Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19351E672 + (22:57:08, 23 December 2024)
- ML19351E671 + (22:57:09, 23 December 2024)
- ML19351E670 + (22:57:10, 23 December 2024)
- ML19351E669 + (22:57:11, 23 December 2024)
- ML19351E668 + (22:57:13, 23 December 2024)
- ML19351E667 + (22:57:14, 23 December 2024)
- ML19351E666 + (22:57:15, 23 December 2024)
- ML19351E665 + (22:57:16, 23 December 2024)
- ML19351E664 + (22:57:18, 23 December 2024)
- ML19351E662 + (22:57:21, 23 December 2024)
- ML19351E660 + (22:57:23, 23 December 2024)
- ML19351E659 + (22:57:24, 23 December 2024)
- 05000324/LER-1980-094-03, /03L-0:on 801111,primary Containment Atmospheric monitor,2-CAC-ATH-1263,Beckman Model F3,observed Indicating Upscale.Caused by Defective Oxygen Analyzer & Defective Monitor Photohelic Unit.Analyzer & Unit Replaced + (22:57:31, 23 December 2024)
- 05000339/LER-1980-087-03, /03L-0:on 801029 Axial Flux Difference Twice Deviated Greater than 5% from Target.Caused by 10% Load Swing & 50% Load Rejection from 100% Power for Startup Testing.Power & Control Rod Manipulations Performed + (22:57:33, 23 December 2024)
- 05000324/LER-1980-094, Forwards LER 80-094/03L-0 + (22:57:38, 23 December 2024)
- 05000317/LER-1980-062-03, /03L-0:on 801103 & 04,LPSI Pump 12 Tripped Off, Causing Temporary Loss of Shutdown Cooling.Apparently Caused by Spurious Reactor Analysis & Safety Signals Received While re-energizing Actuation Sys + (22:57:40, 23 December 2024)
- 05000317/LER-1980-063-03, /03L-0:on 801106,control Room Air Conditioning Unit Failed to Start.Cause Undetermined.Simulation of Control Imputs to Breaker 52-1108 & Initiation of Shutdown Sequencer Performed + (22:57:42, 23 December 2024)
- 05000339/LER-1980-087, Forwards LER 80-087/03L-0 + (22:57:44, 23 December 2024)
- 05000364/LER-1980-002-01, /01T-0:on 801126,during Insp on Msivs,Damage to Valve Disc Bolt Holes & Disc Arm Bolting on Three Downstream MSIVs Discovered.Caused by Design Deficiency.Design Change Will Be Implemented Prior to Initial Startup + (22:57:46, 23 December 2024)
- 05000317/LER-1980-062, Forwards LER 80-062/03L-0 + (22:57:48, 23 December 2024)
- 05000317/LER-1980-063, Forwards LER 80-063/03L-0 + (22:57:52, 23 December 2024)
- 05000318/LER-1980-053-03, /03L-0:on 801101 & 07,containment Atmosphere Particulate Monitor Failed.Caused by Loosened Channel Field Cable Leads Due to Improper Crimping.New Connectors Properly Installed + (22:57:54, 23 December 2024)
- 05000364/LER-1980-002, Forwards LER 80-002/01T-0 + (22:57:55, 23 December 2024)
- 05000318/LER-1980-053, Forwards LER 80-053/03L-0 + (22:57:59, 23 December 2024)
- TXX-3220, Responds to NRC Re Violations Noted in IE Insp Repts 50-445/80-20 & 50-446/80-20.Corrective Actions:Qa Personnel Will Perform Inprocess & Release Insp of Future Shipments from Supplier + (22:58:00, 23 December 2024)
- ML19351E630 + (22:58:03, 23 December 2024)
- ML19351E627 + (22:58:05, 23 December 2024)
- 05000409/LER-1980-009-03, /03L-0:on 801027,mechanical Interlock Preventing Containment Bldg Personnel Airlock Doors from Opening Simultaneously Found Inoperable.Caused by Stripped Door Link Subassembly.Door Guarded & Padlocked & Subassembly Repaired + (22:58:09, 23 December 2024)
- 05000409/LER-1980-010-03, /03L-0:on 801028,shutdown Condenser Control Valve Quarterly Test Performed Approx 4-h Beyond Deadline.Caused by Personnel Error.Test Performed & Supervisor Will Check Schedule More Closely in Future + (22:58:13, 23 December 2024)
- ML19351E622 + (22:58:14, 23 December 2024)
- 05000409/LER-1980-009, Forwards LER 80-009/03L-0 & Updated LER 80-005/01T-1 + (22:58:16, 23 December 2024)
- 05000409/LER-1980-010, Forwards LER 80-010/03L-0 + (22:58:19, 23 December 2024)
- 05000348/LER-1980-073-01, /01T-0:on 801126,during Insp of Msivs,Damage to Valve Disc Bolt Holes & Disc Arm Bolting on Three Valves Was Revealed.Caused by Design Deficiency & Inadequate Locking Devices on Bolting.Discs Will Be Repaired or Replaced + (22:58:21, 23 December 2024)
- 05000267/LER-1980-066-03, /03L-0:on Eleven Occasions During 801105-18,plant Operated W/Primary Coolant Oxidants Greater than 10 Ppm & Average Core Outlet Temp Greater than 1,200 F.Caused by Residual Moisture & Leakage Past HV-21352 + (22:58:25, 23 December 2024)
- 05000348/LER-1980-038-03, /03L-0:on 800712,bistable Associated W/Pressurizer Pressure Transmitter 457 Failed to Meet Low Pressure Trip Setpoint Requirements & One Pressure Channel Declared Inoperable.Caused by Dirty Electric Contacts + (22:58:27, 23 December 2024)
- 05000348/LER-1980-073, Forwards LER 80-073/01T-0 + (22:58:30, 23 December 2024)
- 05000267/LER-1980-066, Forwards LER 80-066/03L-0 + (22:58:34, 23 December 2024)
- ML19351E603 + (22:58:37, 23 December 2024)
- 05000259/LER-1980-062, Has Been Cancelled + (22:58:39, 23 December 2024)
- 05000267/LER-1980-071-03, /03L-0:on 801106,malfunction of Helium Circulator 1B Speed Modifier Caused Loss of Plant Protective Sys Function of High Speed Trips to One of Three Channels.Caused by Resistance Change in Speed Element Cable Assembly + (22:58:41, 23 December 2024)
- 05000259/LER-1980-067, Has Been Cancelled + (22:58:43, 23 December 2024)
- ML19351E597 + (22:58:46, 23 December 2024)
- 05000267/LER-1980-071, Forwards LER 80-071/03L-0 + (22:58:48, 23 December 2024)
- ML19351E594 + (22:58:49, 23 December 2024)
- ML19351E593 + (22:58:50, 23 December 2024)
- ML19351E591 + (22:58:51, 23 December 2024)
- ML19351E590 + (22:58:52, 23 December 2024)
- 05000267/LER-1980-069-03, /03L-0:on 801107,two Circulator 1D High Speed Trip Channels,One for Steam Turbine & One for Water Turbine,Found to Have Trip Points Higher than Max Allowable.Caused by Bistable Instrument Drift.Bistables Adjusted + (22:58:53, 23 December 2024)
- 05000267/LER-1980-069, Forwards LER 80-069/03L-0 + (22:58:55, 23 December 2024)
- 05000285/LER-1980-029-03, /03L-0:on 801106,outboard Motor Bearing on Containment Spray Pump SI-3C Motor Found Severely Degraded & Motor Shaft Scored.Probably Caused by Lack of Oil to Bearing.Bearing Replaced & Rotor Shaft Repaired + (22:58:57, 23 December 2024)
- ML19351E584 + (22:58:58, 23 December 2024)