ML20009F652

From kanterella
Jump to navigation Jump to search
Revised Final Deficiency Rept Re Differential Pressure Indicators on Air Cleanup Units,Initially Reported on 800801.Indicator Panel Will Be Removed & Connection Lines Retubed on Back by 810821.Also Reported Per Part 21
ML20009F652
Person / Time
Site: Bellefonte  
Issue date: 07/16/1981
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21- 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8107310382
Download: ML20009F652 (2)


Text

-

OPPICIAL copy 400 Chestnut Street Tower ~II July 16, 1981 N

Mr. James P. O'Reilly, Director Office of Inspection and Enforcement j

yf, U.S. Nuclear Regulatory Commission b

I Region II - Suite 3100 W-

~

' gfQ 101 Marietta Street

.j yp#

Atlanta, Georgia 30303 m

f/

Dear Mr. O'Reilly*

n'

./ NFh8 BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - DIFFERENTIAL SUREhNDICATORS ON AIR CLEANUP UNITS - NCR 1237 - REVISED FINAL REPORT The subject nonconformance was initially reported to NRC-0IE Inspector L W.

Wright on August 1, 1980, in accordance with 10 CFR 50.55(e).

Interim reports were cubmitted August 29 and November 10, 1980, and our final report was submitted April 9, 1981. We consider 10 CFR Part 21 to be applicable to this deficiency. As discussed with R. V. Crlenjak by telephone on July 14, 1981, enclosed is our revised final report. The reason for the revision is to change the expcoted completion date of the corrective action. The date for completion has been delayed because of the extent of the rework required.

If you have any questions concering this matter, please get in touch with D. L. Lambert at FTS 857-2581.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Regulation and Safety Enclosure cc:

Mr. Victor Stello, Jr., Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 i

s i) 8107310302 010716 PDR ADOCK 05000438 S

PDR

A e

ENCLOSURE BELLEFCNTE NUCLEAR PLANT' UNITS 1'AND.2 DIFFERENTIAL PRESSURE INDICATORS ON AIR CLEANUP UNITS NCR 1237 - 10CFR50.55(e)

REVISED FINAL REPORT Description of Deficiency The differential pressure indicators, on t'e majority of the air cleanup h

i units provided by ClI-Nuclear, are improperly tubed..

Safety Implications The differential pressure indicLtors are required to notify plant personnel of the need to change the filters to prevent clogging. Because these specific air cleanup units operate continuously at Bellefonte and are also required postaccident, the filters must not be allowed to become clogged.

Should they become clogged, low airflow would result and the required l

negative pressure in the Auxiliary Building could not be maintained. Thus, l

had this item gone undeteuted, it could have adversely affected safe operation of the plant.

i Corrective Action l

l CTI-Nuclear representatives met with TVA representatives at the Bellefonte site and agreed chat a majority of the differential pressure indicators were improperly connected to the sampling lines.

Agreement was reached l

that the best solution to the concern would be to remove the indicator panel and retube the connection lines on the back of the panels. TVA is to proceed with the recommended solution. TVA expects to complete the work by August 21, 1981.

CTI-Nuclear has certified that if TVA retubes the back of the indicator panel with the same type and quality of tubing and fittings used originally, that the equipment meets the seismic qualification requirements of the contract and that CTI-Nuclearis original warranty is still valid.

As all material and equipment on this contract has been delivered to the jobsite, no action to prevent recurrence at Bellefonte has been initiated.

TVA is continually reviewing CTI-Nuclear's quality program.

The only other TVA site to verify similar conditions for the CTI-Nuclear air cleanup units was Watts Bar. However, the pressure indicators are only for local indication and are not safety related.