- ML19341A210 + (ML19341A210)
- 05000318/LER-1980-052-03, /03L-0:on 801103,CTMT Penetration Room Exhaust Fan Discharge Damper 22 Linkage Was Found Broken.Caused by Excessive Wear on Clevis Pin Due to Inadequate Lubrication. Linkage Repaired & Restored to Svc on 801104 + (ML19341A211)
- ML19341A212 + (ML19341A212)
- 05000334/LER-1980-118-03, /03L-0:on 801217,during Chlorine Detection Sys Surveillance test,101A,B & C Detectors Electrolyte Found Not Dripping.Caused by Vacuums in Fluid Tanks & Clogged Glass Orifices.Wicks Replaced & Orifices Cleaned + (ML19341A213)
- 05000325/LER-1980-092, Forwards LER 80-092/03L-0 + (ML19341A214)
- ML19341A215 + (ML19341A215)
- 05000325/LER-1980-092-03, /03L-0:on 801220,reactor Vessel Conductivity Measured Over Tech Spec Level.Caused by Removal of Reactor Water Cleanup Sys from Svc for Valve Maint.Valves Repaired & Sys Returned to Svc + (ML19341A216)
- ML19341A217 + (ML19341A217)
- 05000325/LER-1981-001, Forwards LER 81-001/01T-0 + (ML19341A218)
- ML19341A219 + (ML19341A219)
- 05000325/LER-1981-001-01, /01T-0:on 810103,feed Pump Tripped on High Vessel Level Due to safety-relief Valve B21-F013G,Model 67F,lift. Caused by High Second Stage & Pilot Leakage in Valve.Pilot Valve Temporarily Replaced Until Next Scheduled Outage + (ML19341A220)
- ML19341A221 + (ML19341A221)
- ML19341A222 + (ML19341A222)
- ML19341A223 + (ML19341A223)
- 05000324/LER-1980-115, Forwards LER 80-115/03L-0 + (ML19341A224)
- ML19341A225 + (ML19341A225)
- ML19341A226 + (ML19341A226)
- 05000324/LER-1980-115-03, /03L-0:on 801222,reactor Vessel Conductivity, Exceeded 2 umho/cm2 for 27.3-h W/Highest Measured Value at 3.35 umho/cm2.Caused by High Conductivity Condensate in Heater Drains Sys Being Concentrated in Vessel + (ML19341A228)
- ML19341A229 + (ML19341A229)
- ML19341A230 + (ML19341A230)
- 05000267/LER-1980-076, Forwards LER 80-076/03L-0 + (ML19341A231)
- ML19341A232 + (ML19341A232)
- ML19341A233 + (ML19341A233)
- ML19341A234 + (ML19341A234)
- ML19341A235 + (ML19341A235)
- ML19341A236 + (ML19341A236)
- ML19341A238 + (ML19341A238)
- 05000267/LER-1980-076-03, /03L-0:on 801216,results of Lab Carbon Sample Analysis of 1A Reactor Plant Exhaust Filter Showed Less Radioactive Methyl Iodine Removal Capability than Required. Caused by Normal Depletion of Activated Charcoal Adsorber + (ML19341A239)
- 05000346/LER-1980-092, Forwards LER 80-092/03L-0 + (ML19341A240)
- ML19341A241 + (ML19341A241)
- ML19341A242 + (ML19341A242)
- IR 05000348/1980035 + (ML19341A243)
- 05000346/LER-1980-092-03, /03L-0:on 801219,isolation Valve from Main Steam Line to Auxiliary Feed Pump Turbine Failed to Close W/Simulated Low Pressure.Caused by Failed Couch Relay R1. New Relay Installed + (ML19341A244)
- ML19341A245 + (ML19341A245)
- 05000346/LER-1980-093, Forwards LER 80-093/03L-0 + (ML19341A246)
- ML19341A247 + (ML19341A247)
- 05000346/LER-1980-093-03, /03L-0:on 801219,demineralized Water Containment Isolation Valve DW6831B Did Not Close in Required Time. Caused by Dump Solenoid Orifice Too Small to Allow Adequate Bleedoff Flow.Solenoid to Be Replaced + (ML19341A248)
- 05000338/LER-1981-002, Forwards LER 81-002/03L-0 + (ML19341A249)
- ML19341A250 + (ML19341A250)
- 05000338/LER-1981-002-03, /03L-0:on 801231,pressurizer Power Operated Relief Valve Declared Inoperable Because of Low Nitrogen Gas Supply Tank Pressure in 1-GN-TK-1A.Caused by Excessive Usage of Nitrogen to Cycle Relief Valves to Reduce RCS Pressure + (ML19341A251)
- 05000271/LER-1980-043, Forwards LER 80-043/03L-0 + (ML19341A252)
- ML19341A253 + (ML19341A253)
- 05000271/LER-1980-043-03, /03L-0:on 801220,reactor Core Isolation Cooling Valve 15 Had Seat Leakage of 1.531 Lbm/Hr,Exceeding Tech Specs.No Cause Noted.Valve Seating Surfaces Lapped & Valve Retested + (ML19341A254)
- 05000278/LER-1980-031-03, /03L-0:on 801218,reactor Core Isolation Cooling Inboard Steam Supply Isolation Valve Did Not Automatically Close.Caused by Valve Closing Torque Switch on Type Smb Limitorque Operator for Valve MO3-13-15 Being Open + (ML19341A255)
- AECM-80-268, Submits Addl Info Re IE Bulletin 80-07, BWR Jet Pump Assembly Failure, in Response to NRC Request.Describes Actions to Preclude Occurrence of Jet Pump Cracking & Commitment for long-term Solution + (ML19341A256)
- 05000277/LER-1980-037, Forwards LER 80-037/01T-0 + (ML19341A257)
- ML19341A258 + (ML19341A258)
- ML19341A259 + (ML19341A259)
- 05000277/LER-1980-037-01, /01T-0:on 801230,during Subcritical Reactor Cooldown,Max Cooldown Rate Exceeded by 2 F.Caused by Operator Error.Allowable Cooldown Rate Established & Operator Counseled + (ML19341A260)
- ML19341A261 + (ML19341A261)
- 05000277/LER-1981-001, Forwards LER 81-001/04T-0 + (ML19341A262)