Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000272/LER-1982-093, Forwards LER 82-093/03L-0.Detailed Event Analysis Encl + (ML20083M493)
- ML20083M495 + (ML20083M495)
- 05000317/LER-1982-078, Forwards LER 82-078/03L-0 + (ML20083M497)
- 05000271/LER-1983-001-01, /01T-0:on 830107,containment Isolation Valves Failed to Close When Operator Attempted to Secure Nitrogen Flow.Caused by Accumulation of Ferrous Metal Particles on Magnet Providing Valve Position Indication.Valves Cleaned + (ML20083M501)
- ST-HL-AE-1080, Forwards Final Rept Re Control Room Design Review,Addressing NRC Audit Comments + (ML20083M502)
- 05000272/LER-1982-093-03, /03L-0:on 821225,plant Vent Gross Activity Monitor Indication Declared Inoperable.Daily Grab Samples of Plant Vent Effluent Not Taken Until 830104 Violating Ets. Caused by Personnel Error.Procedures Reviewed + (ML20083M509)
- ML20083M510 + (ML20083M510)
- ML20083M512 + (ML20083M512)
- ML20083M517 + (ML20083M517)
- ML20083M518 + (ML20083M518)
- 05000339/LER-1983-004, Forwards LER 83-004/03L-0 + (ML20083M520)
- ML20083M524 + (ML20083M524)
- 05000397/LER-1984-022, :on 840319,electrician Inadvertently Bumped Clapper of Auxiliary Undervoltage Relay,Which Tripped Supply Breaker to Div 3 ESF Bus.Caused by Human Error. Personnel Advised of Precautions + (ML20083M525)
- 05000339/LER-1983-004-03, /03L-0:on 830105,casing Cooling Pump B Removed from Svc.Caused by Need to Repair Small Leak in Discharge Flange of Pump.Repair Made & Pump Returned to Svc + (ML20083M526)
- ML20083M528 + (ML20083M528)
- ML20083M533 + (ML20083M533)
- 05000302/LER-1982-076, Forwards LER 82-076/03L-0 + (ML20083M536)
- ML20083M537 + (ML20083M537)
- ML20083M539 + (ML20083M539)
- 05000397/LER-1984-017, :on 840318,Div II Control Room Emergency Fan Initiated.Caused by Personnel Error.Procedure Revised & Subsequent Surveillances Ran Successfully W/No Inadvertent Actuations + (ML20083M540)
- ML20083M547 + (ML20083M547)
- 05000302/LER-1982-076-03, /03L-0:on 821220,feedwater Ultrasonic Flow Indicator FW-313-FI & Emergency Feedwater Train B Discovered Inoperable.Caused by Excessive Heat in Emergency Feedwater Line.Line Cooled.Indicators Will Be Replaced + (ML20083M548)
- ML20083M551 + (ML20083M551)
- 05000325/LER-1982-152, Forwards LER 82-152/03L-0 + (ML20083M552)
- ML20083M554 + (ML20083M554)
- ML20083M558 + (ML20083M558)
- B11087, Forwards Thermal Shield Damage Recovery Program,Final Rept, App A:Effects of Core Barrel Bypass Flow on Fuel Assemblies Testing & Analyses, Per + (ML20083M561)
- 05000325/LER-1982-152-03, /03L-0:on 821221,visual Insp of Main Steam Line Secondary Containment Boot Seals Revealed Hole in Boot Seal of Main Steam Line A.Caused by Thermal Expansion & High Ambient Temps.Boot Replaced + (ML20083M562)
- ULNRC-03211, Submits Special Rept 95-01 Re Number of Tubes Plugged During Eighth SG Tube ISI + (ML20083M563)
- ML20083M565 + (ML20083M565)
- RBG-41427, Emphasizes Changes Taken Place as Result of Shift in Mgt Philosophy Between pre-merger Gsu Mgt & post-merger Entergy Operations,Inc Mgt.Response to NRC Re Lessons Learned from Jul 1992 QA Audit of Security Program Encl + (ML20083M566)
- ML20083M568 + (ML20083M568)
- 05000416/LER-1982-181, Forwards LER 82-181/03L-0 + (ML20083M569)
- ML20083M573 + (ML20083M573)
- 05000416/LER-1982-181-03, /03L-0:on 821228,two Fire Rated Doors in Control Bldg Blocked Open to Perform Control Room Pressure Test. Continuous Fire Watch Established.Doors Closed & Fire Watch Disbanded Upon Test Completion + (ML20083M579)
- ML20083M584 + (ML20083M584)
- 05000296/LER-1982-067, Forwards LER 82-067/03L-0 + (ML20083M586)
- ML20083M587 + (ML20083M587)
- 05000296/LER-1982-067-03, /03L-0:on 821225,coupling Unit on Diesel Generator C Lube Oil Pump Found Broken.Caused by Deterioration of Coupling Spider Due to Normal Svc.Pump Mfg by Viking & Coupling by Lovejoy.Coupling Replaced + (ML20083M590)
- ML20083M595 + (ML20083M595)
- 05000335/LER-1982-070, Forwards LER 82-070/03L-0 + (ML20083M596)
- ML20083M597 + (ML20083M597)
- 05000335/LER-1982-070-03, /03L-0:on 821229,during Routine Testing,Emergency Safety Features Actuation & Reactor Protection Sys Channel B Input for Containment Pressure Failed.Caused by Failed 45-volt Power Supply.Power Supply Replaced + (ML20083M600)
- ML20083M601 + (ML20083M601)
- ML20083M604 + (ML20083M604)
- PLA-1492, Ro:On 821211,channels to Loose Parts Monitoring Sys Determined Inoperable Due to Erroneous Data.Caused by Incorrect Low Level Alarm Settings.Alarm Levels Reset + (ML20083M606)
- 05000397/LER-1984-025, :on 840319,control Room Air Radiation Monitors WOA-RIS-31A,31B,32A & 32B Tripped Associated High Radiation Alarms & Started Control Room Emergency Filtration Units. Caused by Electrical Noise + (ML20083M608)
- ML20083M610 + (ML20083M610)
- 05000373/LER-1982-179, Forwards LER 82-179/03L-0 + (ML20083M612)
- 05000373/LER-1982-179-03, /03L-0:on 821224,lake Blowdown Flow Recorder Indicated Incorrect Readings.Caused by Lake Blowdown Flow Instrument Probe Being air-bound Preventing Correct Signal from Being Transmitted.Mod Issued to Modify Sys + (ML20083M616)
- ML20083M617 + (ML20083M617)