E-Mail, O'Keefe, Fple, to Miller, NRR, Seabrook License Amendment 05-08
ML062720006
Person / Time
Site: Seabrook NextEra Energy icon.png
Issue date: 09/28/2006
From: O'Keefe M
Florida Power & Light Energy Seabrook
To: Geoffrey Miller
Plant Licensing Branch III-2
References
LAR 05-08, TAC MC8554
Download: ML062720006 (2)


Text

From: <michael_okeefe@fpl.com>To:<GXM@nrc.gov>Date: 09/28/2006 4:24:13 PM

Subject:

Re: LAR 05-08 Ed, FPL Energy Seabrook LLC concurs with the proposed license condition tolimit primary-to-secondary leakage to 150 gallons per day per steam generator and if the limit is exceeded to take appropriate action in accordance with Technical Specification 3.4.6.2, Reactor Coolant SystemLeakage."Mike O'KeefeFPLE Seabrook Regulatory Compliance Supervisor 603-773-7745 (office) 603-771-7939 (pager) 765-6319 (cell)

"Ed Miller"

<GXM@nrc.gov> To: michael_okeefe@fpl.com

cc:

09/28/2006 03:04

Subject:

LAR 05-08

PM

Mike, Currently, FPLE procedurally limits operational primary-to-secondary leakage to 150 gallons per day (gpd) per Steam Generator (SG) compared to the Technical Specification (TS) limit of 500 gpd per SG. Upon further review, the staff determined that this procedural restriction needs to be contained in a license condition stating that FPLE will maintain theoperational limit of primary-to-secondary leakage at 150 gpd per SG and if this limit is exceeded, Seabrook will take the appropriate actions inaccordance with TS 3.4.6.2, "Reactor Coolant System Leakage." An e-mail, to be docketed, confirming the acceptability of this condition will besufficient.G. Edward MillerProject Manager Division of Operating Reactor Licensing U.S. Nuclear Regulatory Commission (301) 415-2481 Mail Envelope Properties(451C2F61.42C : 22 : 21548)

Subject:

Re: LAR 05-08Creation Date 09/28/2006 4:25:39 PMFrom: <michael_okeefe@fpl.com>Created By:michael_okeefe@fpl.comRecipientsnrc.gov TWGWPO01.HQGWDO01 GXM (Ed Miller)Post OfficeRoute TWGWPO01.HQGWDO01nrc.govFilesSizeDate & Time MESSAGE230609/28/2006 4:25:39 PM Mime.8223683Options Expiration Date:None Priority:Standard ReplyRequested:

No Return Notification:None Concealed

Subject:

No Security:StandardJunk Mail Handling Evaluation Results Message is eligible for Junk Mail handling This message was not classified as Junk MailJunk Mail settings when this message was delivered Junk Mail handling disabled by User Junk Mail handling disabled by Administrator Junk List is not enabled Junk Mail using personal address books is not enabled Block List is not enabled