Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000259/LER-1981-039-03, /03L-0:on 810703,inverter for Alarm Panel XA-55-8E Became Inoperable.Caused by Failure of Inverter Control Card.Card Replaced & Successfully Tested + (ML20009H529)
- 05000321/LER-1981-079, Forwards LER 81-079/03L-0 + (ML20009H530)
- ML20009H531 + (ML20009H531)
- ML20009H532 + (ML20009H532)
- 05000369/LER-1981-093, Forwards Updated LER 81-093/01X-1 + (ML20009H533)
- ML20009H534 + (ML20009H534)
- ML20009H535 + (ML20009H535)
- 05000321/LER-1981-079-03, /03L-0:on 810713,pump P41-C001C Failed to Meet Acceptance Criteria for Total Dynamic Head.Caused by Wear & Erosion.Pump Removed & Rebuilt + (ML20009H536)
- 05000369/LER-1981-093-01, Three Instrument Lines Which Penetrate Containment Were Not Closed.Caused by Three Containment Isolation Valves Left Open Due to Omission from Containment Penetration List.Valves Closed + (ML20009H537)
- ML20009H538 + (ML20009H538)
- IR 05000293/1981011 + (ML20009H539)
- 05000247/LER-1981-017, Forwards LER 81-017/03L-0 + (ML20009H540)
- ML20009H541 + (ML20009H541)
- 05000338/LER-1981-051, Forwards LER 81-051/03L-0 + (ML20009H542)
- ML20009H543 + (ML20009H543)
- 05000247/LER-1981-017-03, /03L-0:on 810630,feed Breaker for 480-volt Bus 5A Opened & Associated Lockout Relay Actuated.Caused by Defective Westinghouse DB-75 Breaker Tripping Device. Device Replaced + (ML20009H544)
- 05000213/LER-1981-010, Forwards LER 81-010/03L-0 + (ML20009H545)
- 05000213/LER-1981-010-03, /03L-0:on 810704,charging Pump B Found Leaking Oil.Caused by Vibration Which Cracked Hardened Pipe Thread Sealing Matl.Two Nipples & Union Replaced + (ML20009H549)
- 05000338/LER-1981-051-03, /03L-0:on 810703-08,containment Average Air Temp Exceeded Tech Specs.Caused by Temporary Loss of Cooling Medium.Temp Reduced by Placing Steam Chiller in Svc + (ML20009H550)
- ML20009H551 + (ML20009H551)
- ML20009H553 + (ML20009H553)
- ML20009H554 + (ML20009H554)
- ML20009H555 + (ML20009H555)
- ML20009H556 + (ML20009H556)
- 05000271/LER-1981-017, Forwards LER 81-017/03L-1 + (ML20009H558)
- ML20009H559 + (ML20009H559)
- ML20009H560 + (ML20009H560)
- 05000271/LER-1981-017-03, /03L-1:on 810629,containment Isolation Valve LRN-95 Failed to Close During Quarterly Surveillance.Caused by three-way Air Solenoid Failure to Exhaust Air Due to Dirt Plugging Port.Solenoid Was Cleaned,Tested & Returned to Sv + (ML20009H561)
- IR 05000317/1981010 + (ML20009H562)
- L-81-321, Interim Deficiency Rept Re Omission of Locking Rings Slots on Modutronic Controller/Allen Bradley Selector Switches, Initially Reported 810624.Deficiency Being Evaluated.Addl Info Will Be Provided by 810803 + (ML20009H565)
- ML20009H567 + (ML20009H567)
- 05000260/LER-1981-035-03, /03L-0:on 810708,while Performing Level Switch Testing,Scram Discharge Instrument Vol Tank Level Switch 2-LS-85-45F Failed to Operate.Caused by Inoperable Robertshaw Level Switch Model SL-305-EI-X.Switch Replaced + (ML20009H568)
- 05000259/LER-1981-032, Forwards Updated LER 81-032/01X-1 + (ML20009H569)
- ML20009H570 + (ML20009H570)
- ML20009H574 + (ML20009H574)
- ML20009H577 + (ML20009H577)
- ML20009H578 + (ML20009H578)
- 05000259/LER-1981-032-01, While Performing Surveillance Instruction 4.2.B.8,switches Ps 68-93 & 94 Were Out of Limits of Tech Specs.Caused by Setpoint Drift. Barksdale Model B2T-M12SS Pressure Switches Reset + (ML20009H579)
- AECM-81-240, Final Deficiency Rept Re Reactor Controls,Inc Issuance of Drawings Prior to Verification of Design Adequacy,Initially Reported on 800925.Stop Work Order Issued Until Design Adequacy Verified + (ML20009H580)
- 05000260/LER-1981-038, Forwards LER 81-038/03L-0 + (ML20009H581)
- ML20009H582 + (ML20009H582)
- 05000260/LER-1981-038-03, /03L-0:on 810706,while Moving Equipment Through Equipment Air Lock Door,Door 238 Not Latched Properly When Opposite Door Was Opened,Resulting in Momentary Breach of Secondary Containment.Caused by Personnel Error + (ML20009H587)
- ML20009H589 + (ML20009H589)
- 05000338/LER-1981-053, Forwards LER 81-053/03L-0 + (ML20009H592)
- ML20009H593 + (ML20009H593)
- ML20009H595 + (ML20009H595)
- 05000338/LER-1981-053-03, /03L-0:on 810710 & 12,post Reactor Trip Specific Activity Samples of RCS Indicated Dose Equivalent I-131 Level Greater than Tech Specs.Caused by Known Fuel Element Defect in Reactor Core + (ML20009H596)
- 05000324/LER-1981-060, Forwards LER 81-060/03L-0 + (ML20009H600)
- ML20009H601 + (ML20009H601)
- ML20009H602 + (ML20009H602)
- 05000261/LER-1981-018, Forwards LER 81-018/03L-0 + (ML20009H603)