Displayed 31 items.
- ML20054F725 (← links)
- 05000409/LER-1981-013-03, Following scram,1B 2,400-volt Bus Reserve Feed Breaker Did Not Close Automatically.Cause Undetermined.Reserve Feed Breaker Control Switch Flagged to Trip Position (← links)
- 05000409/LER-1981-014-03, /03L-0:on 811223,following Scram,Offsite Transmission Network Did Not Automatically Supply Onsite Power Distribution Sys.Cause Undetermined.Transformer Breaker Closed (← links)
- 05000409/LER-1981-014, Forwards LER 81-014/03L-0 & Updated LER 81-013/03X-1. Detailed Event Analysis Encl (← links)
- 05000409/LER-1981-015-01, /01T-0:on 811224,following Reactor Scram,Temp of 1B Forced Circulation Loop Piping Decreased Below Tech Specs Limit.Caused by Inoperation of Pump Due to Seal Problems & Lack of Monitoring.Personnel Reinstructed (← links)
- 05000409/LER-1981-015, Forwards LER 81-015/01T-0.Detailed Event Analysis Encl (← links)
- ML20039B229 (redirect page) (← links)
- 05000409/LER-1981-013 (redirect page) (← links)
- 05000409/LER-1981-011-03, /03L-0:on 811031,observed That Radiation Hose on High Pressure Svc Water Diesel Engine 1B Was Slightly Cracked.Cause Not Stated.Hose Replaced & Diesel 1B Tested Satisfactorily (← links)
- 05000409/LER-1981-011, Forwards LER 81-011/03L-0.Detailed Event Analysis Submitted (← links)
- 05000409/LER-1981-012-03, /03L-0:on 811101,gasoline Levels in Three Emergency Svc Water Supply Sys Gasoline Engine Driven Pumps & Spare Pump Found to Be Less than 5 Gallons During Monthly Insp.Cause Unknown.Gasoline Added to Fill Tanks (← links)
- 05000409/LER-1981-012, Forwards LER 81-012/03L-0.Detailed Event Analysis Submitted (← links)
- 05000409/LER-1981-009-03, /03L-0:on 810917,upscale Trip Setpoint on Nuclear Instrument Channel 7 Found in Excess of Tech Spec Limit. Cause Not Determined.Setpoint Reset (← links)
- 05000409/LER-1981-009, Forwards LER 81-009/03L-0.Detailed Event Analysis Submitted (← links)
- 05000409/LER-1981-010-01, /01T-0:on 810923,during Normal Operation Mechanical Interlock Preventing Simultaneous Opening of Both Doors of Containment Bldg Personnel Airlock Failed.Caused by Worn or Misadjusted Actuating Mechanism.Drawings Encl (← links)
- 05000409/LER-1981-010, Forwards LER 81-010/01T-0.Detailed Event Analysis Submitted (← links)
- 05000409/LER-1981-008-01, /01T-0:on 810729,main Steam Bypass Valve Did Not Open During Momentary Pressure Spikes Approx 20 Psi Above Nominal Reactor Pressure.Caused by Decrease in Pressure Prior to Valve Opening Due to Short Duration & Spikes (← links)
- 05000409/LER-1981-008, Forwards LER 81-008/01T-0.Detailed Event Analysis Submitted (← links)
- 05000409/LER-1981-003-03, /03L-0:on 810202,gross Alpha Activity of Primary Coolant Sample Exceeded Tech Spec.Caused by Degraded Fuel Cladding During Previous Fuel Cycles.Primary Purification Sys Operation Reduced Concentration to Allowable Level (← links)
- 05000409/LER-1981-003, Forwards LER 81-003/03L-0.Detailed Event Analysis Encl (← links)
- 05000409/LER-1981-002-02, /02L-0:on 810201,independent Circuit Between Offsite Transmission Network & Onsite Power Distribution Sys Was Disconnected.Caused by Operator Opening Incorrect Disconnect Switch.Switch Reclosed.Operators Retrained (← links)
- 05000409/LER-1981-002, Forwards LER 81-002/02L-0.Detailed Event Analysis Submitted (← links)
- 05000409/LER-1981-006-01, /01T-0:on 810518,during Installation of Attachment on Containment Pressure Sensing Line,High Containment Bldg Pressure Starting Signal to HPCS Pump 1B,auxiliary Cooling Sys Pump & AC Valve Was Isolated.Procedures Not Followe (← links)
- 05000409/LER-1981-006, Forwards LER 81-006/01T-0.Detailed Event Analysis Encl (← links)
- 05000409/LER-1981-001-02, /02L-0:on 810201,independent Circuit Between Offsite Transmission Network & Onsite Power Distribution Sys Disconnected.Caused by Disconnect Switch Opened Due to Operator Error.Two Operators to Operate Switching Order (← links)
- 05000409/LER-1981-001-03, /03L-0:on 810116,independent Circuit Between Offsite Transmission Network & Onsite Power Distribution Sys Disconnected.Caused by Maint on Main Transformer Airbreak Switch 25NA1 Due to Ice in Swivel Joint.Ice Melted (← links)
- 05000409/LER-1981-004-03, /03L-0:on 810309,during Condition 3,480-volt Diesel Bldg Essential Switchgear Bus 1B Was Energized from 1B Emergency Diesel Generator for Approx 25 Minutes W/Control Power Key in on Position (← links)
- 05000409/LER-1981-004, Forwards LER 81-004/03L-0.Detailed Event Analysis Also Submitted (← links)
- 05000409/LER-1981-007-01, /01T-0:on 810601,during Initial Integrated Sys Test W/Plant Shut Down,Emergency Svc Water Supply Sys Did Not Produce 900 Gpm at 90 Psig,As required.Three-way Distributor Fabricated.Sys Retested Satisfactorily (← links)
- 05000409/LER-1981-007, Forwards LER 81-007/01T-0 (← links)
- 05000409/LER-1981-001, Forwards LER 81-001/02L-0 (← links)