- 05000267/LER-1980-076-03, /03L-0:on 801216,results of Lab Carbon Sample Analysis of 1A Reactor Plant Exhaust Filter Showed Less Radioactive Methyl Iodine Removal Capability than Required. Caused by Normal Depletion of Activated Charcoal Adsorber + (ML19341A239)
- 05000346/LER-1980-092, Forwards LER 80-092/03L-0 + (ML19341A240)
- ML19341A241 + (ML19341A241)
- ML19341A242 + (ML19341A242)
- IR 05000348/1980035 + (ML19341A243)
- 05000346/LER-1980-092-03, /03L-0:on 801219,isolation Valve from Main Steam Line to Auxiliary Feed Pump Turbine Failed to Close W/Simulated Low Pressure.Caused by Failed Couch Relay R1. New Relay Installed + (ML19341A244)
- ML19341A245 + (ML19341A245)
- 05000346/LER-1980-093, Forwards LER 80-093/03L-0 + (ML19341A246)
- ML19341A247 + (ML19341A247)
- 05000346/LER-1980-093-03, /03L-0:on 801219,demineralized Water Containment Isolation Valve DW6831B Did Not Close in Required Time. Caused by Dump Solenoid Orifice Too Small to Allow Adequate Bleedoff Flow.Solenoid to Be Replaced + (ML19341A248)
- 05000338/LER-1981-002, Forwards LER 81-002/03L-0 + (ML19341A249)
- ML19341A250 + (ML19341A250)
- 05000338/LER-1981-002-03, /03L-0:on 801231,pressurizer Power Operated Relief Valve Declared Inoperable Because of Low Nitrogen Gas Supply Tank Pressure in 1-GN-TK-1A.Caused by Excessive Usage of Nitrogen to Cycle Relief Valves to Reduce RCS Pressure + (ML19341A251)
- 05000271/LER-1980-043, Forwards LER 80-043/03L-0 + (ML19341A252)
- ML19341A253 + (ML19341A253)
- 05000271/LER-1980-043-03, /03L-0:on 801220,reactor Core Isolation Cooling Valve 15 Had Seat Leakage of 1.531 Lbm/Hr,Exceeding Tech Specs.No Cause Noted.Valve Seating Surfaces Lapped & Valve Retested + (ML19341A254)
- 05000278/LER-1980-031-03, /03L-0:on 801218,reactor Core Isolation Cooling Inboard Steam Supply Isolation Valve Did Not Automatically Close.Caused by Valve Closing Torque Switch on Type Smb Limitorque Operator for Valve MO3-13-15 Being Open + (ML19341A255)
- AECM-80-268, Submits Addl Info Re IE Bulletin 80-07, BWR Jet Pump Assembly Failure, in Response to NRC Request.Describes Actions to Preclude Occurrence of Jet Pump Cracking & Commitment for long-term Solution + (ML19341A256)
- 05000277/LER-1980-037, Forwards LER 80-037/01T-0 + (ML19341A257)
- ML19341A258 + (ML19341A258)
- ML19341A259 + (ML19341A259)
- 05000277/LER-1980-037-01, /01T-0:on 801230,during Subcritical Reactor Cooldown,Max Cooldown Rate Exceeded by 2 F.Caused by Operator Error.Allowable Cooldown Rate Established & Operator Counseled + (ML19341A260)
- ML19341A261 + (ML19341A261)
- 05000277/LER-1981-001, Forwards LER 81-001/04T-0 + (ML19341A262)
- ML19341A263 + (ML19341A263)
- 05000277/LER-1981-001-04, /04T-0:on 801019,max Daily Chlorination Time Limit Exceeded by 30 Minutes.Caused by Personnel Error. Instructions Posted at Chlorination Control Panel,Procedure Clarified & Individual Reinstructed + (ML19341A265)
- ML19341A266 + (ML19341A266)
- 05000327/LER-1980-204, Forwards LER 80-204/03L-0 + (ML19341A267)
- ML19341A268 + (ML19341A268)
- ML19341A269 + (ML19341A269)
- ML19341A270 + (ML19341A270)
- ML19341A271 + (ML19341A271)
- 05000327/LER-1980-204-03, /03L-0:on 801216,axial Flux Difference Was Out of Target Band Longer than 1-h.Caused by Rod Stepping to Maintain Power & Blocked Borate Paths Due to Low Heat Trace Setting.Notice to Maintain Temp at 200 F Put on Control + (ML19341A272)
- 05000327/LER-1980-203, Forwards LER 80-203/03L-0 + (ML19341A273)
- ML19341A274 + (ML19341A274)
- ML19341A275 + (ML19341A275)
- ML19341A276 + (ML19341A276)
- 05000327/LER-1980-203-03, /03L-0:on 801216,during Ice Condenser Insp, Intermediate Deck Door Under AHU-3A Found Frozen Shut. Caused by AHU-3A Drain Line Flange Leaking.Ice Removed from Door,Flange Gasket Replaced & Leakage Stopped + (ML19341A277)
- ML19341A278 + (ML19341A278)
- ML19341A279 + (ML19341A279)
- 05000327/LER-1980-200, Forwards LER 80-200/03L-0 + (ML19341A281)
- ML19341A282 + (ML19341A282)
- ML19341A283 + (ML19341A283)
- ML19341A284 + (ML19341A284)
- ML19341A286 + (ML19341A286)
- 05000327/LER-1980-200-03, /03L-0:on 801217,valves 1-FCV-1-15,16 & 17 Found Not to Have Been Stroke Tested After Repacking on 801209. Caused by Engineer & Craft Failure to Notify Proper Personnel.Valves Tested & Personnel Instructed + (ML19341A287)