- ML19343B401 + (ML19343B401)
- 05000277/LER-1980-031-01, /01T-0:on 801126,water Collected in Offgas Rad Monitor Sampling Sys,Reducing Flow.Caused by Recent Drain Mod Combined W/Pressure Variations Due to Load Change.Water Purged & Full Sample Flow re-established + (ML19343B402)
- 05000327/LER-1980-188, Forwards LER 80-188/03L-0 + (ML19343B403)
- ML19343B405 + (ML19343B405)
- 05000327/LER-1980-188-03, /03L-0:on 801117,determined That Refueling Water Storage Tank Boron Concentration Was Too High.Caused by Excessive Addition of Boron.Boron Free Makeup Water Added to Restore Boron Concentration to Allowable Limits + (ML19343B406)
- ML19343B407 + (ML19343B407)
- ML19343B408 + (ML19343B408)
- ML19343B410 + (ML19343B410)
- 05000336/LER-1980-038, Forwards LER 80-038/03L-0 + (ML19343B411)
- ML19343B412 + (ML19343B412)
- 05000327/LER-1980-189, Forwards LER 80-189/03L-0 + (ML19343B413)
- ML19343B414 + (ML19343B414)
- 05000336/LER-1980-038-03, /03L-0:on 801116,leak Found in C Svc Water Strainer.Caused by Corrosion.Strainer Bodies Scheduled for Replacement + (ML19343B416)
- 05000327/LER-1980-189-03, /03L-0:on 801119,containment Sump Valve to Containment Spray Pump 1B-B,1-FCV-72-20,failed to Open. Caused by Dirty Contacts on Valve Switch.Contacts Cleaned & Valve Tested + (ML19343B417)
- AECM-80-311, Deficiency Rept 3 Re Unqualified Insulation Repairs in Rockbestos Supplied 680 V Cable.Qualification Tests to Be Performed to Demonstrate Acceptability of Repairs.Final Rept to Be Provided by 810224 + (ML19343B418)
- 05000302/LER-1980-050, Forwards LER 80-050/03L-0 + (ML19343B419)
- ML19343B420 + (ML19343B420)
- 05000302/LER-1980-050-03, /03L-0:on 801119,found That Level Indication for Sodium Hydroxide Tank BST-2 Was Erratic & Displaying Incorrect Indication.Caused by Water in Sensing Lines. Engineering Investigation Is Being Conducted + (ML19343B421)
- 05000302/LER-1980-047, Forwards LER 80-047/04L-0 + (ML19343B422)
- ML19343B423 + (ML19343B423)
- 05000334/LER-1980-110, Forwards LER 80-110/03L-0 + (ML19343B424)
- ML19343B425 + (ML19343B425)
- 05000334/LER-1980-110-03, /03L-0:on 801201,charcoal Test Cell in 1B Main Filter Bank Found Passing Flow Over Tech Spec Limit.Caused by Workmen Error in Not Replacing Cell in June 1980.Cell Replaced + (ML19343B426)
- 05000302/LER-1980-047-04, /04L-0:on 801118,difference of More than Two Std Units Discovered Between Preop Study & Operational Study in Metabolic Function of Discharge Salt Marshes.Possibly Caused by Plant Thermal Output or Natural Phenomena + (ML19343B427)
- 05000302/LER-1980-049, Forwards LER 80-049/03L-0 + (ML19343B428)
- ML19343B429 + (ML19343B429)
- 05000302/LER-1980-049-03, /03L-0:on 801119,containment Isolation Valve CFV-12 Would Not Close After Bubbling Nitrogen to CFT-1B. Caused by Broken Can in Torque Switch.New Switch Installed & Adjusted + (ML19343B430)
- 05000336/LER-1980-039, Forwards LER 80-039/03L-0 + (ML19343B431)
- ML19343B432 + (ML19343B432)
- ML19343B433 + (ML19343B433)
- 05000336/LER-1980-039-03, /03L-0:on 801117,hydrogen Analyzer B Declared Inoperable.Caused by Failure of Operational Analyzer Amplifier (Struthers-Dunn,Inc,Model 12A).Malfunction Isolated,Corrected & Surveillance Completed + (ML19343B434)
- 05000320/LER-1980-053, Forwards LER 80-053/01L-0 + (ML19343B435)
- 05000320/LER-1980-053-03, /03L-0:on 801117,incore Thermocouples N-8 & N-9 Exhibited Erratic Behavior.Cause Undetermined.Situation Being Evaluated + (ML19343B437)
- ML19343B438 + (ML19343B438)
- ML19343B439 + (ML19343B439)
- ML19343B440 + (ML19343B440)
- ML19343B442 + (ML19343B442)
- ML19343B443 + (ML19343B443)
- ML19343B444 + (ML19343B444)
- ML19343B445 + (ML19343B445)
- ML19343B446 + (ML19343B446)
- ML19343B447 + (ML19343B447)
- ML19343B448 + (ML19343B448)
- ML19343B449 + (ML19343B449)
- ML19343B450 + (ML19343B450)
- ML19343B452 + (ML19343B452)
- ML19343B454 + (ML19343B454)
- IR 05000483/1980026 + (ML19343B455)
- ML19343B456 + (ML19343B456)
- IR 05000313/1980017 + (ML19343B458)
- ML19343B460 + (ML19343B460)