Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000280/LER-1981-015-03, /03L-0:on 810603,spent Fuel Pit Overflowed Into New Fuel Handling Area & Outside to Storm Drain.Caused by Leaking Diaphragm Valve & Defeated High Level Alarm Annunciator.Valve Repaired + (13:17:25, 21 December 2024)
- 05000366/LER-1981-067, Forwards LER 81-067/03L-0 + (13:17:28, 21 December 2024)
- 05000280/LER-1981-015, Forwards LER 81-015/03L-0,updated LER 81-035/03X-1 & Corrected LER 81-036/03L-0 + (13:17:30, 21 December 2024)
- 05000339/LER-1981-047-03, /03L-0:on 810609,solid State Protection Sys Train B Stop Valve Generator Trip Logic Failed to Meet Acceptance Criteria.Caused by Faulty Universal Card A404. Card Replaced & Logic Channel Returned to Svc + (13:17:34, 21 December 2024)
- ML20009F707 + (13:17:35, 21 December 2024)
- 05000339/LER-1981-047, Forwards LER 81-047/03L-0 + (13:17:37, 21 December 2024)
- 05000366/LER-1981-061-03, /03L-0:on 810624,hi-lo Flow Alarm Received for Reactor Bldg Vent Radiation Monitor Sys.Caused by Tripping of Sample Pumps a & B Due to Overload Protection Tripping. Vanes in Pump a Replaced.Pump B Overload Reset + (13:17:44, 21 December 2024)
- 05000327/LER-1981-065-03, /03L-0:on 810603,turbine Sump Discharge Monitor O-RM-90-212 Declared Inoperable.Caused by Broken Pump/Motor Coupling.Coupling Replaced & Monitor Returned to Svc + (13:17:45, 21 December 2024)
- ML20009F700 + (13:17:48, 21 December 2024)
- 05000369/LER-1981-076-03, /03L-0:on 810502,alarm Annunciated for Noble Gas Activity monitor,EMF-33,indicating Loss of Sample Flow During Initial Fuel Loading.Caused by Bolts Insufficiently Tightened to Secure Seals During Monitor Maint + (13:17:52, 21 December 2024)
- ML20009F697 + (13:17:52, 21 December 2024)
- ML20009F695 + (13:17:54, 21 December 2024)
- 05000369/LER-1981-076, Forwards LER 81-076/03L-0.Detailed Event Analysis Encl + (13:17:55, 21 December 2024)
- 05000369/LER-1981-072-03, /03L-0:on 810427,RHR Sys Discovered Isolated from RCS During Mod of Train a Solid State Protection Sys to Include Reactor on Turbine Trip.Caused by de-energized Relay in Logic,Closing Isolation Valve + (13:17:57, 21 December 2024)
- 05000327/LER-1981-065, Forwards LER 81-065/03L-0 + (13:17:58, 21 December 2024)
- ML20009F686 + (13:17:59, 21 December 2024)
- 05000366/LER-1981-061, Forwards LER 81-061/03L-0 + (13:18:02, 21 December 2024)
- 05000369/LER-1981-072, Forwards LER 81-072/03L-0.Detailed Event Analysis Encl + (13:18:06, 21 December 2024)
- ML20009F680 + (13:18:09, 21 December 2024)
- 05000302/LER-1981-039-03, /03L-0:on 810630,control Rod Units 1 & 2 Rendered Inoperable During Maint on House Svcs Transformer.Caused by Personnel Shorting 4,160-volt Bus Supplying Startup Transformer While Checking Energized Sections + (13:18:12, 21 December 2024)
- 05000366/LER-1981-065-03, /03L-0:on 810626,hydrogen-oxygen Analyzer Found Inoperable.Caused by Partially Clogged Gas Flow Regulators. Gas Flow Regulators Cleaned & Readjusted.Analyzer Recalibr + (13:18:14, 21 December 2024)
- ML20009F675 + (13:18:15, 21 December 2024)
- ML20009F674 + (13:18:15, 21 December 2024)
- 05000302/LER-1981-039, Forwards LER 81-039/03L-0 + (13:18:16, 21 December 2024)
- ML20009F671 + (13:18:17, 21 December 2024)
- ML20009F669 + (13:18:18, 21 December 2024)
- 05000260/LER-1981-034-03, /03L-0:on 810630,RHR Svc Water Pumps B2,D-1 & D-2 Were Not in Svc.Caused by Removing B2 from Svc to Change Motor Oil & Tagging Closed Crosstie Valve to Unit 1, FCV-1-74-100.Oil Changed + (13:18:19, 21 December 2024)
- 05000260/LER-1981-031-03, /03L-0:on 810701,RHR Pump Room Cooler 3-A Developed Water Leak.Caused by Broken Silfos Joint on 1/4-inch Vent Line.Joint Resoldered + (13:18:20, 21 December 2024)
- ML20009F666 + (13:18:22, 21 December 2024)
- 05000339/LER-1981-054-03, /03L-0:on 810629,train J of Onsite Ac Power Sys Discovered Not Tested Per Tech Specs Since 790316.Caused by Mistaken Impression That Both Buses Were Retested on 800331.Emergency Bus J Tested on 800331 + (13:18:24, 21 December 2024)
- 05000260/LER-1981-034, Forwards LER 81-034/03L-0 + (13:18:25, 21 December 2024)
- 05000366/LER-1981-065, Forwards LER 81-065/03L-0 + (13:18:26, 21 December 2024)
- ML20009F659 + (13:18:27, 21 December 2024)
- ML20009F658 + (13:18:29, 21 December 2024)
- 05000260/LER-1981-031, Forwards LER 81-031/03L-0 + (13:18:30, 21 December 2024)
- 05000348/LER-1981-045-03, /03L-0:on 810613,train Svc Water Loop a Declared Inoperable.Caused by Inoperable Emergency Recirculation Valve Due to Blown Control Circuit Fuse.Fuse Replaced,Valve Tested & Loop Returned to Svc on 810613 + (13:18:31, 21 December 2024)
- 05000339/LER-1981-054, Forwards LER 81-054/03L-0 + (13:18:33, 21 December 2024)
- ML20009F652 + (13:18:34, 21 December 2024)
- ML20009F650 + (13:18:35, 21 December 2024)
- 05000369/LER-1981-082-03, /03L-0:on 810504-22,fire Detection Sys Found Inoperable.Caused by Const in Area.Fire Watches & Patrols Established + (13:18:36, 21 December 2024)
- 05000335/LER-1981-027-03, /03L-0:on 810519,while Cleaning Condenser Water Boxes,Control Element Assembly 65 Dropped While Being Inserted.Cause Unknown.Assembly Returned to Group Position + (13:18:38, 21 December 2024)
- 05000348/LER-1981-044-03, /03L-0:on 810610,diesel Generator 1C Declared Inoperable During Test FNP-1-STP-28.1.Caused by Overvoltage Condition Due to Damaged Voltage Regulator Circuitry Resulting from Failed Engine Running Relay + (13:18:39, 21 December 2024)
- 05000369/LER-1981-095-03, /03L-0:on 810606,flow Rate Measurement Instrumentation on Waste Monitor Tank a Declared Inoperable During Attempted Liquid Water Release.Caused by Supply Air Isolation Valve to Transmitter Left Closed Following Maint + (13:18:40, 21 December 2024)
- 05000321/LER-1981-057-03, /03L-0:on 810611,temporary Change to HNP-1-6907 (Reactor Core Isolation Cooling Pump Suction Hydro) Found Not Approved by Mgt within Reguired Time.Caused by Personnel Failure to Maintain Adequate Control Over Procedure + (13:18:42, 21 December 2024)
- 05000369/LER-1981-082, Forwards LER 81-082/03L-0 + (13:18:43, 21 December 2024)
- ML20009F640 + (13:18:44, 21 December 2024)
- 05000335/LER-1981-027, Forwards LER 81-027/03L-0 + (13:18:45, 21 December 2024)
- 05000369/LER-1981-077-01, /01T-0:on 810521,ASME Code Rejectable Indications Found in Vendor Seal Plate to Door Frame Welds During Nondestructive Exam of Personnel Lock Shim Plate Welds. Caused by Use of Seal Rather than Structural Welds + (13:18:47, 21 December 2024)
- 05000369/LER-1981-095, Forwards LER 81-095/03L-0 + (13:18:48, 21 December 2024)
- 05000364/LER-1981-025-03, /03L-0:on 810604,steam Jet Air Ejector Noble Gas Activity Monitor RE-15 Failed Low.Caused by Faulty Connection at Detector.Condition Corrected & Monitor Returned to Svc on 810615 + (13:18:51, 21 December 2024)
- ML20009F633 + (13:18:52, 21 December 2024)