- ML20082N969 + (ML20082N969)
- ML20082N974 + (ML20082N974)
- ML20082N977 + (ML20082N977)
- 05000416/LER-1983-172-03, /03L-0:on 831026,MSIVs B21-F067A & B21-F016 Failed to Meet Max Allowable Closing Times.Caused by Swelled Packing on Valves at near-rated Temp & Pressure.Packing Adjusted + (ML20082N978)
- ML20082N988 + (ML20082N988)
- ST-HL-AE-1028, Forwards Addl Info Re Isolation Valve Cubicle Roof Design, Per NRC Request.Addl Info Provided for Certain Questions Re 830913 Submittal + (ML20082N990)
- ML20082N996 + (ML20082N996)
- ML20082N999 + (ML20082N999)
- ML20082P000 + (ML20082P000)
- RBG-16-421, Forwards Responses to Draft SER Open Items Identified by Radiological Assessment Branch.Responses Will Be Provided in Future Amend to FSAR + (ML20082P006)
- 05000327/LER-1983-156-03, /03L-0:on 831101,upper Head Injection Level Switch 1-LS-87-23 Declared Inoperable,Due to Failure to Meet Surveillance Requirement.Caused by Loose Setpoint Lockdown Screw.Screw Retightened & Switch Recalibr + (ML20082P009)
- 05000260/LER-1983-070-03, /03L-0:on 831103,downstream HEPA MSA Ask 1743-1217 Filters in Standby Gas Treatment Train C Measured 98% DOP Removal.Caused by Degradation & Wear of Filters Through Normal Use.Filters Replaced + (ML20082P010)
- ML20082P016 + (ML20082P016)
- ML20082P027 + (ML20082P027)
- 05000328/LER-1983-157-03, /03L-0:on 831102,during RCS Flow Loop Temp Channel Response Time Review,Protection Channel I (2-TE-68-2A & 14A) Check for Delta T/Tavg Not Performed within Required Time. Caused by Inadequate Procedure + (ML20082P030)
- ML20082P033 + (ML20082P033)
- ML20082P038 + (ML20082P038)
- ML20082P043 + (ML20082P043)
- 05000416/LER-1983-173-03, /03L-0:on 831031,reactor Water Cleanup Differential Flow Channels a & B Read 30 & 3 Gpm, Respectively.Channel a Declared Inoperable.Caused by Failed Card in Instrument Square Root Extractor + (ML20082P046)
- 05000327/LER-1983-155-03, /03L-0:on 831104,loop 4 Feedwater Flow Transmitter 1-FT-103A Became Inoperable When Line Pulled Loose from Connection Upstream of Isolation Valve.Caused by Incorrectly Installed Fitting.Connection Repaired + (ML20082P053)
- ML20082P055 + (ML20082P055)
- ML20082P062 + (ML20082P062)
- RBG-16-413, Forwards Response to Draft SER Open Item Re Reactor Vessel Matls Surveillance Program.Response Will Be Incorporated Into Future FSAR Amend + (ML20082P065)
- 05000327/LER-1983-152-03, /03L-0:on 831028,containment Isolation Valve 1-FCV-77-20 in Reactor Coolant Drain Tank Nitrogen Supply Line Found Inoperable.Valve Isolated.Caused by Bad Cable. Cable Will Be Replaced + (ML20082P066)
- ML20082P067 + (ML20082P067)
- 05000328/LER-1983-161-03, /03L-0:on 831102,w/unit in Mode 2 at Zero Power, Rod Bottom Light for Control Rod H-10 Did Not Come on at Shutdown.Light Declared Inoperable.Caused by Failed Resistor in Module.Module Replaced + (ML20082P069)
- 05000260/LER-1983-065-03, /03L-0:on 831013,reactor Protective Sys Channel a Manually Tripped W/O Performing Functional Test on Scram Discharge Instrument Vol Channel B.Caused by Personnel Oversight.Tech Spec Criteria Stressed + (ML20082P070)
- ML20082P076 + (ML20082P076)
- BSEP-83-3848, Ro:On 831111,conservative Determination Made That Drywell Equipment Drain Line,Floor Drain & Svc Air Header Not Adequately Supported.Investigation Incomplete.Rept Expected by 831209 + (ML20082P079)
- ML20082P085 + (ML20082P085)
- 05000328/LER-1983-160-03, /03L-0:on 831102,turbine-driven Auxiliary Feedwater Pump Failed Criteria SI-166.32 by Not Obtaining 880 Gpm Min Flow Rate.Caused by High Reading Due to Air in Instrument Sense Line.Lines Vented + (ML20082P087)
- ML20082P088 + (ML20082P088)
- RBG-16-438, Forwards Responses to Draft SER & Changes to FSAR Re Safe Shutdown Sys & Fire Hazards Analysis,Reflecting Resolution of Each Open Item.Changes Will Be Incorporated Into Next FSAR Amend + (ML20082P089)
- 05000338/LER-1983-076-03, /03L-0:on 831101,individual Rod Position Indication for Channel N-09 Deviated from Group Demand Position by Greater than 12 Steps.Caused by Instrument Drift.Channel Recalibr + (ML20082P095)
- 05000425/LER-1991-009-02, :on 910813,safety Injection Pump Start Occurred During Surveillance Testing.Caused by Intermittent Failure of Reset.Shift Briefings Held Informing Control Room Personnel of Switch Malfunction + (ML20082P097)
- 05000333/LER-1995-007, :on 950313,reactor Coolant Temp Raised Above 212 Degrees W/Less than Min Number of Required Operable Crev Air Supply Fans.Caused by Inoperability of Fan Motor.Fan Repaired + (ML20082P100)
- 05000302/LER-1995-005, :on 950322,engineering Performed Net Positive Suction Head Evaluation for Unique ECCS Configuration. Condition Caused by Insufficient Review During EOP Change Process.Affected Procedures Annotated + (ML20082P114)
- 05000339/LER-1983-073-03, /03L-0:on 831107 & 14,w/unit in Mode 1 at 100% Power,Inner Personnel Hatch Door Found to Have Unacceptable Leak Rate,Contrary to Tech Spec 3.6.1.3.Caused by Dirty Door Seals Due to Multiple Containment Entries + (ML20082P116)
- 05000389/LER-1983-069-03, /03L-0:on 831027,while Performing Periodic Control Element Assembly (CEA) Exercise,Cea 86 Dropped to Full Insertion.Caused by Control Element Drive Mechanism Failure to Close Upper Gripper + (ML20082P117)
- 05000260/LER-1983-071-03, /03L-0:on 831104,while Performing Surveillance Insp 4.2.B-7,2-PS-3-74A Pressure Switch 1 Had as-found Setpoint of 214.43 Psig.Caused by Calibr Drift.Barksdale B 2T-M12SS Switch Recalibr + (ML20082P124)
- 05000416/LER-1983-174-03, /03L-0:on 831026,during Div II Diesel Generator Monthly Surveillance,Fuel Oil Leak Discovered on Cylinder Injector Return Line 81B.Caused by Unknown Bump by Tool or Personnel.Line Replaced + (ML20082P125)
- 05000259/LER-1983-063-03, /03L-0:on 831102,flow Distribution Through Standby Gas Treatment Train B Failed Acceptance Criteria.Caused by Accumulation of Sand in Moisture Separator.Moisture Separator Repaired + (ML20082P127)
- 05000339/LER-1983-075-03, /03L-0:on 831112,solid State Protection Sys Train a Stop Valve Generator Trip Logic Failed to Meet Acceptance Criteria.Caused by Faulty Universal Card.Card Replaced & Logic Channel Returned to Svc After Calibr + (ML20082P129)
- ML20082P133 + (ML20082P133)
- ST-HL-AE-3848, Responds to NRC Inspector Follow-up Item 498/9104-01 Re Inservice Insp Program for Steam Generator Tubes + (ML20082P139)
- 05000338/LER-1983-074-03, /03L-0:on 831106,steam Generator C Channel I Level Indication Drifted High Out of Specified Tolerance.Caused by body-to-bonnet Leakage of Ref Leg Root Valve.Valve Leak Stopped + (ML20082P143)
- ML20082P146 + (ML20082P146)
- BSEP-83-3720, Ro:On 831020,while Performing Visual Insp of Fire Barrier Penetration Seals on Diesel Generator Bldg,Discovered Several Fire Barrier Penetrations Did Not Meet Test Acceptance Criteria.Caused by Cracked Insulating Cement + (ML20082P150)
- ML20082P153 + (ML20082P153)
- AECM-83-0767, RO 83-105/0:on 831031-1106,fluctuating Temps in Auxiliary Bldg Steam Tunnel Exceeded Tech Spec Limit of 125 F for More than 8 H.Steam Tunnel Cooler Coils Replaced to Resolve Temp Problems + (ML20082P154)
- 05000296/LER-1983-026, Supplemental LER 83-026/03X-4:on 830411,while Attempting to Establish EECW Flow Rate to Emergency Diesel Generator 3 Coolers,Head on HX Found Cracked.Caused by Mfg Defect.Cast Iron Head Replaced + (ML20082P157)