- ML20063P111 + (ML20063P111)
- L-82-427, Final Deficiency Rept Re Incorrect Shaft Bearings on Diesel Generator Motors 2A1 & 2A2.Initially Reported on 820826.Shaft Bearings Replaced w/self-aligning Bearings.Not Reportable Per 10CFR50.55e,but Reportable Per Part 21 + (ML20063P138)
- ML20063P144 + (ML20063P144)
- ML20063P147 + (ML20063P147)
- ML20063P151 + (ML20063P151)
- 05000346/LER-1982-044, Forwards LER 82-044/03L-0 + (ML20063P155)
- 05000346/LER-1982-044-03, /03L-0:on 820916,review Revealed That Steam & Feedwater Rupture Control Sys Monthly Surveillance Procedure ST 5031.14 Not Completed in Time Allotted in Tech Specs. Caused by Personnel Error.Test Completed + (ML20063P157)
- PM-82-101, Forwards Monthly Operating Repts for Sept 1982 + (ML20063P158)
- ML20063P160 + (ML20063P160)
- 05000331/LER-1982-057, Forwards LER 82-057/03L-0 + (ML20063P161)
- 05000331/LER-1982-057-03, /03L-0:on 820902,during Normal Operation,While Investigating River Water Intake Sys 1C-102 Trouble Alarm, Mode Switch HS-2906B Found in Off Position.Caused by Lack of Procedural Guidance.Procedures Under Review + (ML20063P163)
- ML20063P164 + (ML20063P164)
- ML20063P166 + (ML20063P166)
- ML20063P167 + (ML20063P167)
- 05000255/LER-1982-027, Forwards LER 82-027/03L-0 + (ML20063P168)
- ML20063P170 + (ML20063P170)
- 05000255/LER-1982-027-03, /03L-0:on 820901,procedural Inadequacies Discovered Which Could Cause Reduction in Degree of Redundancy in Containment Cooling Sys.Procedures Revised to Require Fans to Be Declared Inoperable If Stopped + (ML20063P172)
- ML20063P175 + (ML20063P175)
- ML20063P176 + (ML20063P176)
- ML20063P178 + (ML20063P178)
- ML20063P180 + (ML20063P180)
- 05000259/LER-1982-072, Forwards LER 82-072/03L-0 + (ML20063P183)
- ML20063P185 + (ML20063P185)
- 05000259/LER-1982-072-03, /03L-0:on 820908,during Startup,Rod Worth Minimizer (RWM) Applied Rod Blocks When Rod 30-51 Selected. Caused by Listing Two Rods Twice in RWM Sequence Due to Typing Error.Rwm Sequence Corrected & Returned to Svc + (ML20063P186)
- 05000311/LER-1982-103-03, /03L-0:on 820904,while Running Auxiliary Alarm Summary,Control Breaker Alarm Observed for Containment Spray Pump 21.Caused by Opened 4 Kv Breaker Hl Contact.Breaker Racked Out & Pump Declared Operable + (ML20063P187)
- 05000259/LER-1982-075, Forwards LER 82-075/01T-0 + (ML20063P188)
- ML20063P190 + (ML20063P190)
- ML20063P191 + (ML20063P191)
- 05000259/LER-1982-075-01, /01T-0:on 820924,four Degraded Voltage Relays, Three Timers & One loss-of-voltage Relay Found to Be Outside Allowable Tech Spec Setpoint Range.Caused by Setpoint Drift. Relays Recalibr & Returned to Svc + (ML20063P193)
- 05000369/LER-1982-069, Forwards LER 82-069/03L-0.Detailed Event Analysis Encl + (ML20063P194)
- ML20063P197 + (ML20063P197)
- 05000369/LER-1982-069-03, /03L-0:on 820903,investigation of Several Spurious Fire Detection Sys Zone Alarms Resulted in Sys Being Declared Inoperable.Caused by Water in Data Gathering Panel Creating Ground Condition Affecting Entire Sys + (ML20063P198)
- ML20063P199 + (ML20063P199)
- RBG-13-482, Interim Deficiency Rept 73 Re Improperly Installed Spring Nuts in GE Supplied Power Generation Control Complex Termination Cabinets.Initially Reported on 820902. Investigation Continuing.Next Rept Expected by 830121 + (ML20063P201)
- 05000366/LER-1982-101, Forwards LER 82-101/03L-0 + (ML20063P202)
- ML20063P204 + (ML20063P204)
- 05000366/LER-1982-101-03, /03L-0:on 820829,inboard MSIV in Loop C Failed Closed.Caused by Improper Stem to Disk Thread Engagement. Disk & Stem Assembly Replaced in Both C Loop Msivs.Valves Tested & Returned to Svc + (ML20063P205)
- ML20063P207 + (ML20063P207)
- ML20063P208 + (ML20063P208)
- ML20063P210 + (ML20063P210)
- 05000254/LER-1982-030, Forwards LER 82-030/03L-0 + (ML20063P211)
- ML20063P213 + (ML20063P213)
- 05000244/LER-1982-019, Forwards LER 82-019/03L-0 + (ML20063P214)
- 05000254/LER-1982-030-03, /03L-0:on 820905,while Testing RHR Svc Water Pump 1-1001-65D,packing Found Burned.Caused by Excessive Tightening in Packing to Limit Leakage.Mods Installed to Protect Bearings from Seal Leakage + (ML20063P216)
- 05000249/LER-1982-034, Forwards LER 82-034/03L-0 + (ML20063P217)
- 05000244/LER-1982-019-03, /03L-0:on 820901,while Performing PT-2.9, Containment Particulate/Gas Radiation Monitor R11/12 Return Line Isolation Check Valve CV-1599 Found Leaking Excessively.Caused by Graphite in Valve & Valve Disc Wear + (ML20063P219)