{{#Wiki_filter:Figure 8a2.1 One-Line Diagram - Normal Electrical Power Supply System NOTES:1. BREAKERS DROP OUT (TRIP) ON LOSS OF POWER TO THE BUS AND CAN BE       MANUALLY CLOSED SELECTIVELY AFTER SDG RESTORES POWER TO THE BUSES.2. SDG AND AUTOMATIC TRANSFER EQUIPMENT LOCATED IN SEPARATE BUILDING.
{{#Wiki_filter:Chapter 8 - Electrical Power Systems                                                                                                                                                                                          Normal Electrical Power Systems Figure 8a2.1 One-Line Diagram - Normal Electrical Power Supply System 12kV UTILITY FEEDER                                                                                                                                                    12kV UTILITY FEEDER 12kV-480Y/277V                                                                                                                                                          12kV-480Y/277V 2000 kVA                                                                                                                                                                2000 kVA 3PH                                                                                                                                                                      3PH TRANSFORMER                                                                                                                                                              TRANSFORMER OUTDOOR TYPE                                                                                                                                                            OUTDOOR TYPE M                                                                                                                                                                      M FIRE PUMP                                                      CABLE BUS                                                                                                                                                                CABLE BUS CONTROLLER BOX (NOTE 7)
: 3. RESPECTIVE 480V AC SWGR BUS A OR B POWERS THE SDG BUSES DURING NORMAL OPERATION. ON LOSS OF OFF-SITE POWER, BOTH AC SWGR A AND B WILL BE   CONNECTED AS NEEDED.4. ON LOSS OF OFF-SITE POWER SDG WILL START. AFTER RATED VOLTAGE AND   FREQUENCY ARE ESTABLISHED AT THE SDG BUS, BREAKER FEEDS TO OTHER FACILITY LOADS WILL BE MANUALLY CONNECTED AS NEEDED.5. LOAD BREAKERS EQUIPPED WITH SOFT STARTERS.6. SDG - STANDBY DIESEL GENERATOR7. FIRE PUMP CONTROLLER BOX PER NFPA 20 AND IS LOCATED IN SIGHT OF FIRE   PUMP ROOM.480V-208Y/120V75 kVA3PHDISTRIBUTION PANEL FOR TCAP1, 2, 3 & 4CHILLER 1FACILITY 480V AC PLANT SWGR A208Y/120V 200A3PH, 4W12kV-480Y/277V2000 kVA3PHTRANSFORMER OUTDOOR TYPE12kV UTILITY FEEDERCABLE BUSUTILITY INTERFACEZONE 1 EXHAUSTFAN AZONE 2 EXHAUSTFAN AOUTDOORNCM480V-208Y/120V75 kVA3PHDISTRIBUTION PANEL FOR TCAP5, 6, 7 & 8CHILLER 3 FACILITY 480V AC PLANT SWGR B208Y/120V 200A 3PH, 4W12kV-480Y/277V 2000 kVA3PHTRANSFORMER OUTDOOR TYPE12kV UTILITY FEEDERCABLE BUSUTILITY INTERFACEZONE 2 EXHAUSTFAN B(STANDBY)OUTDOORNCM480VLATER kW3PH, 4WNCNOBATTERYCHARGER ABATTERYCHARGER BNCNCNONOPLUG-INPORTABLE DG FACILITY 480V AC SDG BUS A AT SWGR ROOM NOTE 3 NOTE 3NCNOTE 4LOCATED INSDG BUILDINGUPS VOLTAGEREGULATINGXFMR ASSEMBLY BUPS VOLTAGEREGULATINGXFMR ASSEMBLY ANCNCNCNCTO 480V AC MCC A1TO 480V ACMCC A2TO 480V ACMCC B1TO 480V ACMCC B2TO 480V ACSDG MCC B125HP200HP100HP200HP100HPSDGCHILLER 4200HPCHILLER 2200HPEMERGENCYLIGHTINGPANELZONE 1EXHAUST FAN B(STANDBY)125HPNCTO 480V ACSDG MCC ANCEMERGENCYLIGHTINGPANEL FACILITY 480V AC SDG BUS B AT SWGR ROOM NOOUTDOOR LOAD BANKFOR SDGTESTINGNONOFROM 480V AC  SUPPLY SDG MCC A FIRE PUMP200HPFIRE PUMP ROOM(LOCATED OUTSIDE FACILITY)FIRE PUMPCONTROLLER BOX(NOTE 7) Chapter 8 - Electrical Power Systems  Normal Electrical Power Systems SHINE Medical Technologies Rev. 0}}
OUTDOOR                                                                                                                                                                  OUTDOOR UTILITY INTERFACE                                                                                                                                                        UTILITY INTERFACE 200 HP FIRE PUMP FIRE PUMP ROOM (LOCATED OUTSIDE FACILITY)
FACILITY 480V AC PLANT SWGR A                                                                                                              FACILITY 480V AC PLANT SWGR B NC                                                  NC NOTE 3                                            NOTE 3 480V-208Y/120V                                                                                                                                        480V-208Y/120V 75 kVA                                                                                                                                                75 kVA 3PH                                                                                                                                                    3PH TO 480V AC        100                                200          200        100      TO 480V AC                                                                                                          200          200            125          125 TO 480V AC                                                                                    TO 480V AC MCC A1          HP                  208Y/120V      HP          HP        HP          MCC A2                                                                                              208Y/120V      HP          HP            HP            HP MCC B1                                                                                        MCC B2 200A                                                                                                                                                  200A ZONE 2                            CHILLER 1    CHILLER 2    ZONE 2                                                                                                                        CHILLER 3    CHILLER 4      ZONE 1        ZONE 1 3PH, 4W                                                                                                                                                3PH, 4W EXHAUST                                                      EXHAUST                                                                                                                                                    EXHAUST      EXHAUST FAN B                                                      FAN A                                                                                                                                                      FAN B        FAN A (STANDBY)  DISTRIBUTION                                                                                                                                          DISTRIBUTION                                        (STANDBY)
PANEL                                                                                                                                                  PANEL FOR TCAP                                                                                                                                              FOR TCAP 1, 2, 3 & 4                                                                                                                                            5, 6, 7 & 8 NC                                                NC NO                NO FACILITY 480V AC SDG BUS A AT SWGR ROOM                                                                                                          FACILITY 480V AC SDG BUS B AT SWGR ROOM NC              NC                NC            NC                                    NO                                    NC              NC              NC                NC NOTES:
: 1. BREAKERS DROP OUT (TRIP) ON LOSS OF POWER TO THE BUS AND CAN BE MANUALLY CLOSED SELECTIVELY AFTER SDG RESTORES POWER TO THE BUSES.
: 2. SDG AND AUTOMATIC TRANSFER EQUIPMENT LOCATED IN SEPARATE BUILDING.
: 3. RESPECTIVE 480V AC SWGR BUS A OR B POWERS THE SDG BUSES DURING NORMAL OPERATION. ON LOSS OF OFF-SITE POWER, BOTH AC SWGR A AND B WILL BE CONNECTED AS NEEDED.
: 4. ON LOSS OF OFF-SITE POWER SDG WILL START. AFTER RATED VOLTAGE AND FREQUENCY ARE ESTABLISHED AT THE SDG BUS, BREAKER FEEDS TO OTHER FACILITY LOADS WILL BE MANUALLY CONNECTED AS NEEDED.
: 5. LOAD BREAKERS EQUIPPED WITH SOFT STARTERS.
: 6. SDG - STANDBY DIESEL GENERATOR NOTE 4 TO 480V AC        BATTERY        EMERGENCY      UPS VOLTAGE                                                                  EMERGENCY        BATTERY        UPS VOLTAGE        TO 480V AC        7. FIRE PUMP CONTROLLER BOX PER NFPA 20 AND IS LOCATED IN SIGHT OF FIRE NO        NO    OUTDOOR SDG MCC A        CHARGER A          LIGHTING      REGULATING                                                                  LIGHTING      CHARGER B        REGULATING        SDG MCC B                PUMP ROOM.
LOAD BANK PANEL           XFMR                                              FOR SDG                  PANEL                             XFMR ASSEMBLY A                                    NO                                                              ASSEMBLY B TESTING PLUG-IN PORTABLE                SDG DG FROM 480V AC 480V       SUPPLY SDG MCC A LATER kW 3PH, 4W LOCATED IN SDG BUILDING SHINE Medical Technologies                                                                                                                                                                                                                                                                   Rev. 0}}

Latest revision as of 11:23, 31 October 2019

Shine Medical Technologies V. 0 - Chapter 08 - Figure 8a2.1-001
ML15161A176
Person / Time
Site: SHINE Medical Technologies
Issue date: 05/21/2015
From: Bynum R
Shine Medical Technologies
To:
Office of Nuclear Reactor Regulation
Lynch S
References
SHINE, SHINE.SUBMISSION.18, SHN.PSAR.P, SHN.PSAR.P.8
Download: ML15161A176 (1)


Text

Chapter 8 - Electrical Power Systems Normal Electrical Power Systems Figure 8a2.1 One-Line Diagram - Normal Electrical Power Supply System 12kV UTILITY FEEDER 12kV UTILITY FEEDER 12kV-480Y/277V 12kV-480Y/277V 2000 kVA 2000 kVA 3PH 3PH TRANSFORMER TRANSFORMER OUTDOOR TYPE OUTDOOR TYPE M M FIRE PUMP CABLE BUS CABLE BUS CONTROLLER BOX (NOTE 7)

OUTDOOR OUTDOOR UTILITY INTERFACE UTILITY INTERFACE 200 HP FIRE PUMP FIRE PUMP ROOM (LOCATED OUTSIDE FACILITY)

FACILITY 480V AC PLANT SWGR A FACILITY 480V AC PLANT SWGR B NC NC NOTE 3 NOTE 3 480V-208Y/120V 480V-208Y/120V 75 kVA 75 kVA 3PH 3PH TO 480V AC 100 200 200 100 TO 480V AC 200 200 125 125 TO 480V AC TO 480V AC MCC A1 HP 208Y/120V HP HP HP MCC A2 208Y/120V HP HP HP HP MCC B1 MCC B2 200A 200A ZONE 2 CHILLER 1 CHILLER 2 ZONE 2 CHILLER 3 CHILLER 4 ZONE 1 ZONE 1 3PH, 4W 3PH, 4W EXHAUST EXHAUST EXHAUST EXHAUST FAN B FAN A FAN B FAN A (STANDBY) DISTRIBUTION DISTRIBUTION (STANDBY)

PANEL PANEL FOR TCAP FOR TCAP 1, 2, 3 & 4 5, 6, 7 & 8 NC NC NO NO FACILITY 480V AC SDG BUS A AT SWGR ROOM FACILITY 480V AC SDG BUS B AT SWGR ROOM NC NC NC NC NO NC NC NC NC NOTES:

1. BREAKERS DROP OUT (TRIP) ON LOSS OF POWER TO THE BUS AND CAN BE MANUALLY CLOSED SELECTIVELY AFTER SDG RESTORES POWER TO THE BUSES.
2. SDG AND AUTOMATIC TRANSFER EQUIPMENT LOCATED IN SEPARATE BUILDING.
3. RESPECTIVE 480V AC SWGR BUS A OR B POWERS THE SDG BUSES DURING NORMAL OPERATION. ON LOSS OF OFF-SITE POWER, BOTH AC SWGR A AND B WILL BE CONNECTED AS NEEDED.
4. ON LOSS OF OFF-SITE POWER SDG WILL START. AFTER RATED VOLTAGE AND FREQUENCY ARE ESTABLISHED AT THE SDG BUS, BREAKER FEEDS TO OTHER FACILITY LOADS WILL BE MANUALLY CONNECTED AS NEEDED.
5. LOAD BREAKERS EQUIPPED WITH SOFT STARTERS.
6. SDG - STANDBY DIESEL GENERATOR NOTE 4 TO 480V AC BATTERY EMERGENCY UPS VOLTAGE EMERGENCY BATTERY UPS VOLTAGE TO 480V AC 7. FIRE PUMP CONTROLLER BOX PER NFPA 20 AND IS LOCATED IN SIGHT OF FIRE NO NO OUTDOOR SDG MCC A CHARGER A LIGHTING REGULATING LIGHTING CHARGER B REGULATING SDG MCC B PUMP ROOM.

LOAD BANK PANEL XFMR FOR SDG PANEL XFMR ASSEMBLY A NO ASSEMBLY B TESTING PLUG-IN PORTABLE SDG DG FROM 480V AC 480V SUPPLY SDG MCC A LATER kW 3PH, 4W LOCATED IN SDG BUILDING SHINE Medical Technologies Rev. 0