Line 3: Line 3:
| issue date = 03/23/1989
| issue date = 03/23/1989
| title = Revised Application for Amend to Licenses DPR-58 & DPR-74 Re Diesel Generator Fuel Oil Tank Cleaning
| title = Revised Application for Amend to Licenses DPR-58 & DPR-74 Re Diesel Generator Fuel Oil Tank Cleaning
| author name = ALEXICH M P
| author name = Alexich M
| author affiliation = INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
| author affiliation = INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
| addressee name = MURLEY T E
| addressee name = Murley T
| addressee affiliation = NRC
| addressee affiliation = NRC
| docket = 05000315, 05000316
| docket = 05000315, 05000316
Line 14: Line 14:
| document type = OPERATING LICENSES-APPLIATION TO AMEND-RENEW EXISTING, TEXT-LICENSE APPLICATIONS & PERMITS
| document type = OPERATING LICENSES-APPLIATION TO AMEND-RENEW EXISTING, TEXT-LICENSE APPLICATIONS & PERMITS
| page count = 5
| page count = 5
| project =
| stage = Request
}}
}}


=Text=
=Text=
{{#Wiki_filter:ACCELERATED DI1BUTION "o'DEMONSTP+TION, Fr'PTEgREGULATORY INFORMATION DISTRIBUTION SYSTEM(RIDS)ACCESSXON NBR:8903300119 DOC.DATE:
{{#Wiki_filter:ACCELERATED               DI1BUTION               DEMONSTP+TION, Fr'PTEg "o'
89/03/23NOTARIZED:
REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
NODOCKETFACIL:50-315 DonaldC.CookNuclearPowerPlant,Unit1,Indiana60500031550-316DonaldC.CookNuclearPowerPlant,Unit2,Indiana&05000316AUTH.NAMEAUTHORAFFXLIATXON ALEXICH,M.P.
ACCESSXON     NBR:8903300119         DOC.DATE: 89/03/23      NOTARIZED: NO            DOCKET FACIL:50-315 Donald C. Cook Nuclear Power Plant, Unit 1, Indiana 6 05000315 50-316 Donald C. Cook Nuclear Power Plant, Unit 2, Indiana & 05000316 AUTH. NAME              AUTHOR AFFXLIATXON ALEXICH,M.P.           Indiana Michigan Power Co. (formerly Xndiana 6 Michigan Ele RECIP.NAME             RECIPXENT AFFILIATION MURLEY,T.E.             NRC No Detailed Affiliation Given
IndianaMichiganPowerCo.(formerly Xndiana6MichiganEleRECIP.NAME RECIPXENT AFFILIATION MURLEY,T.E.
NRC-NoDetailedAffiliation Given


==SUBJECT:==
==SUBJECT:==
Revisedapplication foramendtoLicensesDPR-586DPR-74redieselgenerator fueloiltankcleaning.
Revised application        for amend  to Licenses    DPR-58 6 DPR-74    re diesel generator fuel        oil tank  cleaning.
DISTRIBUTION CODE:A001DCOPIESRECEIVED:LTR ENCLSIZE:TITLE:ORSubmittal:
DISTRIBUTION CODE: A001D            COPIES RECEIVED:LTR         ENCL      SIZE:
GeneralDistribution NOTESRECIPIENT IDCODE/NAME PD3-1LASTANG,JINTERNAL:
TITLE:     OR  Submittal: General Distribution NOTES RECIPIENT            COPIES            RECXPXENT          COPIES I
ARM/DAF/LFMB NRR/DEST/CEB 8HNRR/DEST/MTB 9HNRR/DEST/S ICB,NUDOCS-ABSTRACT 01EXTERNAL:
ID  CODE/NAME          LTTR ENCL      ID CODE/NAME         LTTR ENCL            A PD3-1 LA                  1    1      PD3-1 PD                1    1 STANG,J                    5    5 INTERNAL: ARM/DAF/LFMB                   1    0      NRR/DEST/ADS    7E      1    1 NRR/DEST/CEB 8H            1    1      NRR/DEST/ESB    8D      1    1 NRR/DEST/MTB 9H            1    1      NRR/DEST/RSB    8E      1    1 I
LPDRNSICCOPIESLTTRENCL1155101111111111111~1RECXPXENT IDCODE/NAME PD3-1PDNRR/DEST/ADS 7ENRR/DEST/ESB 8DNRR/DEST/RSB 8ENRR/DOEA/TSB 11OGC/HDS1RES/DSXR/EIB NRCPDRCOPIESLTTRENCL1111111111101111IARISNaZEIQALLiiRXDSiiRECXPXENrS:
NRR/DEST/S CB, NUDOCS-ABSTRACT 1    1      NRR/DOEA/TSB   11      1 1
PLEASEHELPUSK)REMJCEHASTE!CXWZACZ'IHEDOCUMERZCOhGR3LDESKIROOMPl-37(EXT.20079)TOELZKBQTEYOURNAMEFMMDISTRIBUTION IZSTSFORDOCUMEHI'S YOUDGNiTNEEDtTOTALNUMBEROFCOPIESREQUIRED:
1 0
LTTR22ENCL20 indianaMichiganPowerCompanyP.O.Box16631Cotumbus, OH432168AEP:NRC:0896M DonaldC.CookNuclearPlantUnits1and2DocketNos.50-315and50-316LicenseNos.DPR-58andDPR-74REVISEDTECHNICAL SPECIFICATIONS FORDIESELGENERATOR FUELOILTANKCLEANINGAttn:T.E.MurleyMarch23,1989
1    1      OGC/HDS 1 01        1    1      RES/DSXR/EIB           1    1 EXTERNAL: LPDR                          1    1      NRC PDR                1    1 NSIC                      1  ~ 1 R
I S
NaZE IQ ALL iiRXDSii RECXPXENrS:
PLEASE HELP US  K) REMJCE HASTE! CXWZACZ 'IHE DOCUMERZ COhGR3L DESKI ROOM Pl-37 (EXT. 20079) TO ELZKBQTE YOUR NAME FMM DISTRIBUTION IZSTS FOR DOCUMEHI'S YOU DGNiT NEEDt TOTAL NUMBER OF COPIES REQUIRED: LTTR                22  ENCL    20


==DearDr.Murley:==
indiana Michigan Power Company P.O. Box 16631 Cotumbus, OH 43216 8
Thisletterrevisesourapplication foramendment totheTechnical Specifications (T/Ss)fortheDonaldC.CookNuclearPlantsubmitted inAEP:NRC:0896H datedNovember25,1987,andupdatesinformation contained inAEP:NRC:0896I datedJanuary24,1989.Adetaileddescription oftheproposedrevisionandanupdatedanalysisconcerning significant hazardsconsiderations areincludedinAttachment 1tothisletter.Attachment 2containstheproposedrevisedT/Spages.Webelievetheproposedchangewillnotresultin(1)asignificant changeinthetypesofeffluents orasignificant increaseintheamountsofanyeffluentthatmaybereleasedoffsite,or(2)asignificant increaseinindividual orcumulative occupational radiation exposure.
AEP:NRC:0896M Donald C. Cook Nuclear Plant Units 1 and      2 Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 REVISED TECHNICAL SPECIFICATIONS FOR DIESEL GENERATOR FUEL OIL TANK CLEANING Attn: T.        E. Murley March 23, 1989
TheseproposedchangeshavebeenreviewedbythePlantNuclearSafetyReviewCommittee andwillbereviewedbytheNuclearSafetyandDesignReviewCommittee.
 
Incompliance withtherequirements of10CFR50.91(b)(1),
==Dear Dr. Murley:==
copiesofthisletteranditsattachments havebeentransmitted toMr.'.C.CallenoftheMichiganPublicServiceCommission andMr.G.Bruchmann oftheMichiganDepartment ofPublicHealth.Thisdocumenthasbeenpreparedfollowing Corporate procedures whichincorporate areasonable setofcontrolstoensureitsaccuracyandcompleteness priortosignature bytheundersigned.
 
Sincerely, M.PEAlichVicePresident ldpAttachments 8903300ii9 890323PDRADOCK050003i5PDC Dr.T.E.Murley-2-AEP:NRC:0896M cc:D.H.Williams, Jr.W.G.Smith,Jr.-BridgmanR.C.CallenG.CharnoffA.B.DavisNRCResidentInspector
This    letter revises our application for  amendment to the Technical Specifications (T/Ss) for the Donald C.     Cook Nuclear Plant submitted in      AEP:NRC:0896H dated November 25, 1987, and updates information contained in AEP:NRC:0896I dated January 24, 1989.       A detailed description of the proposed revision and an updated analysis concerning significant hazards considerations are included in Attachment 1 to this letter. Attachment 2 contains the proposed revised T/S pages.
-BridgmanG.Bruchmann ATTACHMENT 1TOAEP:NRC:0896M REASONSAND10CFR50.92ANALYSISFORCHANGETOTHEDONALDC.COOKNUCLEARPLANTUNITS1AND2TECHNICAL SPECIFICATIONS Attachment 1toAEP:NRC:0896M Page1BackroundXnAEP:NRC:0896H datedNovember25,1987,wesubmitted aproposedTechnical Specification (T/S)changewhichrequiredthatthedieselgenerator fueloiltanksbecleanedatleastonceeverytenyears.XnAEP:NRC:0896I datedJanuary24,1989,weprovidedadetaileddescription ofeachofthetwocleaningmethodsallowedbytheproposedT/Ssandtheacceptance criteriaassociated witheachmethod.Thefirstoptionrequiresthatthetanksbeemptiedandtheinteriormechanically cleaned;theacceptance criteriaisaclean,dryinteriorasdetermined byvisualexamination.
We  believe the proposed change will not result in (1) a significant change in the types of effluents or a significant increase in the amounts of any effluent that may be released offsite, or (2) a significant increase in individual or cumulative occupational radiation exposure.
Thesecondoptionrequiresthattheoilbeagitatedbybubblingnitrogengasintothetankwhileaminimumoffivetankvolumesofoiliscirculated throughafive-micron filter.Threesuccessive samplesoffuelarethencollected andanalyzedaccording toASTMD2276-83.
These proposed changes have been reviewed by the Plant Nuclear Safety Review Committee and will be reviewed by the Nuclear Safety and Design Review Committee.
Thisprocess,including thethreesuccessive samplesconstitutes oneiteration cycle.Ouroriginalproposalwastorepeatthecycleuntilallthreesamplesindicated acontaminant levellessthantenmgperliter.Therecirculation andsamplingisrepeateduntilallthreesamplesindicateacontaminant levellessthantenmgperliter.DescritionofRevisionDuringdiscussion withmembersoftheNRCstaff,wewereinformedthattheywereunwilling toapproveourtankcleaningrequirements intheircurrentformbutwouldbereceptive toaslightlymodifiedproposal.
In compliance with the requirements of 10 CFR 50.91(b)(1), copies of this letter and its attachments have been transmitted to Mr.'. C. Callen of the Michigan Public Service Commission and Mr. G. Bruchmann of the Michigan Department of Public Health.
Specifically, theNRCstaffrequested thatwemodifyourproposedT/Sstorequireconducting thetankcleaningusingthedrain-and-clean methodifunacceptable resultsareobtainedonthreesuccessive iterations usingtheagitation-filtration method.VehavemodifiedtheproposedT/Spagesaccordingly andincludedtheminAttachment 2.Also,asrequested bytheNRCstaff,wehavemodifiedthethirdparagraph onBasespageB3/48-2toclarifythatitappliesonlytothesamplestakentomeetsurveillance requirement 4.8.1.1.2.d, nottothesamplestakenduringtankcleaningtomeetsurveillance requirement 4.8.1.1.2.f.l.
This document has been prepared following Corporate procedures which incorporate a reasonable set of controls to ensure its accuracy and completeness prior to signature by the undersigned.
AnalsisofSinificantHazardsTheproposedT/Schangessubmitted inthisletteraremorerestrictive thantheproposedchangessubmitted inAEP:NRC:0896H.
Sincerely, M. PE  Al ich Vice President ldp Attachments 8903300ii9 890323 PDR  ADOCK    050003i5 PDC
Thesignificant hazardsanalysissubmitted inAEP:NRC:0896H remainsapplicable tothechangessubmitted inthisletter.Theseproposedchangeswilltherefore notsignificantly increasetheprobability orconsequences ofanaccidentpreviously evaluated, createthepossibility ofanewordifferent accidentfromanyaccidentpreviously evaluated, orsignificantly decreaseamarginofsafetyandconsequently donotconstitute anunreviewed safetyquestionasdefinedin10CFR50.92.}}
 
Dr. T. E. Murley                   AEP:NRC:0896M cc: D. H. Williams, Jr.
W. G. Smith, Jr. - Bridgman R. C. Callen G. Charnoff A. B. Davis NRC  Resident Inspector - Bridgman G. Bruchmann
 
ATTACHMENT 1 TO AEP:NRC:0896M REASONS AND 10 CFR  50.92 ANALYSIS FOR CHANGE TO THE DONALD C. COOK NUCLEAR PLANT UNITS 1 AND 2 TECHNICAL SPECIFICATIONS to  AEP:NRC:0896M                                 Page 1 Back round Xn AEP:NRC:0896H dated November 25, 1987, we submitted a proposed Technical Specification (T/S) change which required that the diesel generator fuel oil tanks be cleaned at least once every ten years.
Xn AEP:NRC:0896I   dated January 24, 1989, we provided a detailed description of  each of the two cleaning methods allowed by the proposed T/Ss and the acceptance criteria associated with each method. The  first  option requires that the tanks be emptied and the  interior mechanically cleaned;   the acceptance criteria is a clean, dry interior as determined    by visual examination. The second option requires that the oil be agitated by bubbling nitrogen gas into the tank while a minimum of five tank volumes of oil is circulated through a five-micron filter. Three successive samples of fuel are then collected and analyzed according to ASTM D2276-83. This process, including the three successive samples constitutes one iteration cycle. Our original proposal was to repeat the cycle until all three samples indicated a contaminant level less than ten mg per liter. The recirculation and sampling is repeated until all three samples indicate a contaminant level less than ten mg per liter.
Descri tion of Revision During discussion with members of the NRC staff, we were informed that they were unwilling to approve our tank cleaning requirements in their current form but would be receptive to a slightly modified proposal. Specifically, the NRC staff requested that we modify our proposed T/Ss to require conducting the tank cleaning using the drain-and-clean method    if unacceptable results are obtained on three successive iterations using the agitation-filtration method. Ve have modified the proposed T/S pages accordingly and included them in Attachment 2.
Also, as requested by the NRC staff, we have modified the third paragraph on Bases page B 3/4 8-2 to clarify that    it  applies only to the samples taken to meet surveillance requirement 4.8.1.1.2.d, not to the samples taken during tank cleaning to meet surveillance requirement 4.8.1.1.2.f.l.
Anal sis of Si  nificant  Hazards The proposed T/S changes  submitted in this letter are more restrictive than the proposed changes submitted in AEP:NRC:0896H.
The significant hazards analysis submitted in AEP:NRC:0896H remains applicable to the changes submitted in this letter. These proposed changes will therefore not significantly increase the probability or consequences of an accident previously evaluated, create the possibility of a new or different accident from any accident previously evaluated, or significantly decrease a margin of safety and consequently do not constitute an unreviewed safety question as defined in 10 CFR 50.92.}}

Latest revision as of 04:35, 16 November 2019

Revised Application for Amend to Licenses DPR-58 & DPR-74 Re Diesel Generator Fuel Oil Tank Cleaning
ML17325B177
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 03/23/1989
From: Alexich M
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Murley T
NRC
Shared Package
ML17325B178 List:
References
AEP:NRC:0896M, AEP:NRC:896M, NUDOCS 8903300119
Download: ML17325B177 (5)


Text

ACCELERATED DI1BUTION DEMONSTP+TION, Fr'PTEg "o'

REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSXON NBR:8903300119 DOC.DATE: 89/03/23 NOTARIZED: NO DOCKET FACIL:50-315 Donald C. Cook Nuclear Power Plant, Unit 1, Indiana 6 05000315 50-316 Donald C. Cook Nuclear Power Plant, Unit 2, Indiana & 05000316 AUTH. NAME AUTHOR AFFXLIATXON ALEXICH,M.P. Indiana Michigan Power Co. (formerly Xndiana 6 Michigan Ele RECIP.NAME RECIPXENT AFFILIATION MURLEY,T.E. NRC No Detailed Affiliation Given

SUBJECT:

Revised application for amend to Licenses DPR-58 6 DPR-74 re diesel generator fuel oil tank cleaning.

DISTRIBUTION CODE: A001D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: OR Submittal: General Distribution NOTES RECIPIENT COPIES RECXPXENT COPIES I

ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL A PD3-1 LA 1 1 PD3-1 PD 1 1 STANG,J 5 5 INTERNAL: ARM/DAF/LFMB 1 0 NRR/DEST/ADS 7E 1 1 NRR/DEST/CEB 8H 1 1 NRR/DEST/ESB 8D 1 1 NRR/DEST/MTB 9H 1 1 NRR/DEST/RSB 8E 1 1 I

NRR/DEST/S CB, NUDOCS-ABSTRACT 1 1 NRR/DOEA/TSB 11 1 1

1 0

1 1 OGC/HDS 1 01 1 1 RES/DSXR/EIB 1 1 EXTERNAL: LPDR 1 1 NRC PDR 1 1 NSIC 1 ~ 1 R

I S

NaZE IQ ALL iiRXDSii RECXPXENrS:

PLEASE HELP US K) REMJCE HASTE! CXWZACZ 'IHE DOCUMERZ COhGR3L DESKI ROOM Pl-37 (EXT. 20079) TO ELZKBQTE YOUR NAME FMM DISTRIBUTION IZSTS FOR DOCUMEHI'S YOU DGNiT NEEDt TOTAL NUMBER OF COPIES REQUIRED: LTTR 22 ENCL 20

indiana Michigan Power Company P.O. Box 16631 Cotumbus, OH 43216 8

AEP:NRC:0896M Donald C. Cook Nuclear Plant Units 1 and 2 Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 REVISED TECHNICAL SPECIFICATIONS FOR DIESEL GENERATOR FUEL OIL TANK CLEANING Attn: T. E. Murley March 23, 1989

Dear Dr. Murley:

This letter revises our application for amendment to the Technical Specifications (T/Ss) for the Donald C. Cook Nuclear Plant submitted in AEP:NRC:0896H dated November 25, 1987, and updates information contained in AEP:NRC:0896I dated January 24, 1989. A detailed description of the proposed revision and an updated analysis concerning significant hazards considerations are included in Attachment 1 to this letter. Attachment 2 contains the proposed revised T/S pages.

We believe the proposed change will not result in (1) a significant change in the types of effluents or a significant increase in the amounts of any effluent that may be released offsite, or (2) a significant increase in individual or cumulative occupational radiation exposure.

These proposed changes have been reviewed by the Plant Nuclear Safety Review Committee and will be reviewed by the Nuclear Safety and Design Review Committee.

In compliance with the requirements of 10 CFR 50.91(b)(1), copies of this letter and its attachments have been transmitted to Mr.'. C. Callen of the Michigan Public Service Commission and Mr. G. Bruchmann of the Michigan Department of Public Health.

This document has been prepared following Corporate procedures which incorporate a reasonable set of controls to ensure its accuracy and completeness prior to signature by the undersigned.

Sincerely, M. PE Al ich Vice President ldp Attachments 8903300ii9 890323 PDR ADOCK 050003i5 PDC

Dr. T. E. Murley AEP:NRC:0896M cc: D. H. Williams, Jr.

W. G. Smith, Jr. - Bridgman R. C. Callen G. Charnoff A. B. Davis NRC Resident Inspector - Bridgman G. Bruchmann

ATTACHMENT 1 TO AEP:NRC:0896M REASONS AND 10 CFR 50.92 ANALYSIS FOR CHANGE TO THE DONALD C. COOK NUCLEAR PLANT UNITS 1 AND 2 TECHNICAL SPECIFICATIONS to AEP:NRC:0896M Page 1 Back round Xn AEP:NRC:0896H dated November 25, 1987, we submitted a proposed Technical Specification (T/S) change which required that the diesel generator fuel oil tanks be cleaned at least once every ten years.

Xn AEP:NRC:0896I dated January 24, 1989, we provided a detailed description of each of the two cleaning methods allowed by the proposed T/Ss and the acceptance criteria associated with each method. The first option requires that the tanks be emptied and the interior mechanically cleaned; the acceptance criteria is a clean, dry interior as determined by visual examination. The second option requires that the oil be agitated by bubbling nitrogen gas into the tank while a minimum of five tank volumes of oil is circulated through a five-micron filter. Three successive samples of fuel are then collected and analyzed according to ASTM D2276-83. This process, including the three successive samples constitutes one iteration cycle. Our original proposal was to repeat the cycle until all three samples indicated a contaminant level less than ten mg per liter. The recirculation and sampling is repeated until all three samples indicate a contaminant level less than ten mg per liter.

Descri tion of Revision During discussion with members of the NRC staff, we were informed that they were unwilling to approve our tank cleaning requirements in their current form but would be receptive to a slightly modified proposal. Specifically, the NRC staff requested that we modify our proposed T/Ss to require conducting the tank cleaning using the drain-and-clean method if unacceptable results are obtained on three successive iterations using the agitation-filtration method. Ve have modified the proposed T/S pages accordingly and included them in Attachment 2.

Also, as requested by the NRC staff, we have modified the third paragraph on Bases page B 3/4 8-2 to clarify that it applies only to the samples taken to meet surveillance requirement 4.8.1.1.2.d, not to the samples taken during tank cleaning to meet surveillance requirement 4.8.1.1.2.f.l.

Anal sis of Si nificant Hazards The proposed T/S changes submitted in this letter are more restrictive than the proposed changes submitted in AEP:NRC:0896H.

The significant hazards analysis submitted in AEP:NRC:0896H remains applicable to the changes submitted in this letter. These proposed changes will therefore not significantly increase the probability or consequences of an accident previously evaluated, create the possibility of a new or different accident from any accident previously evaluated, or significantly decrease a margin of safety and consequently do not constitute an unreviewed safety question as defined in 10 CFR 50.92.