Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19309G437 + (07:31:30, 2 January 2025)
- 05000317/LER-1980-013-03, During Surveillance Test, Channel D Containment High Pressure Setpoint Less Conservative than Tech Specs.Caused by Failed Signal Isolator 1-E/E-5313D.Instrument Returned for Repair + (07:31:32, 2 January 2025)
- ML19309G434 + (07:31:33, 2 January 2025)
- 05000317/LER-1980-013, Forwards Updated LER 80-013/03X-1 + (07:31:35, 2 January 2025)
- ML19309G431 + (07:31:36, 2 January 2025)
- 05000295/LER-1980-017-03, /03L-0:on 800402,during Load Test on Diesel Generator O to Facilitate Taking Diesel Generator 1A Out of Svc,Diesel Generator O Tripped from Full Load,Placing Auxiliary Power Sys in Degraded Condition + (07:31:37, 2 January 2025)
- ML19309G429 + (07:31:39, 2 January 2025)
- ML19309G428 + (07:31:40, 2 January 2025)
- 05000295/LER-1980-017, Forwards LER 80-017/03L-0 + (07:31:41, 2 January 2025)
- ML19309G423 + (07:31:43, 2 January 2025)
- 05000317/LER-1980-018-03, /03L-0:on 800401,Number 11 Control Room Air Conditioning Unit Taken Out of Operation for Maint.Caused by Need to Calibr Outside Air Temp Transmitter 0-TT-5350. Transmitter Calibr & Placed Back in Svc + (07:31:45, 2 January 2025)
- ML19309G421 + (07:31:46, 2 January 2025)
- 05000317/LER-1980-018, Forwards LER 80-018/03L-0 + (07:31:47, 2 January 2025)
- ML19309G416 + (07:31:49, 2 January 2025)
- ML19309G418 + (07:31:49, 2 January 2025)
- ML19309G415 + (07:31:50, 2 January 2025)
- ML19309G414 + (07:31:51, 2 January 2025)
- 05000293/LER-1980-015-03, /03L-0:on 800401,during Performance of Surveillance Test,Dry Chemical Fire Protection Sys Failed to Automatically Initiate.Caused by Erratic Pyrotronics, Dtf 190 heat-actuated Device.Unit Replaced + (07:31:52, 2 January 2025)
- 05000266/LER-1980-004-03, /03L-0:on 800409,w/plant at Normal Steady State, Emergency Diesel Generator Failed to Start During Routine Surveillance Test.Second Attempt Unsuccessful.Caused by Broken Vane in Starting Air Motor.Air Motor Replaced + (07:31:54, 2 January 2025)
- ML19309G411 + (07:31:56, 2 January 2025)
- 05000293/LER-1980-015, Forwards LER 80-015/03L-0 + (07:31:57, 2 January 2025)
- ML19309G408 + (07:31:59, 2 January 2025)
- 05000282/LER-1980-012-03, /03L-0:on 800331,during Review of Electrical Surveillance Program,Discovered That Individual Float Cell Voltage Measurements Were Not Done in Mar 1980 on Battery Monthly Test.Caused by Personnel Oversight + (07:32:00, 2 January 2025)
- ML19309G404 + (07:32:02, 2 January 2025)
- 05000282/LER-1980-012, Forwards LER 80-012/03L-0 + (07:32:03, 2 January 2025)
- ML19309G400 + (07:32:04, 2 January 2025)
- 05000266/LER-1980-004, Forwards LER 80-004/03L-0 + (07:32:06, 2 January 2025)
- 05000312/LER-1980-022-03, /03L-0:on 800406,refueling Test Revealed Valve Sfv 53603 Returned to Open Position After Signal Reset.Caused by Sticking Blpb Open Contacts.Blpb Replaced & Valve Successfully Tested + (07:32:08, 2 January 2025)
- ML19309G396 + (07:32:09, 2 January 2025)
- ML19309G395 + (07:32:09, 2 January 2025)
- 05000313/LER-1980-012-03, /03L:on 800406,while Performing Monthly Inservice Valve Stroke Test,Emergency Feedwater Supply valves,CV2667 & CV2617,failed to Fully Open.Caused by Binding Due to Loose Bolts Securing Actuator + (07:32:10, 2 January 2025)
- 05000312/LER-1980-022, Forwards LER 80-022/03L-0 + (07:32:14, 2 January 2025)
- ML19309G389 + (07:32:15, 2 January 2025)
- ML19309G390 + (07:32:15, 2 January 2025)
- 05000346/LER-1980-030-01, /01T-0:on 800418,contrary to Tech Spec 3.4.1,decay Heat Pump 1-2 Stopped When RCS Water Level Decreased to 37 Inches Above Hot Leg Piping Centerline.Caused by Valve Operator Component Failure.Work Order Issued for Adjustment + (07:32:17, 2 January 2025)
- ML19309G387 + (07:32:19, 2 January 2025)
- 05000334/LER-1980-020-03, /03L-0:on 800329,during Operations to Increase Level in RCS Loops,Vol Control Tank Outlet MOV-CH-115C Found Closed.Vol Control Tank Level Indicated Normally.Caused by Bad Fuse Holder for Level Bistable.Fuse Holder Replaced + (07:32:21, 2 January 2025)
- 05000155/LER-1980-008-03, /03L-0:on 800411,following Intermittent Automatic Test Circuit Alarms,Sensor Channel D of Reactor Depressurizing Sys Was Removed from Svc to Correct Problem. Caused by Drift.Unit Was Readjusted + (07:32:23, 2 January 2025)
- 05000346/LER-1980-030, Forwards LER 80-030/01T-0 + (07:32:25, 2 January 2025)
- 05000334/LER-1980-020, Forwards LER 80-020/03L-0 + (07:32:28, 2 January 2025)
- 05000155/LER-1980-006-03, /03L-0:on 800403,following Intermittent Automatic Test Circuit Alarms,Sensor Channel D of Reactor Depressurizing Sys Was Removed from Svc to Correct Problem. Caused by Setpoint Drift.Unit Was Readjusted + (07:32:30, 2 January 2025)
- 05000409/LER-1980-003-01, /01T-0:on 800417,during Type C Leakage Testing, Containment Isolation Did Not Meet Test Criteria.Seal Rings Which Exhibited Aging Due to Normal Wear replaced.Post-maint Leakage Rate Test on 800425 Exhibited Zero Leakage + (07:32:32, 2 January 2025)
- 05000313/LER-1980-012, Forwards LER 80-012/03L-0 + (07:32:34, 2 January 2025)
- ML19309G375 + (07:32:36, 2 January 2025)
- 05000313/LER-1980-009-03, /03L-0:on 800328,while Performing Surveillance Test,Lead Hydrogen Purge Supply fan,VSF-30A Tripped on Overload.Caused by Check Valve HPA-5 Being Stuck,Due to Corrosion from Seal Water Leaking Onto Valve + (07:32:38, 2 January 2025)
- 05000348/LER-1980-025-03, /03L-0:on 800331,0407 & 22,diesel Generator 1C Started & Reached Rated Speeds in Excess of Tech Spec Requirement.Lube Oil Sump Temp Below 120-130 F Range Was Only Abnormal Condition Found.Cause Under Investigation + (07:32:40, 2 January 2025)
- ML19309G372 + (07:32:41, 2 January 2025)
- 05000313/LER-1980-009, Forwards LER 80-009/03L-0 + (07:32:43, 2 January 2025)
- 05000409/LER-1980-002-01, /01T-0:on 800415,during Type C Leakage Testing, Containment Isolation Did Not Meet Test Criteria.Seat Ring on Upstream Containment Ventilation Isolation Exhaust Damper 73-25-005 Replaced & Leakage Rate Retested + (07:32:45, 2 January 2025)
- 05000313/LER-1980-011-03, /03L-0:on 800401,based on Sys Review Per IE Bulletin 79-14,certain Hangers Declared Inoperable.Cause Not Stated.Hangers Repaired or Modified within Required Time Limit on Affected Svc Water & Main Steam Sys + (07:32:47, 2 January 2025)
- ML19309G366 + (07:32:50, 2 January 2025)