- ML20040C751 + (ML20040C751)
- 05000260/LER-1981-065-03, /03L-0:on 811211,HPCI Suppression Chamber High Level Switches Discovered to Be Set 8 Inches Above Normal Level.Caused by Change to Tech Specs Not Being Reflected in Table 3.2.B.Switches Physically Lowered + (ML20040C752)
- 05000335/LER-1981-057-03, /03L-0:on 811106,NRC Inspector Noticed Grease on Fitting Used to Addl Fluid to Hydraulic Snubber.Eight Snubbers in Component Cooling Sys Contaminated.Caused by Improper Lubrication.Snubbers Rebuilt + (ML20040C753)
- ML20040C754 + (ML20040C754)
- ML20040C755 + (ML20040C755)
- ML20040C757 + (ML20040C757)
- ML20040C758 + (ML20040C758)
- 05000366/LER-1981-126-03, /03L-0:on 811215,during steady-state Operation Analyzer 2T49-B001B Found Inoperative.Caused by Component Failure.Power Supply Filter Capacitor Replaced & Tested Satisfactorily + (ML20040C759)
- 05000366/LER-1981-119-03, /03L-0:on 811207,main Steam Line High Radiation Instrument 2D1-K603D,hi Hi Trip Was Found to Actuate at 4850 M/H.Caused by Setpoint Drift.Switch Recalibr & Successfully Functionally Tested Per HNP-2-3005 + (ML20040C760)
- ML20040C761 + (ML20040C761)
- ML20040C764 + (ML20040C764)
- ML20040C765 + (ML20040C765)
- 05000366/LER-1981-130, Forwards LER 81-130/03L-0 + (ML20040C767)
- ML20040C769 + (ML20040C769)
- ML20040C770 + (ML20040C770)
- 05000366/LER-1981-130-03, /03L-0:on 811217,while Making Power Changes from 2352 Mwt to 2111 Mwt,Low Pressure Alarms Were Received on CRD Hydraulic Control Units H26-47 & H46-15.Switches Found Out of Tolerance.Caused by Setpoint Drift.Switches Recalib + (ML20040C771)
- 1CAN018202, Informs That Addl Info Deemed Not Required for TMI Action Item II.K.2.16 (Reactor Coolant Pump Seal Damage) & 800523 Response + (ML20040C772)
- 05000321/LER-1981-140, Forwards LER 81-140/03L-0 + (ML20040C773)
- ML20040C775 + (ML20040C775)
- ML20040C777 + (ML20040C777)
- ML20040C782 + (ML20040C782)
- ML20040C783 + (ML20040C783)
- ML20040C784 + (ML20040C784)
- ML20040C786 + (ML20040C786)
- 05000321/LER-1981-140-03, /03L-0:on 811218,overheating Electrical Insulation Was Observed in Main Control Room.Caused by Loose Connection on Line Side of Fuse Block Resulting in Overheating.Jumper & Fuse Block Replaced + (ML20040C787)
- 05000339/LER-1981-089, Forwards LER 81-089/03L-0 + (ML20040C788)
- ML20040C790 + (ML20040C790)
- 05000321/LER-1981-133, Forwards LER 81-133/03L-0 + (ML20040C791)
- ML20040C793 + (ML20040C793)
- ML20040C794 + (ML20040C794)
- 05000321/LER-1981-133-03, /03L-0:on 811204,recombiner Bldg Vent Monitor P003A Was Found Inoperable.Sample Pump a Was Inoperable But Redundant Pump B Was Put in Svc & Sys Resumed Normal Operation.Caused by Pump Being Wired W/Improper Voltage + (ML20040C795)
- ML20040C796 + (ML20040C796)
- ML20040C798 + (ML20040C798)
- ML20040C799 + (ML20040C799)
- ML20040C801 + (ML20040C801)
- ML20040C802 + (ML20040C802)
- ML20040C803 + (ML20040C803)
- IR 05000278/1981032 + (ML20040C804)
- ML20040C805 + (ML20040C805)
- 05000324/LER-1981-130, Forwards LER 81-130/03L-0 + (ML20040C806)
- PNO-I-82-009A, on 820125,RCS at 822 psig,370 F.Bubble Drawn in Pressurizer & Pressurizer Leveled Out Near 50%.Cooldown Reduced to 5 F/H + (ML20040C808)
- 05000324/LER-1981-130-03, /03L-0:on 811210,variable Sensing Log Isolation Root Valve of Reactor Level Instrument Found Not to Hold Pressure & Automatic Depressurization Sys Declared Inoperable.Cause Not Determined.Penetration Test Completed + (ML20040C809)
- ML20040C810 + (ML20040C810)
- ML20040C811 + (ML20040C811)
- ML20040C813 + (ML20040C813)
- PNO-I-82-009, on 820125,primary to Secondary Leakage Indicated in Steam Generator B & Reactor Trip Initiated. Site Alert Declared & Upgraded to Site Emergency.Reactor Containment Isolated.All Levels Returned to Background + (ML20040C814)
- IR 05000322/1981023 + (ML20040C815)
- ML20040C816 + (ML20040C816)
- PNO-III-81-121A, Region 2,NRR & Resident Inspector Completed Review of 811228 Plant Scram.Licensee Plans to Take Reactor Critical 820122.Special Testing & Monitoring of Main & Reserve Transformer Breakers Will Be Performed + (ML20040C817)
- ML20040C818 + (ML20040C818)
- PNO-I-82-004A, on 820118,vehicle Owned by Us Priority Transport Co (non-licensee) Carrying Radioactive Matl Was Stolen.Boston Police Dept Recovered Vehicle Same Day.All Radioactive Contents Accounted for + (ML20040C819)