- 05000249/LER-1976-031, :on 761101,during Refueling Outage Local Leak Rate Testing,Isolation Check Valve 3-205-2-7 Exhibited Leak Rate Above Tech Spec Limit.Caused by Dirt in Seating Area & on Disc Pivot Pin + (ML20084P495)
- 05000254/LER-1976-022-03, /03L-0:on 760723,operability Testing on Containment Cooling Loop Performed on Wrong Unit.Caused by Personnel Error + (ML20084P496)
- ML20084P502 + (ML20084P502)
- 05000249/LER-1976-029, :on 761028,during Refueling Outage Surveillance Testing,Control Rod Drive Return Line Primary Isolation Check Valve 3-0301-98 Exceeded Tech Spec Leak Rate Limit. Caused by Normal Wear of Seating Area + (ML20084P507)
- ML20084P509 + (ML20084P509)
- 05000254/LER-1976-021-03, /03L-1:on 760709 Two Control Rods Withdrawn Simultaneously.Caused by Personnel Error.Procedure Rev Implemented to Further Clarify Control Rod Drive Maint Requirements + (ML20084P512)
- 05000249/LER-1976-028, :on 761018,after Preliminary Testing & Subsequent Insp by vendor,250 Volt Battery Found in Degraded Condition. Caused by Prior Battery Charger Problems.Battery Replaced W/Larger Capacity Unit + (ML20084P515)
- B11166, Forwards Status of Info Requested by Power Sys Branch Mechanical Series Questions on 840116.Revised Responses & Corresponding marked-up FSAR Pages Also Encl + (ML20084P517)
- ML20084P526 + (ML20084P526)
- ML20084P532 + (ML20084P532)
- ML20084P534 + (ML20084P534)
- ML20084P535 + (ML20084P535)
- 05000249/LER-1976-027, :on 761009,during Routine Surveillance Testing,Six Component Cooling Svc Water Pump Vault Penetrations Exhibited Detectable Leakage When Pressurized.Caused by Operational Vibration.Penetrations Resealed + (ML20084P538)
- ML20084P546 + (ML20084P546)
- 05000249/LER-1976-026, :on 761012,during Valve Operability Testing of Drywell Spray Sys,Motor Operated Valve 3-1501-27A Failed to Open.Caused by Loose Terminal in Valve Control Circuitry. Terminals Tightened + (ML20084P548)
- ML20084P551 + (ML20084P551)
- ML20084P557 + (ML20084P557)
- ML20084P563 + (ML20084P563)
- ML20084P569 + (ML20084P569)
- 05000327/LER-1984-025, :on 840415,sampling of RCS for Boron Concentration Caused Pressurizer Level Transmitter 1-LT-68-320 to Become Inoperable Due to Mod Made During Last Outage Routing Sense Line from Low Side Top + (ML20084P573)
- 05000249/LER-1976-025, :on 761007,during Refueling Outage Local Leak Rate Testing,Feedwater Check Valves 3-820-58B & 62B Exhibited Leakage Rates Above Tech Spec Limit.Caused by Dirt in Seating Area.Valve Cleaned & Retested + (ML20084P579)
- ML20084P584 + (ML20084P584)
- ML20084P592 + (ML20084P592)
- ML20084P594 + (ML20084P594)
- ML20084P597 + (ML20084P597)
- 05000249/LER-1976-024, Following Refueling Outage Surveillance Testing of Diesel Generator,Engine Speed Could Not Be Adjusted from Control Room.Caused by Loose Wire on Diesel Governor Control Circuit + (ML20084P598)
- ML20084P599 + (ML20084P599)
- 05000249/LER-1976-024-01, :on 761009,following Refueling Outage Surveillance Test of Diesel Generator,Engine Speed Could Not Be Regulated from Control Room.Caused by Loose Wire on Diesel Governor Control Circuit.Wire Tightened + (ML20084P613)
- 05000249/LER-1976-023, :on 761007,during Refueling Outage Local Leak Rate Testing,Lpci Primary Isolation Check Valve 3-1501-25B Exhibited Leak Rate Above Tech Spec Limit.Caused by Dirt & Scratches on Valve Seat.Valve Cleaned + (ML20084P617)
- 05000254/LER-1976-020-03, /03L-0:on 760701,loss of Indication & Operability Occurred on Containment Spray Loop B Outboard Valve MO-1-1101-23B.Caused by Loose hold-down Bolts.Bolts tightened.W/760729 Forwarding Ltr + (ML20084P619)
- ML20084P626 + (ML20084P626)
- ML20084P627 + (ML20084P627)
- 05000249/LER-1976-022, :on 760929,during Prerequisite Testing for Refueling Outage LPCI Logic Surveillance,Dpis 261-34A Failed to Trip.Caused by Roller Cam Being Jammed by Microswitch Actuating Arm.Switch Repaired + (ML20084P630)
- 05000249/LER-1976-021, :on 760924,during Routine Insp of Drywell Snubbers,Snubbers 24 & 30 Appeared to Be Inoperable Due to Loss of Fluid.Caused by Leakage Through Grease Fittings. Grease Fittings Replaced + (ML20084P633)
- ML20084P635 + (ML20084P635)
- 05000249/LER-1976-020, :on 760922,during Refueling Outage Local Leak Rate Testing,Vol Bounded by Main Steam Line Drain Valves 3-220-1 & 2 Exhibited Leak Above Tech Specs Limit.Probably Caused by Deteriorated Pressure Seal Ring + (ML20084P642)
- ML20084P648 + (ML20084P648)
- ML20084P651 + (ML20084P651)
- 05000249/LER-1976-020-01, Vol Bounded by Steam Line Drain Valves 3-220-1 & 2 Exhibited Leakage Above Tech Spec Limits.Caused by Deteriorated body-to-bonnet Pressure Seal Ring & Dirt in Seating Area + (ML20084P653)
- ML20084P654 + (ML20084P654)
- ML20084P657 + (ML20084P657)
- ML20084P661 + (ML20084P661)
- ML20084P664 + (ML20084P664)
- ML20084P667 + (ML20084P667)
- ML20084P671 + (ML20084P671)
- 05000249/LER-1976-019, :on 760921,diesel Generator Not Shutdown Following Return to Svc of Bus 34-1 & Engine High Temp Alarm Received. Caused by Partially Clogged Strainer in Lube Oil Circulating Pump.Strainer Cleaned + (ML20084P672)
- ML20084P674 + (ML20084P674)
- ML20084P676 + (ML20084P676)
- 05000249/LER-1976-018, :on 760921,during Refueling Outage Local Leak Rate Testing,Feedwater Check Valves 3-220-58A & 62A Exhibited Leak Rates Above Tech Spec Limit.Caused by Dirt in Seating Area & Worn Disc Assembly Pins + (ML20084P677)
- ML20084P681 + (ML20084P681)
- ML20084P686 + (ML20084P686)