Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20063P378 + (ML20063P378)
- ML20063P380 + (ML20063P380)
- ML20063P381 + (ML20063P381)
- 05000311/LER-1982-109, Forwards LER 82-109/01T-0.Detailed Event Analysis Encl + (ML20063P382)
- 05000387/LER-1982-020, Forwards LER 82-020/03L-0 + (ML20063P384)
- 05000346/LER-1982-031, Forwards LER 82-031/03X-2 + (ML20063P388)
- ML20063P390 + (ML20063P390)
- 05000311/LER-1982-109-01, /01T-0:on 820923,svc Water Leakage of Approx 0.6 Gpm Discovered on Containment Fan Coil Unit 21 Cooling Coil. Caused by Erosion by Silt in Svc Water.Leaks Repaired W/ Blanked Flange & Belzona Metal Filler + (ML20063P391)
- 05000387/LER-1982-020-03, /03L-0:on 820903,after Both RHR Sys Trains Removed from Svc,Pressure & Temp Were Not Recorded.Caused by Operator Misjudgment.Operators Instructed to Log & Follow All Action Statements + (ML20063P394)
- 05000387/LER-1982-018, Forwards LER 82-018/03L-0 + (ML20063P396)
- ML20063P398 + (ML20063P398)
- 05000346/LER-1982-031-03, /03X-2:on 820625 & 0706,fire Barrier Doors 500 & 426 Found Slightly Open.On 820629,fire Barrier & Negative Pressure Door 302 Found Slightly Open.Caused by Closure Mechanism Failure to Seat Doors Tightly Due to Design Error + (ML20063P400)
- ML20063P401 + (ML20063P401)
- 05000387/LER-1982-018-03, /03L-0:on 820902,w/mode Switch in Refuel,Three Out of Four Source Range Monitors Were Inoperable.Caused by Inadvertent Stressing of Cables During Undervessel Work. Procedure Revised to Reduce Cable Wear + (ML20063P405)
- ML20063P406 + (ML20063P406)
- ML20063P407 + (ML20063P407)
- 05000313/LER-1982-026, Forwards LER 82-026/03L-0 + (ML20063P413)
- ML20063P416 + (ML20063P416)
- 05000313/LER-1982-026-03, /03L-0:on 820901,installed Hose Reel (HR-49) Found Not Visually Inspected Per Tech Specs.Caused by Lack of Communication,Leading to Omission of HR-49 from Insp procedures.HR-49 Inspected & Procedure Revised + (ML20063P418)
- 05000387/LER-1982-019-01, /01T-0:on 820920,during Power Ascension Testing, Turbine Bldg Vent Monitor Sys Became Inoperable.Caused by Failure to Remove Mechanical Vacuum Pump from Svc.Pump Stopped & Steam Jet Air Ejectors Placed in Svc + (ML20063P419)
- ML20063P420 + (ML20063P420)
- 05000331/LER-1982-058, Forwards LER 82-058/03L-0 + (ML20063P422)
- 05000331/LER-1982-058-03, /03L-0:on 820910,river Water Supply Sys Traveling Screen 1F-36B Would Not Run in Auto or Continuous Mode. Caused by Low Discharge Pressure for Screen Wash Pump. Permissive Pressure Switch PS-2903 Recalibr + (ML20063P428)
- 05000346/LER-1982-043, Forwards LER 82-043/03L-0 + (ML20063P435)
- 05000366/LER-1982-109, Forwards LER 82-109/03L-0 + (ML20063P438)
- ML20063P440 + (ML20063P440)
- 2CAN108202, Responds to NRC Transmitting Amend 24 to License NPF-6 Re Seized Reactor Coolant Pump Shaft Event Reanalysis. Event Description & Results of Cycle 2 Seized Rotor Event Encl + (ML20063P442)
- 05000346/LER-1982-043-03, /03L-0:on 820829,fire Door 428C to Electrical Isolation Room 429A Found Cracked Open.Caused by Component Failure.Latch Mechanism Repaired + (ML20063P443)
- 05000247/LER-1982-035, Forwards LER 82-035/03L-0 + (ML20063P444)
- 05000254/LER-1982-027, Forwards LER 82-027/03L-0 + (ML20063P446)
- 05000366/LER-1982-109-03, /03L-0:on 820908,performance of RCIC Preventative Maint Procedure Disclosed Inoperability of RCIC Trip & Throttle Valve & RCIC Sys.Caused by Closure of Turbine Trip & Throttle Valve.Trip & Throttle Valve Opened + (ML20063P448)
- ML20063P452 + (ML20063P452)
- 05000247/LER-1982-035-03, /03L-0:on 820829,nuclear Power Range Instrumentation Channel N41 Became Inoperative Due to Failure of Power Supply Unit.Cause of Unit Failure Not Stated.Defective High Voltage Power Supply Removed + (ML20063P454)
- ML20063P459 + (ML20063P459)
- 05000373/LER-1982-100, Forwards LER 82-100/03L-0 + (ML20063P461)
- 05000259/LER-1982-070, Forwards LER 82-070/03L-0 + (ML20063P463)
- ML20063P465 + (ML20063P465)
- ML20063P466 + (ML20063P466)
- 05000373/LER-1982-100-03, /03L-0:on 820903,RCIC Equalizing Valves Failed to Close.Caused by Improperly Adjusted Spring Tension.Spring Tension Adjusted + (ML20063P468)
- ML20063P469 + (ML20063P469)
- ML20063P470 + (ML20063P470)
- 05000259/LER-1982-070-03, /03L-0:on 820908,while Calibr Reactor Protection Sys high-water Level Switches on Scram Discharge Tank,Level Switch LS-85-45E Operated at 27 Gallons,Contrary to Tech Specs.Caused by Calibr Drift on Level Switch SL-305-EI-X + (ML20063P471)
- 05000327/LER-1982-108, Forwards LER 82-108/03L-0 + (ML20063P475)
- ML20063P479 + (ML20063P479)
- 05000327/LER-1982-108-03, /03L-0:on 820907,during Mode 1,level Channel LT-63-50 on Refueling Water Storage Tank Declared Inoperable.Caused by Transmitter Out of Tolerance Due to Instrument Drift.Loop Recalibr + (ML20063P486)
- 05000335/LER-1982-041, Forwards LER 82-041/03L-0 + (ML20063P489)
- 05000317/LER-1982-056, Forwards LER 82-056/03L-0 + (ML20063P494)
- 05000335/LER-1982-041-03, /03L-0:on 820907,at 99% Power,Reactor/Turbine Trip Occurred Resulting in Brief Loss of Vital Buses & Iodine Spike.Caused by Motor Auxiliary Contact Initiating False Loss of Load & Inhibit Signals + (ML20063P496)
- 05000254/LER-1982-032, Forwards LER 82-032/03L-0 + (ML20063P498)
- ML20063P500 + (ML20063P500)
- ML20063P501 + (ML20063P501)