Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- 05000369/LER-1981-082, Forwards LER 81-082/03L-0 + (ML20009F642)
- ML20009F643 + (ML20009F643)
- 05000321/LER-1981-057-03, /03L-0:on 810611,temporary Change to HNP-1-6907 (Reactor Core Isolation Cooling Pump Suction Hydro) Found Not Approved by Mgt within Reguired Time.Caused by Personnel Failure to Maintain Adequate Control Over Procedure + (ML20009F644)
- 05000369/LER-1981-095-03, /03L-0:on 810606,flow Rate Measurement Instrumentation on Waste Monitor Tank a Declared Inoperable During Attempted Liquid Water Release.Caused by Supply Air Isolation Valve to Transmitter Left Closed Following Maint + (ML20009F646)
- 05000348/LER-1981-044-03, /03L-0:on 810610,diesel Generator 1C Declared Inoperable During Test FNP-1-STP-28.1.Caused by Overvoltage Condition Due to Damaged Voltage Regulator Circuitry Resulting from Failed Engine Running Relay + (ML20009F647)
- 05000335/LER-1981-027-03, /03L-0:on 810519,while Cleaning Condenser Water Boxes,Control Element Assembly 65 Dropped While Being Inserted.Cause Unknown.Assembly Returned to Group Position + (ML20009F648)
- 05000369/LER-1981-082-03, /03L-0:on 810504-22,fire Detection Sys Found Inoperable.Caused by Const in Area.Fire Watches & Patrols Established + (ML20009F649)
- ML20009F650 + (ML20009F650)
- ML20009F652 + (ML20009F652)
- 05000339/LER-1981-054, Forwards LER 81-054/03L-0 + (ML20009F653)
- ML20009F654 + (ML20009F654)
- 05000348/LER-1981-045-03, /03L-0:on 810613,train Svc Water Loop a Declared Inoperable.Caused by Inoperable Emergency Recirculation Valve Due to Blown Control Circuit Fuse.Fuse Replaced,Valve Tested & Loop Returned to Svc on 810613 + (ML20009F655)
- 05000260/LER-1981-031, Forwards LER 81-031/03L-0 + (ML20009F656)
- ML20009F657 + (ML20009F657)
- ML20009F658 + (ML20009F658)
- ML20009F659 + (ML20009F659)
- ML20009F660 + (ML20009F660)
- 05000366/LER-1981-065, Forwards LER 81-065/03L-0 + (ML20009F661)
- ML20009F662 + (ML20009F662)
- 05000260/LER-1981-034, Forwards LER 81-034/03L-0 + (ML20009F663)
- ML20009F664 + (ML20009F664)
- 05000339/LER-1981-054-03, /03L-0:on 810629,train J of Onsite Ac Power Sys Discovered Not Tested Per Tech Specs Since 790316.Caused by Mistaken Impression That Both Buses Were Retested on 800331.Emergency Bus J Tested on 800331 + (ML20009F665)
- ML20009F666 + (ML20009F666)
- 05000260/LER-1981-031-03, /03L-0:on 810701,RHR Pump Room Cooler 3-A Developed Water Leak.Caused by Broken Silfos Joint on 1/4-inch Vent Line.Joint Resoldered + (ML20009F667)
- 05000260/LER-1981-034-03, /03L-0:on 810630,RHR Svc Water Pumps B2,D-1 & D-2 Were Not in Svc.Caused by Removing B2 from Svc to Change Motor Oil & Tagging Closed Crosstie Valve to Unit 1, FCV-1-74-100.Oil Changed + (ML20009F668)
- ML20009F669 + (ML20009F669)
- ML20009F671 + (ML20009F671)
- 05000302/LER-1981-039, Forwards LER 81-039/03L-0 + (ML20009F672)
- ML20009F673 + (ML20009F673)
- ML20009F674 + (ML20009F674)
- ML20009F675 + (ML20009F675)
- 05000366/LER-1981-065-03, /03L-0:on 810626,hydrogen-oxygen Analyzer Found Inoperable.Caused by Partially Clogged Gas Flow Regulators. Gas Flow Regulators Cleaned & Readjusted.Analyzer Recalibr + (ML20009F676)
- 05000302/LER-1981-039-03, /03L-0:on 810630,control Rod Units 1 & 2 Rendered Inoperable During Maint on House Svcs Transformer.Caused by Personnel Shorting 4,160-volt Bus Supplying Startup Transformer While Checking Energized Sections + (ML20009F678)
- ML20009F680 + (ML20009F680)
- 05000369/LER-1981-072, Forwards LER 81-072/03L-0.Detailed Event Analysis Encl + (ML20009F681)
- ML20009F683 + (ML20009F683)
- 05000366/LER-1981-061, Forwards LER 81-061/03L-0 + (ML20009F684)
- ML20009F685 + (ML20009F685)
- ML20009F686 + (ML20009F686)
- 05000327/LER-1981-065, Forwards LER 81-065/03L-0 + (ML20009F687)
- ML20009F688 + (ML20009F688)
- 05000369/LER-1981-072-03, /03L-0:on 810427,RHR Sys Discovered Isolated from RCS During Mod of Train a Solid State Protection Sys to Include Reactor on Turbine Trip.Caused by de-energized Relay in Logic,Closing Isolation Valve + (ML20009F689)
- 05000369/LER-1981-076, Forwards LER 81-076/03L-0.Detailed Event Analysis Encl + (ML20009F691)
- ML20009F694 + (ML20009F694)
- ML20009F695 + (ML20009F695)
- ML20009F697 + (ML20009F697)
- 05000369/LER-1981-076-03, /03L-0:on 810502,alarm Annunciated for Noble Gas Activity monitor,EMF-33,indicating Loss of Sample Flow During Initial Fuel Loading.Caused by Bolts Insufficiently Tightened to Secure Seals During Monitor Maint + (ML20009F698)
- ML20009F700 + (ML20009F700)
- 05000327/LER-1981-065-03, /03L-0:on 810603,turbine Sump Discharge Monitor O-RM-90-212 Declared Inoperable.Caused by Broken Pump/Motor Coupling.Coupling Replaced & Monitor Returned to Svc + (ML20009F701)
- 05000366/LER-1981-061-03, /03L-0:on 810624,hi-lo Flow Alarm Received for Reactor Bldg Vent Radiation Monitor Sys.Caused by Tripping of Sample Pumps a & B Due to Overload Protection Tripping. Vanes in Pump a Replaced.Pump B Overload Reset + (ML20009F703)
- 05000339/LER-1981-047, Forwards LER 81-047/03L-0 + (ML20009F705)