Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000366/LER-1980-106-03, W/Reactor in Cold Shutdown,Insp of Drywell Insulation Revealed Crystalline Deposits Around Seams on Sacrificial Shield.Cause Unknown. Investigation Inconclusive + (10:27:45, 26 May 2025)
- 05000366/LER-1983-081-03, /03L-0:on 830829,during Performance of Procedure HNP-2-3309,personnel Determined HPCI Turbine Exhaust Diaphragm Pressure Switch Out of Calibr.Caused by Instrument Setpoint Drift.Switch Recalibr + (10:27:57, 26 May 2025)
- 05000416/LER-1983-127-03, /03L-0:on 830822,during Surveillance Testing, Control Room Ventilation Radiation Monitor Channel B & Channel C hi-hi Setpoints Exceeded Allowable Values.Caused by Instrument Drift + (10:27:58, 26 May 2025)
- TAC:M89901 + (10:28:11, 26 May 2025)
- ML20080L635 + (10:28:18, 26 May 2025)
- 05000220/LER-1983-024-04, /04L-0:during May,Lower Limit of Detection Sensitivity for Fish Analysis Sample Data Not Met for Many Radionuclide Samples.Caused by Incorrect Converting of LLD Values + (10:28:27, 26 May 2025)
- 05000346/LER-1983-033-03, Fire Detection Zone Reactor Coolant Pump 1-2,containment Level 603 Went Into Alarm & Could Not Be Reset.Caused by Failed Smoke Detector.Detector Replaced + (10:28:29, 26 May 2025)
- 05000346/LER-1981-077-03, During Surveillance Test ST5016.11 Numerous Conduit Pull Boxes Discovered W/Unsealed Fire Resistant Matl.Fire Watch Stationed + (10:28:49, 26 May 2025)
- A830020, Provides List of Valves Performing Pressure Isolation Function Between High & Low Pressure Sys for RCPB Per NRC 830718 Request + (10:29:06, 26 May 2025)
- TXX-9500, Provides Addl Info Describing Activities That Util Has Performed to Verify Quality of Procured & Installed Thermo- Lag & to Ensure That Thermo-Lag at Plant Properly Qualified + (10:29:17, 26 May 2025)
- U-602412, Provides Info Updating Risks of Flammable & Toxic Hazards Associated W/Railroad Transportation Past Plant + (10:29:29, 26 May 2025)
- ML20080K967 + (10:29:42, 26 May 2025)
- ML20080K815 + (10:29:54, 26 May 2025)
- ML20080K564 + (10:30:28, 26 May 2025)
- EPID:L-2019-LLR-0095 + (10:30:34, 26 May 2025)
- ML20080K506 + (10:30:35, 26 May 2025)
- ML20080K110 + (10:31:25, 26 May 2025)
- TAC:54253 + (10:31:37, 26 May 2025)
- EPID:L-2019-LLR-0082 + (10:32:04, 26 May 2025)
- ML20080J718 + (10:32:12, 26 May 2025)
- ML20080J666 + (10:32:18, 26 May 2025)
- TAC:M79407 + (10:33:10, 26 May 2025)
- ML20080H892 + (10:34:09, 26 May 2025)
- ML20080H787 + (10:34:17, 26 May 2025)
- ML20080H680 + (10:34:24, 26 May 2025)
- L-83-152, Interim Deficiency Rept,Item S-11 Re High Strength Bolting of Structural Steel Connections.Initially Reported on 830513.Formal Submittal of Quality Confirmation Program Will Be Made by 831101 + (10:35:55, 26 May 2025)
- ML20080H033 + (10:36:15, 26 May 2025)
- TAC:49199 + (10:36:27, 26 May 2025)
- 05000325/LER-1979-056-03, Main Steam Line Hi Radiation Monitor B Found Actuating at 3.95 Times Background,Above Allowable Limit.Caused by Instrument Drift. Monitor Recalibr + (10:36:59, 26 May 2025)
- ML20080G747 + (10:37:02, 26 May 2025)
- ML20080G390 + (10:37:57, 26 May 2025)
- TAC:M74973 + (10:38:25, 26 May 2025)
- 05000346/LER-1982-045-03, Auxiliary Feedwater Pump 1-1 Suction Valve FW786 Closed W/O Operator Touching Close Button.Cause Unknown.Valve Reopened.Surveillance Test Performed + (10:38:29, 26 May 2025)
- ML20080G100 + (10:38:50, 26 May 2025)
- 05000333/LER-1983-022-03, /03X-1:on 830607,during Performance of Local Leak Rate Testing,Containment Spray Penetration X-39A Found W/Leakage Exceeding 0.6 La.Caused by Normal Use.Valve Seal, Disc &/Or Seat Surfaces Replaced + (10:39:05, 26 May 2025)
- ML20080F747 + (10:39:36, 26 May 2025)
- TAC:52540 + (10:40:25, 26 May 2025)
- ML20080D876 + (10:42:33, 26 May 2025)
- ML20080D807 + (10:42:38, 26 May 2025)
- 05000249/LER-1982-049-03, Diesel Generator D-3 Failed to Start Twice Following Semiannual Insp.Caused by Worn Out Cylinder & Accumulation of Dust Inside Air Starter. Ingersoll-Rand Air Starter Replaced + (10:43:34, 26 May 2025)
- A03121, Provides Followup Response to Item 5 of IE Bulletin 83-03, Check Valve Failures in Raw Water Cooling Sys of Diesel Generator. Inservice Test Program Will Be Modified to Reflect Addl Insp to Assess Wear Rates + (10:44:50, 26 May 2025)
- L-94-038, Forwards Public & Central Files Versions of Revised Epips. Central Files Version of Revised EPIPs Withheld + (10:46:07, 26 May 2025)
- ML20080B493 + (10:47:31, 26 May 2025)
- ML20080A744 + (10:49:12, 26 May 2025)
- 05000387/LER-1983-088-03, RCIC Pump Discharge Valve Failed to Open.Caused by Gaps Between Breaker Male & Female Stab Clips.Investigations Revealed Lack of Clearance in GE 7700 Control Ctrs.Procedures Revised + (10:49:14, 26 May 2025)
- ML20080A720 + (10:49:19, 26 May 2025)
- ML20080A709 + (10:49:21, 26 May 2025)
- 05000259/LER-1983-072-03, /03L-0:on 831227,mean Sea Level Wind Speed Recorder XR-90-104 Read Zero.Caused by Ice Formation on Wind Speed Sensor + (10:50:01, 26 May 2025)
- 05000362/LER-1983-111-03, /03L-0:on 831222,RCS Specific Activity Exceeded 1.0 Mci/G Dose Equivalent I-131.Caused by Iodine Spiking Following Power Changes Associated W/Two Reactor Trips. Purification Flow Increased + (10:50:07, 26 May 2025)
- 05000278/LER-1983-024-03, /03L-0:on 831219,moisture Sensor in Moisture Monitoring Sys Failed.Caused by Defective Techmark Limited Sensor.Inoperable Sensor Will Be Replaced During Next Scheduled or Forced Outage + (10:50:23, 26 May 2025)
- 05000366/LER-1983-047-03, /03L-0:on 830621,vacuum Breaker 2B21-F110B Found Stuck in Open Position.Caused by Bent Hinge Pin.Breaker Replaced + (10:50:28, 26 May 2025)