Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20009H567 + (ML20009H567)
- 05000260/LER-1981-035-03, /03L-0:on 810708,while Performing Level Switch Testing,Scram Discharge Instrument Vol Tank Level Switch 2-LS-85-45F Failed to Operate.Caused by Inoperable Robertshaw Level Switch Model SL-305-EI-X.Switch Replaced + (ML20009H568)
- 05000259/LER-1981-032, Forwards Updated LER 81-032/01X-1 + (ML20009H569)
- ML20009H570 + (ML20009H570)
- ML20009H574 + (ML20009H574)
- ML20009H577 + (ML20009H577)
- ML20009H578 + (ML20009H578)
- 05000259/LER-1981-032-01, While Performing Surveillance Instruction 4.2.B.8,switches Ps 68-93 & 94 Were Out of Limits of Tech Specs.Caused by Setpoint Drift. Barksdale Model B2T-M12SS Pressure Switches Reset + (ML20009H579)
- AECM-81-240, Final Deficiency Rept Re Reactor Controls,Inc Issuance of Drawings Prior to Verification of Design Adequacy,Initially Reported on 800925.Stop Work Order Issued Until Design Adequacy Verified + (ML20009H580)
- 05000260/LER-1981-038, Forwards LER 81-038/03L-0 + (ML20009H581)
- ML20009H582 + (ML20009H582)
- 05000260/LER-1981-038-03, /03L-0:on 810706,while Moving Equipment Through Equipment Air Lock Door,Door 238 Not Latched Properly When Opposite Door Was Opened,Resulting in Momentary Breach of Secondary Containment.Caused by Personnel Error + (ML20009H587)
- ML20009H589 + (ML20009H589)
- 05000338/LER-1981-053, Forwards LER 81-053/03L-0 + (ML20009H592)
- ML20009H593 + (ML20009H593)
- ML20009H595 + (ML20009H595)
- 05000338/LER-1981-053-03, /03L-0:on 810710 & 12,post Reactor Trip Specific Activity Samples of RCS Indicated Dose Equivalent I-131 Level Greater than Tech Specs.Caused by Known Fuel Element Defect in Reactor Core + (ML20009H596)
- 05000324/LER-1981-060, Forwards LER 81-060/03L-0 + (ML20009H600)
- ML20009H601 + (ML20009H601)
- ML20009H602 + (ML20009H602)
- 05000261/LER-1981-018, Forwards LER 81-018/03L-0 + (ML20009H603)
- ML20009H604 + (ML20009H604)
- ML20009H606 + (ML20009H606)
- 05000324/LER-1981-060-03, /03L-0:on 810702,main Steam Line Isolation Valve Failed Causing Reactor Scram.On 810718,main Steam Line Inboard Isolation Valve Failed to Reopen.Caused by Separation of Steam Disk & Main Disk,Respectively + (ML20009H607)
- 05000261/LER-1981-018-03, /03L-0:on 810701,Channel I (PI-474) of a Steam Generator Steam Line Pressure Indicated High Compared to Two Redundant Channels.Caused by Throttled Root Isolation Valve MSV-14.Valve Reopened + (ML20009H610)
- 05000220/LER-1981-030, Forwards LER 81-030/03L-0 + (ML20009H611)
- ML20009H612 + (ML20009H612)
- ML20009H615 + (ML20009H615)
- 05000220/LER-1981-030-03, /03L-0:on 810630,all Emergency Condenser Vent Monitors Exceeded Upscale Trip Setpoint During Calibr. Caused by Difference in Response Between Test Signal & Actual Signal.Procedure Revised + (ML20009H617)
- ML20009H620 + (ML20009H620)
- ML20009H621 + (ML20009H621)
- 05000309/LER-1981-014, Forwards LER 81-014/01T-0 + (ML20009H622)
- 05000325/LER-1981-056, Forwards LER 81-056/03L-0 + (ML20009H624)
- ML20009H625 + (ML20009H625)
- 05000325/LER-1981-056-03, /03L-0:on 810706,RHR Svc Water Pump 1A Experienced Excess Vibration.Caused by Abnormal Bearing Wear from Water in Pump Bearing.Bearings Replaced + (ML20009H628)
- 05000309/LER-1981-014-01, /01T-0:on 810719,containment Isolation Sys Valve on Alternate Letdown Sys Failed Open.Caused by Packing Being Too Tight on Valve.Valve Repaired & Tested + (ML20009H631)
- 05000321/LER-1981-067, Forwards LER 81-067/03L-0 + (ML20009H632)
- ML20009H633 + (ML20009H633)
- 05000324/LER-1981-062, Forwards LER 81-062/03L-0 + (ML20009H634)
- ML20009H635 + (ML20009H635)
- 05000280/LER-1981-017-03, /03L-0:on 810702,discovered That No Fire Watch Had Been Posted for Two Unsealed Fire Barrier Penetrations in Cable Spreading Room Area.Caused by Const Personnel Error. Fire Watch Posted & Seal Installed + (ML20009H637)
- 05000321/LER-1981-067-03, /03L-0:on 810704,discharge Check Valve E11-F005B Failed to Close After Surveillance Procedure.Caused by Excessive Wear at Point Disc Supported by Disc Hanger.Valve Repaired,Sys Retested & Returned to Svc + (ML20009H638)
- 05000324/LER-1981-062-03, /03L-0:on 810704,control Rod Failed to Have Full in Position Indication Lights Lit When Fully Inserted.Caused by Failed Reed Switch Located in Drywell.Switch to Be Repaired During Future Outage + (ML20009H639)
- ML20009H640 + (ML20009H640)
- ML20009H641 + (ML20009H641)
- ML20009H642 + (ML20009H642)
- 05000280/LER-1981-018-03, Ler 81-018/03L-0:on 810702,power Operated Relief Valves Lifted to Mitigate Overpressurization Transient.Caused by Unisolated Charging Flow Control Valve.Valve Isolated. RCS Pressure Reduced Below Setpoint + (ML20009H643)
- 05000259/LER-1981-035, Forwards Updated LER 81-035/03X-1 + (ML20009H644)
- ML20009H645 + (ML20009H645)
- IR 05000443/1981007 + (ML20009H646)
- 05000304/LER-1981-015, Forwards LER 81-015/99X-0 + (ML20009H648)