- 05000366/LER-1981-075, Forwards LER 81-075/03L-0 + (11:26:12, 21 December 2024)
- 05000324/LER-1981-075-03, /03L-0:on 810801,temp Readout Points 1,3,4 & 7 of Temp Recorder 2-CAC-TR-778 on Remote Shutdown Panel Indicated Downscale.Caused by Periodic Upscale Driving of Recorder Print Mechanism Against Mechanical Stop + (11:26:14, 21 December 2024)
- ML20010E753 + (11:26:16, 21 December 2024)
- 05000369/LER-1981-126-01, /01T-0:on 810810,Channel 1 of Engineered Safety Features Instrumentation for Refueling Water Storage Tank Level Failed.Caused by Drift Due to Faulty Transmitter,Model 386.Personnel Failed to Trip Channel.Transmitter Replaced + (11:26:17, 21 December 2024)
- 05000324/LER-1981-075, Forwards LER 81-075/03L-0 + (11:26:19, 21 December 2024)
- 05000369/LER-1981-126, Forwards LER 81-126/01T-0.Detailed Event Analysis Encl + (11:26:21, 21 December 2024)
- 05000327/LER-1981-099-03, /03L-0:on 810731,RHR Check Valves 1-74-514 & 1-74-515 Found Not Tested within Required Time Limit.Caused by Special Performance Package of SI-166.Fifteen Issued W/O Dates.Valves Tested on 810806 + (11:26:22, 21 December 2024)
- 05000302/LER-1981-051-01, /01T-0:on 810813,determined That Concrete Embedments in Wall of Cable Spreading Room Might Not Support Design Live Load Conditions.Caused by Reclassification of Floor in 1978 Requiring Seismic Load Design + (11:26:24, 21 December 2024)
- 05000369/LER-1981-125-03, /03L-0:on 810728,Channel 4 Overtemp Delta T Instrumentation of Reactor Protection Sys Found Out of Calibr.Caused by Faulty Card in Overtemp Delta T Solid State Circuitry.Card Replaced + (11:26:26, 21 December 2024)
- 05000327/LER-1981-099, Forwards LER 81-099/03L-0 + (11:26:27, 21 December 2024)
- 05000369/LER-1981-125, Forwards LER 81-125/03L-0 + (11:26:29, 21 December 2024)
- 05000338/LER-1981-067-03, /03L-0:on 810811,individual Rod Position Indication for Rod D-10 Deviated from Group Demand Position by Greater than 12 Steps.Caused by Instrument Drift Rod Position Indicator Channel Recalibr + (11:26:35, 21 December 2024)
- 05000302/LER-1981-051, Forwards LER 81-051/01T-0 + (11:26:36, 21 December 2024)
- 05000338/LER-1981-067, Forwards LER 81-067/03L-0 + (11:26:42, 21 December 2024)
- 05000321/LER-1981-082-03, /03L-0:on 8710728,HPCI Steam Line Switch 1E41-N005 Failed to Actuate on Simulated High Flow.Caused by Setpoint Drift.Barton Flow Switch Recalibr & Returned to Svc + (11:26:44, 21 December 2024)
- 05000339/LER-1981-063-03, /03L-0:on 810806 & 17,pressure in Both Pressurizer Power Operated Relief Valve Nitrogen Supply Tanks Dropped Below Design Basis Limit for Low Temp RCS Overpressurization Protection.Caused by Leaks in Both Supply Sys + (11:26:45, 21 December 2024)
- ML20010E727 + (11:26:47, 21 December 2024)
- 05000339/LER-1981-063, Forwards LER 81-063/03L-0 + (11:26:49, 21 December 2024)
- 05000321/LER-1981-082, Forwards LER 81-082/03L-0 + (11:26:50, 21 December 2024)
- 05000293/LER-1981-045-03, /03L-0:on 810730,rod 22-11 Found to Have Scram Time Exceeding Tech Spec Limit.Probably Caused by Excessive Seal Leakage.Rod Being Monitored & Future Scram Times Will Be Evaluated + (11:26:52, 21 December 2024)
- AECM-81-295, Corrected Final Deficiency Rept Re Mechanical Connections in GE Termination Blocks,Initially Reported 810305.Review Determined Full Thread Engagement on Both Sides of Mechanical Connection Screw.No Corrective Action Required + (11:26:53, 21 December 2024)
- ML20010E720 + (11:26:56, 21 December 2024)
- 05000293/LER-1981-045, Forwards LER 81-045/03L-0 + (11:26:57, 21 December 2024)
- L-81-368, Final Deficiency Rept Re Reliance Electric Supplied Class IE Microswitch Housings,Initially Reported 810624.Panel Tab Slot Modified,Locking Rings Provided & Switches Installed Following Nonconformance Rept Procedure + (11:26:58, 21 December 2024)
- 05000271/LER-1981-022-03, /03L-0:on 810801,MSIV-80D Failed to Close When Control Switch Was Placed in Closed Position.Caused by Foreign Particle Lodged in Spool Valve,Preventing Air from Operating Main Piston.Msiv Fully Stroked + (11:27:00, 21 December 2024)
- 05000271/LER-1981-022, Forwards LER 81-022/03L-0 + (11:27:02, 21 December 2024)
- ML20010E713 + (11:27:03, 21 December 2024)
- AECM-81-292, Final Deficiency Rept Re RHR Pump B Damage Sustained During Const Testing,Initially Reported 810116.Worn Internal Pump Parts & Seal Flange Bolts Replaced.Barrel Assembly Inspected & Barrel at Junction W/Barrel Flange Tested + (11:27:04, 21 December 2024)
- ML20010E711 + (11:27:05, 21 December 2024)
- 05000311/LER-1981-082-99, /99X-0:on 810603 & 27,inadvertent Safety Injection Occurred Following Turbine/Reactor Trip.Caused by High Steam Line Flow Conditions Set Up by Steam Driven Auxiliary Feedwater Pump Speed Oscillations + (11:27:07, 21 December 2024)
- 05000311/LER-1981-082, Forwards LER 81-082/99X-0.Detailed Event Analysis Encl + (11:27:08, 21 December 2024)
- 05000338/LER-1981-066-03, /03L-0:on 810804,Channel III Feedwater Flow Indicator for Steam Generator C Began Spiking High Periodically.Caused by Multiplier & Divider/Square Root Card Failure Causing Output of Card to Spike High + (11:27:10, 21 December 2024)
- PNO-I-81-100, on 810825,25 Mci Cs-137 well-logging Source Was Severed from Cable Near Bottom of 120-ft Deep Encased Well Into Coal Seam in Acosta,Pa.Recovery Attempts Unsuccessful.Hole Will Be Cemented & Labeled W/Plaque + (11:27:13, 21 December 2024)
- 05000338/LER-1981-066, Forwards LER 81-066/03L-0 + (11:27:17, 21 December 2024)
- 05000321/LER-1981-085-03, /03L-0:on 810805,reactor Core Isolation Cooling Steamline Switch Found to Actuate Above Tech Spec Limit. Caused by Setpoint Drift.Barton Model 288 Recalibr & Returned to Svc + (11:27:20, 21 December 2024)
- 05000271/LER-1981-021-03, /03L-0:on 810730,containment Isolation Valve V20-94 Failed to Close During Surveillance Testing.Possibly Caused by Normal Wear W/Accumulation of Minor Amounts of Dirt.Insp of Air Solenoid Valve Was Inconclusive + (11:27:22, 21 December 2024)
- 05000321/LER-1981-085, Forwards LER 81-085/03L-0 + (11:27:23, 21 December 2024)
- ML20010E699 + (11:27:24, 21 December 2024)
- 05000271/LER-1981-021, Forwards LER 81-021/03L-0 + (11:27:26, 21 December 2024)
- ML20010E696 + (11:27:28, 21 December 2024)
- JAFP-81-0897, Forwards Effluent & Waste Disposal Semiannual Rept,Jan- June 1981 + (11:27:30, 21 December 2024)
- ML20010E695 + (11:27:30, 21 December 2024)
- ML20010E691 + (11:27:32, 21 December 2024)
- ML20010E689 + (11:27:33, 21 December 2024)
- ML20010E688 + (11:27:34, 21 December 2024)
- ML20010E685 + (11:27:35, 21 December 2024)
- 05000327/LER-1981-098-03, /03L-0:on 810731,temp Recorder 1-TR-61-138 for Ice Condenser Temp Monitoring Sys Observed to Be Operating Erratically Rendering Ice Condenser Monitoring Sys Inoperable.Caused by Faulty Selector Switch + (11:27:36, 21 December 2024)
- ML20010E682 + (11:27:38, 21 December 2024)
- 05000327/LER-1981-098, Forwards LER 81-098/03L-0 + (11:27:39, 21 December 2024)
- 05000311/LER-1981-079-03, /03L-0:on 810803,constant Speed Drive Breaker 22 Tripped.Cause Undetermined.Constant Speed Drive Breaker 21 Manually Closed.Cause Under Investigation + (11:27:41, 21 December 2024)
- ML20010E677 + (11:27:42, 21 December 2024)