- 05000416/LER-1983-027, Forwards LER 83-027/99X-0 + (ML20071B958)
- ML20071B960 + (ML20071B960)
- A02905, Provides Results of Ongoing Study of Merits of Not Tripping Diesel Generators Upon Restoration of 125-volt Dc Electrical Power,Per Agreement Reached on IE Insp Rept 50-336/82-33. Listed Mods to Be Incorporated by End of 1983 + (ML20071B961)
- 05000416/LER-1983-027-99, /99X-0:on 830128,fire Door 1A215 Alarmed on Supervision Sys & Would Not Reset,Yet Verified Closed.Caused by Door Position Switch Out of Adjustment.Fire Watch Established.Switch Adjusted.Door Returned to Svc on 830201 + (ML20071B963)
- ML20071B965 + (ML20071B965)
- 05000244/LER-1983-005, Forwards LER 83-005/03L-0 + (ML20071B969)
- ML20071B974 + (ML20071B974)
- 05000244/LER-1983-005-03, /03L-0:on 830117,I-131 Spike Occurred in RCS After Unit Tripped from 100% Power.Caused Not stated.I-131 Concentration Returned to Normal Levels by Normal Letdown + (ML20071B975)
- 05000325/LER-1983-005, Forwards LER 83-005/03L-0 + (ML20071B976)
- 05000325/LER-1983-005-03, /03L-0:on 830119,during Normal Operation,Measured Specific Gravity of Pilot Cell for Div I Battery 1A-1 Was 1.166 & 1.167 for Div II Battery 1B-1.Caused by Age of Pilot Cells.Cells Replaced.Batteries Returned to Svc + (ML20071B979)
- 05000325/LER-1983-010, Forwards LER 83-010/03L-0 + (ML20071B981)
- 05000325/LER-1983-010-03, /03L-0:on 830120,routine Surveillance Revealed Water Leaking Into Reactor Bldg at 17-ft Elevation Via Secondary Containment Penetration/Fire Barrier Seal R1-1-049.Caused by Degradation Due to Exposure to Rainwater + (ML20071B986)
- 05000318/LER-1983-006, Forwards LER 83-006/03L-0 + (ML20071B989)
- ML20071B991 + (ML20071B991)
- 05000318/LER-1983-006-03, /03L-0:on 830123,auxiliary Feedwater Actuating Sys Channel Zd for Steam Generator 21 Level Indicated Low.Caused by Failure of Level Transmitter 2-LT-1114A Due to Defective Zero Adjustment Potentiometer.Transmitter Replaced + (ML20071B993)
- 05000324/LER-1983-010, Forwards LER 83-010/03L-0 + (ML20071B994)
- ML20071B998 + (ML20071B998)
- 05000324/LER-1983-010-03, /03L-0:on 830119,during Plant Operation,Both Doors of Reactor Bldg 20-ft Elevation Personnel Air Lock Opened Simultaneously.Caused by Misalignment of Inner Door Due to Normal Wear Preventing Proper Bolt Engagement + (ML20071B999)
- ML20071C003 + (ML20071C003)
- ML20071C007 + (ML20071C007)
- ML20071C008 + (ML20071C008)
- ML20071C009 + (ML20071C009)
- ML20071C010 + (ML20071C010)
- 0CAN028301, Application for Amend to Licenses DPR-51 & NPF-6,revising Tech Specs to Change in-core Detector Surveillance Requirements & to Correct Various Typographical,Title & Ref Errors + (ML20071C017)
- ML20071C020 + (ML20071C020)
- 1CAN028305, Discusses Understanding Re 821210 Order for Mod to OL Concerning Inadequate Core Cooling,Per 830127 Meeting W/Nrc. Util 830117 Request for Extension of Deadline for Hearing Requests Will Be Withdrawn.Nrc Confirmation Requested + (ML20071C021)
- ML20071C024 + (ML20071C024)
- ML20071C025 + (ML20071C025)
- ML20071C031 + (ML20071C031)
- ML20071C034 + (ML20071C034)
- ML20071C035 + (ML20071C035)
- ML20071C039 + (ML20071C039)
- 05000338/LER-1983-004, Forwards LER 83-004/03L-0 + (ML20071C042)
- ML20071C048 + (ML20071C048)
- 05000338/LER-1983-004-03, /03L-0:on 830125,svc Water Supply Valves MOV-SW- 103B & C & Discharge Valve MOV-SW-104C to Recirculation Spray HXs Would Not Open.Caused by Problems in Valve Operators.Valves Removed & Cleaned + (ML20071C055)
- 05000271/LER-1983-004, Forwards LER 83-004/03L-0 + (ML20071C057)
- ML20071C059 + (ML20071C059)
- ML20071C060 + (ML20071C060)
- ML20071C066 + (ML20071C066)
- 05000271/LER-1983-004-03, /03L-0:on 830120,flowmeter on Containment Air Monitor Read Zero Due to Leakage Past Detector O-ring Seal Into Reactor Bldg.Cause Not determined.O-ring Reseated + (ML20071C069)
- ML20071C073 + (ML20071C073)
- 05000280/LER-1983-003, Forwards LER 83-003/01T-0 + (ML20071C075)
- 05000244/LER-1983-007, Forwards LER 83-007/03L-0 + (ML20071C079)
- ML20071C087 + (ML20071C087)
- 05000280/LER-1983-003-01, /01T-0:on 830209,MOV-SW-103A,B,C & D & MOV-SW-203A,C & D Failed to Open Upon Demand from Control Room.Caused by Corrosion on Motors of MOV-SW-103C & 203C & Torque Switch of 103B.Valves Repaired + (ML20071C089)
- 05000244/LER-1983-007-03, /03L-0:on 830117,water Level in Pressurizer Dropped Below 12% Level.Caused by RCS Cooldown Following Trip.Level Returned to 19.5% within 15 Minutes + (ML20071C090)