Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000369/LER-1981-027, Forwards LER 81-027/03L-0.Detailed Event Analysis Encl + (ML20032B294)
- 05000366/LER-1981-020-03, /03L-0:on 810311,while Performing HNP-2-3102, Reactor High Pressure Function Test & Calibr,Reactor Pressure Switch 2B21-N018B Actuated at 164 Psig.Caused by Setpoint Drift.Switch Recalibr + (ML20032B296)
- ML20032B298 + (ML20032B298)
- 05000369/LER-1981-027-03, /03L-0:on 810306,while in Mode 5,initial Fuel Loading Diesel Generator 1A Inoperable Due to Lack of Cooling Water & Diesel Generator 1B Failed to Start.Caused by Cooling Water Being Isolated for Unrelated Work + (ML20032B299)
- ML20032B300 + (ML20032B300)
- ML20032B302 + (ML20032B302)
- ML20032B303 + (ML20032B303)
- ML20032B304 + (ML20032B304)
- ML20032B307 + (ML20032B307)
- 05000321/LER-1980-125, Has Been Cancelled + (ML20032B308)
- ML20032B309 + (ML20032B309)
- ML20032B311 + (ML20032B311)
- 05000321/LER-1981-012, Forwards LER 81-012/03L-0 + (ML20032B312)
- 05000338/LER-1981-005, Forwards LER 81-005/03L-0 + (ML20032B314)
- ML20032B316 + (ML20032B316)
- ML20032B317 + (ML20032B317)
- 05000369/LER-1981-022, Forwards LER 81-022/03L-0 + (ML20032B318)
- 05000321/LER-1981-012-03, /03L-0:on 810228,turbine Failed to Trip on Overspeed.Caused by Dried Lubrication Around Overspeed Tripping Mechanisms Causing Binding.Mechanism Disassembled, Cleaned,Relubricated & Reassembled + (ML20032B320)
- 05000338/LER-1981-005-03, /03L-0:on 810105,discovered That Control Room Floor Sleeve 1FC00108 Was Never Resealed After Being Previously Breached for Cable Installation.Caused by Failure of Personnel to Follow Procedures.Sleeve Resealed + (ML20032B321)
- ML20032B322 + (ML20032B322)
- ML20032B323 + (ML20032B323)
- 05000369/LER-1981-022-03, /03L-0:on 810301-16,various Portions of Fire Detection Sys Inoperable for Periods Exceeding 1-h.Caused by Const in Area.Fire Watches & Patrols Established as Required + (ML20032B325)
- 05000348/LER-1981-013-03, /03L-0:on 810327,rod K-14 Declared Inoperable When Failing to Move While Driving Control Bank a Inward.Caused by Connector Problem on CRDM Circuit for Rod.Connector Reassembled & Proper Rod Operation Verified + (ML20032B328)
- 05000369/LER-1981-021, Forwards LER 81-021/03L-0.Detailed Event Analysis Encl + (ML20032B329)
- ML20032B332 + (ML20032B332)
- ML20032B333 + (ML20032B333)
- 05000348/LER-1981-014-03, /03L-0:on 810327,turbine Driven Auxiliary Feedwater Pump Inoperable When Pump Speed Could Not Be Increased Above Min Speed.Caused by Design Wiring Error. Wiring Error Corrected & Pump Returned to Svc + (ML20032B334)
- ML20032B335 + (ML20032B335)
- AECM-81-420, Final Deficiency Rept Re Problem of Fire Damper Fusible Link & Retaining Tab Design on Type I Fire Dampers,Initially Reported 810206.American Warming & Ventilating,Inc Has Provided Fusible Link Insp & Installation Procedure + (ML20032B336)
- 05000369/LER-1981-021-03, /03L-0:on 810226,noble Gas Activity Monitor for Condenser Evacuation Sys EMF-33 Not Functioning.Caused by Excessive Amounts of Condensation in Sample Lines.Moisture Removed.Different Type of Moisture Separator to Be Used + (ML20032B338)
- ML20032B339 + (ML20032B339)
- ML20032B340 + (ML20032B340)
- ML20032B341 + (ML20032B341)
- ML20032B342 + (ML20032B342)
- 05000369/LER-1981-020, Forwards LER 81-020/03L-0.Detailed Event Analysis Encl + (ML20032B343)
- 05000327/LER-1981-003, Forwards LER 81-003/03L-0 + (ML20032B346)
- 05000338/LER-1981-012, Forwards LER 81-012/03L-0 + (ML20032B348)
- ML20032B350 + (ML20032B350)
- 05000327/LER-1981-003-03, /03L-0:on 810105,main Feedwater Flow Channel F-3-35B Failed Low.On 810112 Feedwater Channel F-3-35B & F-3-90B Failed.Caused by Freezing of Inadequately Protected Instrument Sense Lines.Lines Thawed + (ML20032B351)
- 05000338/LER-1981-012-03, /03L-0:on 810118,fuel Bldg Supply & Exhaust Fan Suction Dampers Switched to Failed Position,Bypassing Iodine Filter Bank When Control Bank Was Isolated.Caused by Low Outdoor Temp.Dampers Positioned to Exhaust Through Filter + (ML20032B352)
- 05000369/LER-1981-020-03, /03L-0:on 810219,spurious High Radiation Alarm & Loss of Flow Alarm Sounded in Control Room on EMF-49. Personnel Cleared Radiation Alarm But Overlooked Closed Valve,Causing Loss of Flow Alarm.Monitor Repaired + (ML20032B354)
- ML20032B355 + (ML20032B355)
- ML20032B357 + (ML20032B357)
- BSEP-81-1857, Responds to Re Violations Noted in IE Insp Repts 50-324/81-19 & 50-325/81-19.Corrective Actions:Personnel Instructed to Verify Completion of Procedural Revisions Re Correct Use of Contamination Clothing + (ML20032B358)
- 05000369/LER-1981-018, Forwards LER 81-018/03L-0.Detailed Event Analysis Encl + (ML20032B359)
- ML20032B361 + (ML20032B361)
- AECM-81-431, Final Deficiency Rept Re Safety Relief Valve Control Sys, Originally Reported on 771007.Design of Sys Which Controls Safety Relief Valve Actuation Modified.Mod Presented to NRC by GE on 800208.Description of Design Submitted 810902 + (ML20032B362)
- ML20032B363 + (ML20032B363)
- ML20032B364 + (ML20032B364)
- 05000369/LER-1981-018-03, /03L-0:on 810219,annunciator Alarm Indicated Loss of Sample Flow on Radiation Monitor 1-EMF-33.Monitor Vacuum Pump Internally Damaged Due to Water Inside Pump.Pump Vanes & Bearings Replaced & Water Removed + (ML20032B365)
- ML20032B366 + (ML20032B366)