- ML20063K770 + (ML20063K770)
- 05000298/LER-1993-026, :on 930618,determined That Safety Related Portions of SW & Reactor Equipment Cooling Sys Piping Not Included in ASME Code Section XI ISI Program.Portions Will Be Included by Next Refueling Outage + (ML20063K771)
- ML20063K774 + (ML20063K774)
- ML20063K779 + (ML20063K779)
- 05000416/LER-1982-035-03, /03L-0:on 820803,plant Svc Water Sys Isolation Valve Q1P44-F119 Closed Due to Secondary Containment Isolation Signal Generated by Reactor Protection Sys Electrical Fault.Caused by Incorrectly Positioned Switches + (ML20063K781)
- 05000316/LER-1982-068, Forwards LER 82-068/03L-0 + (ML20063K785)
- ML20063K790 + (ML20063K790)
- ML20063K791 + (ML20063K791)
- ML20063K795 + (ML20063K795)
- ML20063K797 + (ML20063K797)
- 05000316/LER-1982-068-03, /03L-0:on 820801,overpressure Protection Sys Channel Functional Test on Power Operated Relief Valve Actuation Channel Not Performed as Required.Caused by Personnel Error.New Procedure Approved + (ML20063K804)
- ML20063K809 + (ML20063K809)
- 05000382/LER-1994-001-02, :on 940118,discovered That Component Cooling Water Valves Open Approx 30% Due to Lack of Work Instructions.Valve Operators for Affected Valves Adjusted to Close Valves & Valves Locked Closed + (ML20063K812)
- ML20063K814 + (ML20063K814)
- ML20063K819 + (ML20063K819)
- ML20063K820 + (ML20063K820)
- ML20063K824 + (ML20063K824)
- ML20063K825 + (ML20063K825)
- SVP-94-012, Responds to Violations Noted in Insp Repts 50-456/93-22 & 50-457/93-22.Corrective Actions:Administrative Controls for Open Fire Door Will Remain in Place Until Door Can Be Closed + (ML20063K827)
- 05000327/LER-1982-099, Forwards LER 82-099/03L-0 + (ML20063K832)
- IR 05000348/2019006 + (ML20063K834)
- ML20063K841 + (ML20063K841)
- ML20063K845 + (ML20063K845)
- ML20063K846 + (ML20063K846)
- 05000416/LER-1982-038, Forwards LER 82-038/03L-0 + (ML20063K847)
- ML20063K853 + (ML20063K853)
- 05000280/LER-1980-009, Forwards LERs 82-049/03L-0,82-080/03L-0 & Updated LER 80-009/01X-1 + (ML20063K854)
- 05000327/LER-1982-099-03, /03L-0:on 820803,refueling Water Storage Tank Level Channel 1-LT-63-50 Declared Inoperable Due to Failing Low.Caused by Faulty Circuit Board in Barton Model 752 Transmitter.Circuit Board Replaced + (ML20063K862)
- ML20063K868 + (ML20063K868)
- 05000416/LER-1982-038-03, /03L-0:on 820804,Zone 2-15 Smoke Detector in Auxiliary Bldg 185-ft Cable Chase Alarmed on Security/Fire Protection Computer & Would Not Clear.Caused by Malfunctioning Hardware.Supervisory Line Board Replaced + (ML20063K870)
- NG-94-0336, Responds to Violation Noted in Insp Rept 50-331/93-19 Re Facility GL 89-10 MOV Program.Corrective actions:re- Evaluation of Votes Data on All GL 89-10 Valves Tested Prior to Refueling Outage 12 Will Be Completed by 940401 + (ML20063K877)
- 05000280/LER-1982-049-03, /03L-0:on 820807,2-SW-P-10B Charging Pump Svc Water Pump Failed to Develop Sufficient Discharge Pressure. Caused by Leaking Pump Strainer.Strainer Replaced & Pump Returned to Svc + (ML20063K883)
- ML20063K885 + (ML20063K885)
- 05000331/LER-1994-003, :on 940124,determined That TS Table 3.2-A Action Statement for Off Gas Vent RMs Not Complied W/During Routine Maint on 940119 Due to Improperly Prepared Work Document.License Amend Process Revised + (ML20063K886)
- 05000280/LER-1982-080-03, /03L-0:on 820804,core Cooling Monitor B Began to Show Erratic Indication & Removed from Svc.Caused by Failure of Relay on Printed Circuit Board.Relay Replaced & Monitor Returned to Svc + (ML20063K893)
- PLA-1258, Second Interim Deficiency Rept Re Emergency Svc Water Sys Water Hamer.Initially Reported on 820505.Design Change Packages Issued & Scheduled for Implementation Prior to 5% Power.Next Rept Will Be Submitted by Mar 1983 + (ML20063K900)
- 05000280/LER-1980-009-01, Westinghouse LOCA-ECCS Reanalysis Indicated Residual Penalty of 0.007 in Fq Exists from Fuel Rod Burst Model.Caused by Reduction in Clad Heatup Rate Which Shifts Fuel Clad Burst Curve + (ML20063K906)
- ML20063K918 + (ML20063K918)
- ML20063K922 + (ML20063K922)
- PY-CEI-NRR-1755, Seismic Rept:On 940107,triaxial time-history Accelerographs for Reactor Building & Containment Vessel Declared Inoperable During Performance of Surveillance Testing. Amplifier Card & Motor Driver Card Replaced + (ML20063K924)
- 05000327/LER-1982-101, Forwards LER 82-101/03L-0 + (ML20063K926)
- ML20063K929 + (ML20063K929)
- 05000456/LER-1993-007-07, :on 931213,both Trains of Control Room Ventilation Declared Inoperable Due to Equipment Failure & Procedural Deficiency.Failed Hydramotor Replaced & Frequency of Loop Calibr Will Be Increased + (ML20063K941)
- ML20063K943 + (ML20063K943)
- 05000327/LER-1982-101-03, /03L-0:on 820805,neutron Instrumentation Power Range Channel N41 Failed Low.Caused by Defective Power Range Channel High Range Power Supply,Model UPM5-X54W.Power Supply Replaced + (ML20063K946)
- 05000339/LER-1982-044, Forwards LER 82-044/03L-0 + (ML20063K948)
- ML20063K950 + (ML20063K950)
- ML20063K952 + (ML20063K952)
- ML20063K955 + (ML20063K955)
- ML20063K960 + (ML20063K960)
- 05000339/LER-1982-044-03, /03L-0:on 820812,during Mode 5 Operation,Steady State Chloride Limit in RCS Exceeded for More than 24-h. Caused by Introduction of Contaminants Into RCS During Maint.Letdown Path re-established + (ML20063K968)