliance ()- Note REV. 2