- IR 05000255/1993021 + (22:25:25, 26 May 2025)
- 05000366/LER-1990-002, :on 900114,RWCU Experienced Partial Primary Containment Isolation Sys Isolation Involving Outboard Isolation Valve.Caused by Component Failure & Less than Adequate Mounting of Relay.Relay Replaced + (22:25:29, 26 May 2025)
- IR 05000306/1993015 + (22:25:32, 26 May 2025)
- ML20058P534 + (22:25:34, 26 May 2025)
- IR 05000400/1993020 + (22:25:37, 26 May 2025)
- ML20058P091 + (22:28:52, 26 May 2025)
- IR 05000219/1990005 + (22:29:40, 26 May 2025)
- ML20058P057 + (22:29:50, 26 May 2025)
- 05000499/LER-1993-008, On 930505,discovered Failure to Maintain Enviromental Qualifications of a RHR Motor Operated Valve.Caused by Lack of Knowledge Regarding Requirements to Maintain Environ Qualifications + (22:30:17, 26 May 2025)
- 05000316/LER-1990-007, :on 900717,accumulated Leakage Found While Performing Type B & C Leak Rate Tests on Containment Penetrations Exceeded Tech Spec 3.6.1.2.b.Caused by Degradation of Isolation Valve Seating Svcs + (22:30:42, 26 May 2025)
- ML20058N940 + (22:30:46, 26 May 2025)
- NUREG-1365, Discusses Three Issues Currently Being Tracked by Generic Issue Mgt Control Sys.Issues Include Behavior of Severely Damaged Fuel,Behavior of Core Melt & Effect of Hydrogen Combustion on Containment Structures + (22:31:25, 26 May 2025)
- ML20058N838 + (22:31:29, 26 May 2025)
- ML20058N641 + (22:33:14, 26 May 2025)
- 05000499/LER-1992-009, :on 921217,TS Surveillance Requirements Were Missed Due to Faulty Toxic Gas Monitoring Sys Modem.Replaced Faulty Modem & Verified Sys Operating Properly + (22:33:21, 26 May 2025)
- ML20058N591 + (22:33:34, 26 May 2025)
- ML20058N587 + (22:33:37, 26 May 2025)
- 05000213/LER-1993-004, :on 930512,control Switches for Swps B & C Placed in Trip Pullout Resulting in Entry Into TS 3.0.3. Caused by Procedural Inadequacy.Associated Procedure Sur 5.7-148B Revised + (22:33:50, 26 May 2025)
- ML20058N470 + (22:34:32, 26 May 2025)
- ML20058N443 + (22:34:50, 26 May 2025)
- ML20058N428 + (22:34:57, 26 May 2025)
- ML20058N423 + (22:35:00, 26 May 2025)
- ML20058N386 + (22:35:17, 26 May 2025)
- ML20058N378 + (22:35:22, 26 May 2025)
- L-93-057, Forwards Addl Info Re 931124 Application for Renewal of License SNM-33 on Environ Assessment,Including Explanation of Substantive Changes from Previous Renewal Submittals & Replacement Pages to Renewal Application + (22:35:31, 26 May 2025)
- NUREG-1200, Summarizes NRC 900706 Discussion W/Officials Involved in Low Level Waste Disposal in PA Re NRC Guidance Documents Including Std Format & Content Guide & Std Review Plan.List of Attendees Also Encl + (22:35:36, 26 May 2025)
- IR 05000528/1993017 + (22:35:48, 26 May 2025)
- IR 05000327/1993002 + (22:35:51, 26 May 2025)
- ML20058N315 + (22:35:55, 26 May 2025)
- IR 05000313/1990004 + (22:37:35, 26 May 2025)
- 05000328/LER-1990-005, :on 900315,inadvertent Containment Vent Isolation Event Occurred While Preparing to Purge Containment.Caused by Personnel Error.Individual Counseled + (22:37:42, 26 May 2025)
- ML20058N064 + (22:38:08, 26 May 2025)
- 05000440/LER-1990-005, :on 900405,HPCS Declared Inoperable Due to Fuel Oil Sediment Exceeding Tech Spec Limits.Caused by Fuel Oil & Storage Tank Degradation,Due to Contaminant in Biocide Additive.Contaminated Biocide Additive Removed + (22:38:30, 26 May 2025)
- ML20058M949 + (22:38:56, 26 May 2025)
- ML20058M578 + (22:41:45, 26 May 2025)
- ML20058M561 + (22:41:55, 26 May 2025)
- 05000395/LER-1993-002, :on 930318,determined 1 Percent of SG Tubes Defective.Caused by Pwscc.Defective Tubes Plugged + (22:42:51, 26 May 2025)
- IR 05000271/1993013 + (22:43:04, 26 May 2025)
- 05000458/LER-1993-006, Provides Addl Info Re Failure of MSIV to Close Re LER 93-006.Atwood & Morrill Has Participated in Corrective Actions by Designing & Mfg 8 MSIV Mod Kits to Be Installed by Util + (22:43:08, 26 May 2025)
- ML20058M415 + (22:43:26, 26 May 2025)
- 05000482/LER-1993-008, :on 930416,flux Doubling Circuit Blocked Due to Personnel Error Re Misunderstanding of Applicability of Ts. Issued Memo & Initiated Change to TS Bases + (22:44:21, 26 May 2025)
- ML20058M250 + (22:44:53, 26 May 2025)
- ML20058M188 + (22:45:15, 26 May 2025)
- 05000458/LER-1990-011, :on 900326,faulted Condition on Transformer 1NJS-X1A Resulted in Trip of Circuit Breaker ACB-016 on Switchgear 1NJS-SWGR1A.Caused by Random Failure of Transformer.Tranformer Replaced + (22:45:29, 26 May 2025)
- 05000302/LER-1989-035, :on 890906,determined Safety Related Components Were Exposed to Voltages in Excess of Mfg Stated Voltage Ratings Due to Inadequate Control of Design Process.Replaced Inoperable Items W/High Voltage Components + (22:45:58, 26 May 2025)
- ML20058M109 + (22:46:07, 26 May 2025)
- ML20058M069 + (22:46:41, 26 May 2025)
- L-93-058, Forwards Response to NRC 931110 RAI Re Decommissioning Funding Plan Submitted on 930528 + (22:47:08, 26 May 2025)
- ML20058L987 + (22:47:17, 26 May 2025)
- ML20058L979 + (22:47:21, 26 May 2025)
- TXX-9319, Forwards Rev 2 to CPSES Glen Rose,Tx ASME Section XI ISI Program Plan,Unit 1 Commercial Operation:900813 First Interval + (22:48:00, 26 May 2025)