- 05000278/LER-1976-036-03, /03L:on 760504,recirculation Motor Generator Set 3B Tripped Due to Electrical Malfunction.Caused by Limitorque Valve Operator SMB-3 W/Serveral Broken Control Wires at Terminal Connections.Repairs Made & Valve Tested +
- 05000277/LER-1976-040-03, /03L:on 760509,gamma Scan Not Performed Prior to Two Liquid Effluent Releases.Caused by Lack of Radwaste Storage Capacity.Beta Activity Reviewed Prior to Release. Based on Previous Data,Limit Would Not Be Exceeded +
- 05000278/LER-1976-046-03, /03L:on 760512,main Steam Line High Temp Switch TS-5932C Failed to Trip Via Local Trip Test Pushbutton. Caused by Dirty Contacts on Circuit Board.Contacts Cleaned & Switch Tested Satisfactorily +
- 05000263/LER-1976-005, :on 760520,during 100% Power Operation,Tip Ball Valve 3 Failed to Close During Routine Use of TIP Sys. Cause Unknown.Valve Cleaned & Lubricated +
- IR 05000206/1975004 +
- 05000029/LER-1976-005-03, /03L-0:on 760520,auxiliary Operator Noted Slight Leakage from Weld on Inlet Charging Pump 3 Relief Valve. Caused by Pullback Gap Not Allowed During Installation of Pipe & Vibration Induced Fatigue Failure +