Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML20009F481 + (ML20009F481)
- ML20009F483 + (ML20009F483)
- 05000321/LER-1981-065, Forwards LER 81-065/03L-0 + (ML20009F485)
- ML20009F486 + (ML20009F486)
- ML20009F487 + (ML20009F487)
- ML20009F488 + (ML20009F488)
- 05000321/LER-1981-065-03, /03L-0:on 810701,instrument N62-N009A Found Inoperable During Offgas Hydrogen Analyzer Test & Calibr. Caused by Component Failure Due to Restricted Immersion Tube in Flame Check Assembly.Component Replaced + (ML20009F489)
- ML20009F490 + (ML20009F490)
- ML20009F491 + (ML20009F491)
- BSEP-81-1369, RO 1-81-57:on 810717,during Review of Wiring Diagram for Reactor Core Isolation Cooling,Two non-electronic Switching Sys Div 2 Cables Found Intermixed W/One Switching Sys Cable in Controlled Logic Panel in Control Room.Review Underway + (ML20009F492)
- ML20009F493 + (ML20009F493)
- 05000269/LER-1981-013, Forwards LER 81-013/01T-0.Detailed Event Analysis Encl + (ML20009F494)
- ML20009F495 + (ML20009F495)
- ML20009F496 + (ML20009F496)
- 05000369/LER-1981-094, Forwards LER 81-094/03L-0 + (ML20009F497)
- ML20009F498 + (ML20009F498)
- ML20009F499 + (ML20009F499)
- ML20009F500 + (ML20009F500)
- 05000269/LER-1981-013-01, /01T-0:on 810630,backup Function of Isolating & Transfer Diodes in Instrumentation & Control Sys Disabled on All Channels on All Units.Caused by Misinterpretation of Tech Specs.Proposed Tech Spec Change Initiated + (ML20009F501)
- ML20009F502 + (ML20009F502)
- 05000369/LER-1981-094-03, /03L-0:on 810603,flow Rate Measurement Instrumentation on Waste Monitor Tank B Declared Inoperable During Attempted Liquid Waste Release.Caused by Root Valves to Tank Flow Transmitter Left Closed After Equipment Mod + (ML20009F503)
- ML20009F504 + (ML20009F504)
- 05000339/LER-1981-052, Forwards LER 81-052/03L-0 + (ML20009F505)
- ML20009F507 + (ML20009F507)
- ML20009F508 + (ML20009F508)
- ML20009F510 + (ML20009F510)
- ML20009F511 + (ML20009F511)
- 05000339/LER-1981-052-03, /03L-0:on 810619,nuclear Instrumentation Channel N-35 Observed to Be Reading Low & Erratic W/Unit Recovering from Turbine Trip.Caused by Failure of High Voltage Power Supply.Power Supply Replaced + (ML20009F512)
- 05000269/LER-1981-010-03, /03L-0:on 810602,turbine Driven Emergency Feedwater Pump Declared Inoperable.Caused by Governor Valve Sticking in Open Position Due to Sys Contamination.Linkage Pin Removed,Governor Valve Freed & Stem Cleaned + (ML20009F513)
- ML20009F514 + (ML20009F514)
- ML20009F515 + (ML20009F515)
- 05000327/LER-1981-070, Forwards LER 81-070/03L-0 + (ML20009F516)
- ML20009F517 + (ML20009F517)
- 05000327/LER-1981-070-03, /03L-0:on 810619,containment Bldg Lower Compartment Air Monitor Valve Failed to Close on Signal. Caused by Loose Screw in Handswitch,Allowing Open Contact to Short Across,Preventing Solenoid Valve from de-energizing + (ML20009F518)
- ML20009F519 + (ML20009F519)
- 05000324/LER-1981-058, Forwards LER 81-058/03L-0 + (ML20009F520)
- ML20009F521 + (ML20009F521)
- 05000324/LER-1981-058-03, /03L-0:on 810620,chart Recorder of Primary Containment Atmosphere Monitor 2-CAC-AR-1259 Did Not Print Atmospheric Concentrations.Caused by Failed Recorder Printing Mechanism Timing Monitor Due to End of Life + (ML20009F522)
- 05000327/LER-1981-069, Forwards LER 81-069/01T-0 + (ML20009F523)
- ML20009F525 + (ML20009F525)
- ML20009F526 + (ML20009F526)
- RBG-10825, Advises That Applicant Reviewed Generic Ltr 81-01.FSAR, Section 1.8,addresses All Applicable NRC Reg Guides.Licensee Will Be in Compliance W/Reg Guide 1.58,Revision 1 & Reg Guide 1.146 Positions Prior to Receiving OL + (ML20009F527)
- ML20009F528 + (ML20009F528)
- 05000327/LER-1981-069-01, /01T-0:on 810623,pipe Hanger Found Omitted from 3/4-inch Test & Fill Line from 3-inch Boron Injection Line to Safety Injection Accumulators.Caused by Engineering Design Failure to Provide Proper Support Requirements + (ML20009F529)
- 05000302/LER-1981-030, Forwards LER 81-030/03L-0.Detailed Event Analysis Encl + (ML20009F530)
- ML20009F532 + (ML20009F532)
- AECM-81-228, Forwards Revised Pages of & Responses to NRC Questions Re Security Training & Qualification Plan.Pages Withheld (Ref 10CFR2.790) + (ML20009F533)
- 05000302/LER-1981-030-03, /03L-0:on 810526 & 0616,emergency Diesel Generator B Shut Down from Ready Condition.Cause of 810526 Event Undetermined.Event on 810616 Caused by Maladjusted Timing Relay.Relay Adjusted + (ML20009F534)
- 05000366/LER-1981-053, Forwards LER 81-053/03L-0 + (ML20009F535)
- ML20009F537 + (ML20009F537)