- 05000254/LER-1985-010-08, :on 850728,RCIC Declared Inoperable After RCIC Bn Turbine Overspeed & Turbine Trip Alarms Received.Caused by Failed RCIC Overspeed Meter Relay Light Bulb.Light Bulb Replaced + (ML20134M243)
- ML20134M245 + (ML20134M245)
- ML20134M246 + (ML20134M246)
- ML20134M247 + (ML20134M247)
- IR 05000456/1996015 + (ML20134M248)
- 05000265/LER-1985-016-04, :on 850729,fuel Pool Radiation Monitor 2A (Il) Indicated Sudden Upscale Reading Past Trip Limits.Caused by Instrument Setpoint Drift.Setpoint Corrected + (ML20134M249)
- 05000414/LER-1997-002, :on 970107,new Incore Fission Detector Was Installed in Unit 2 Reactor & 43 Days Had Elapsed Since Last Survey.Caused by Inadequate Procedural Guidance.Procedure Revised + (ML20134M250)
- 05000331/LER-1985-024, :on 850707,two Reactor Protection Sys Trips Occurred.Caused by Unattached Trip Coil Inside Damping Spring on Feeder Breaker 1B42.Breaker Manufacturer Will Be Notified + (ML20134M251)
- ML20134M253 + (ML20134M253)
- PNO-IV-85-044A, on 850827,accident Occurred Between Train & Truck Transporting Dry Natural U Concentrates from Saskatchewan Enroute to Gore,Ok.Contaminated Matls & Recovered U Concentrate Will Be Shipped Back to Canada + (ML20134M254)
- ML20134M255 + (ML20134M255)
- ML20134M256 + (ML20134M256)
- 05000317/LER-1985-009, :on 850806,reactor Tripped on Low Steam Generator Water Level Due to Insufficient Feed Pump Speed. Caused by Personnel Error.Evaluation Will Be Performed Frequently on Plant Simulator + (ML20134M257)
- 05000331/LER-1985-030, :on 850731,two Secondary Containment Airlock Doors Simultaneously Opened.Caused by out-of-adjustment Door Interlock Mechanism.Defective Mechanism Repaired + (ML20134M258)
- RC-97-0033, Monthly Operating Rept for Jan 1997 for Virgil C Summer Nuclear Station + (ML20134M259)
- ML20134M260 + (ML20134M260)
- B16194, Responds to NRC Staff Request for Addl Info Re Potential Inconsistency Between UFSAR & TS + (ML20134M261)
- IR 05000285/1985011 + (ML20134M262)
- ML20134M263 + (ML20134M263)
- B16256, Forwards Millstone Nuclear Power Station,Unit 2 Independent Corrective Action Verification Program + (ML20134M264)
- ML20134M265 + (ML20134M265)
- ML20134M266 + (ML20134M266)
- ML20134M267 + (ML20134M267)
- ML20134M268 + (ML20134M268)
- ML20134M269 + (ML20134M269)
- 05000443/LER-1997-001, :on 970109,identified That Certain Obstructions to Flow of Flood Water Off Site May Produce Flood Levels Exceeding Elevations Specified in Fsar.Caused by Misapplication of Design Inputs + (ML20134M270)
- ML20134M271 + (ML20134M271)
- ML20134M273 + (ML20134M273)
- BSEP-85-1456, Responds to Violations Noted in Insp Repts 50-324/85-17 & 50-325/85-17.Corrective Actions:Rev 1 to E&RC-0535 Completed on 850812 Re Insp of High Integrity Containers (HIC) & HIC Purchased for Filter Disposal + (ML20134M274)
- ML20134M275 + (ML20134M275)
- NRC-96-0102, Monthly Operating Rept for Oct 1996 for Fermi 2 + (ML20134M276)
- ML20134M278 + (ML20134M278)
- ML20134M280 + (ML20134M280)
- ML20134M281 + (ML20134M281)
- ML20134M282 + (ML20134M282)
- ML20134M283 + (ML20134M283)
- ML20134M284 + (ML20134M284)
- 05000445/LER-1993-010, Forwards LER 93-010-00 Re Hot Particle Contamination Resulting in Exposure Exceeding 10CFR20 Skin Dose Limits + (ML20134M285)
- ML20134M287 + (ML20134M287)
- ML20134M288 + (ML20134M288)
- ML20134M289 + (ML20134M289)
- ML20134M290 + (ML20134M290)
- 05000445/LER-1993-010-02, :on 931120,hot Particle Contamination Resulted in Exposure Exceeding 10CFR20 Skin Dose Limits.Specific Causes Could Not Be Determined.Hot Particle Personnel Frequency Increased.Attachment 1 Partially Deleted + (ML20134M291)
- ML20134M292 + (ML20134M292)
- ST-HL-AE-1340, Ack Receipt of 850806 Request for Addl Info Re Questions 200.02-210.07.Responses Will Be Provided by 850930.Questions Renumbered to Be Consistent W/Existing FSAR Questions + (ML20134M293)
- ML20134M294 + (ML20134M294)
- PY-CEI-NRR-0322, Revises 820312 Response to Question Topic 15 Re Control Room Carpeting.Correction of Section 9.5.1.6.2 to SER Requested.Info Will Be Incorporated Into Future Amend to FSAR + (ML20134M295)
- ML20134M296 + (ML20134M296)