ML19341A212

From kanterella
Jump to navigation Jump to search
QA Program for Meteorological Monitoring Programs, Revision 2
ML19341A212
Person / Time
Site: Dresden 
Issue date: 12/05/1979
From: Jenny Murray
MURRAY & TRETTEL, INC.
To:
Shared Package
ML17193A624 List:
References
NUDOCS 8101220391
Download: ML19341A212 (34)


Text

i.

5 December 1979 Revision 2 i

Quality Assurance Program for Meteorological Moni toring Programs Prepared by MURRAY AND TRETTEL, INCORPORATED Northfield, IL 60093 26 July 1976 Controlled Distribution No.

o 810122039[

L J

u irr,v ana r,..,a in-c.,, m.a c, -..... : ~, u,...-i :-. -

o e

i 26 July 13/6 Revision 0 TABLE OF CONTENTS Page Foreword......................................

1 lntroduction..................................

2 l

1 Organization.

..................... 3 2

Quality Assurance Program...................

7 3

Instr.uctions, Procedures and Drawings........

8 h

Do c ume n t Co n t ro l * * * * * * * * * *.. * * * *. *

  • e

=.. *... 9 5

inspection

.................... 10 6

Equipment Calibration

.......... 11 7

Control of Measuring and Testing Equipment....12 8

Inspec t ion and Tes t S ta t us.................... 13 9

Corrective Action............................. 14 10 Quality Assurance Records..................... 15 ^

11 Audits *........................................ 16 I

i i

1 t

l 1

M U R R A Y ao T R E T T E L,

.d c.

CEatofeED C O N '. U n 1 a fd G 11 4 f l O M f8 8 4 *. s h 3 5

e o

1 Foreword This is Murray and Trettel's Quality Assurance Program which describes the requirements that must be implemented in connection with the Commonwealth Edison Company meteorological monitoring programs.

The report is divided into eleven (11) sections conforming in format to eleven (11) criteria specified in Appendix Three to the " Specifications For 1977-78 Meteorological Monitoring Service and Maintenance", April 1976, Revision 2.

The contents of this report are to be considered as Murray and Trettel policy and, as such, are to be followed by all employees to the extent of their involvement in the monitoring program, k.

f John R. Murray, B.F., J.D.

Certified Consulting Meteorologist President i

22 July 1976 l

M U R R A Y A N O T R E T T E L.

,ue Cfatafa1D COh5utTomG sit tt 0 h 4 L o u e5 1 5

26 July 1976 2

Revision 0 Introduction This report has been prepared to delineate the requirements governing the Murray and Trettel Quality Assurance Program for meteorological monitoring programs.

Implementation of the monitoring program with detailed procedures provides the degree of quality assurance commensurate with the requirements of applicable codes and requirements of agencies which govern the installation and operation of meteorological monitoring equipment, and the handling, reduction and processing of data.

The scope of this report covers the total Quality Assurance Program for the life of the monitoring program.

M U R R A Y a~o T R E T T E L.

.=c CEateretD CON $ue isNG ut s(onotOGsS*5

l 4

0 3

26 July 1976 Revision 0 1.

Or g.in i /a t ion Murray and Trettel, incorporated is responsible for the assurance of quality in all phases of the acquisition, reduction, and analysis of meteorological monitoring data.

Murray and Trettel executes this respon-sibility in accordance with the program described herein and assigns areas of ultimate responsibility to specific individuals.

Lines of authority and responsibility for the Quality Assurance Program are documented in the form of an organization chart.

Key quality assurance positions including those providing technical support or audit responsibility are described. The organization chart for the meteorological monitoring program is shown in Figure 1.

Solid lines represent responsibility for implementing the procedures and instructions.

Dashed lines 'epresent audit responsibility for verifying compliance r

with the procedures and instructions. The Quality Assurance Office acts independently of the person or group directly responsible for performing the activites of the meteorological program.

The specific responsibility for the Quality Assurance Program are described in the following paragraphs.

Executive Vice President The Executive Vice President of Murray and Trettel has the overall responsibility for the Quality Assurance (QA) of the meteorological monitoring programs. The development of quality assurance policy for j

environmental studies is under his jurisdiction.

1 i

M U R R A Y

  • ~ o T R E T T E L.

inc ceafeFatD CON 5ut 14 %G tt i YtCH6 LOGE: fS

T W

x l

i f

p f

u a

o t

r S

h G

c g

e s

n T.i h s i

s t cy s

eel e

HTa n

c n

o o

rtA i

s r

oe t

n P

iHr a

t o

n e

z s

a e

t i

i i

t t

S u

n g

a p

a a

o t c l

D m

g n!

r o

o r

el e

r C

O d p g

o p

a e

s i

sA n

m t

e a

e a

rl M

M r

l P a l

g I

t t

o l

en c

a r

ce e

t P

m j

n i

V n o

e g

o r

m n

r P

n f

i i

r v

o f

r o

n a

t i

E t

i v

S hh n

n cc o

E s

ee M

n TT

~

o l

i s

a t

ct c

a n

i i

r ne g

e om o

p r u l

O t r o

ct r

~~

d es o

n e

l l

e EI t

i e

F M

tne d

d e

i t

se a

~~

r r

o P

pr o

cn i

l e

t t

er

~

T d

t r

n n

e a

e c

d i

y i

f a

s f

r e

O r

r u

P e

M c

e n

c a

r 1

l i

V us e

e s

r v

A u

i g

t y

i u

t F

c i

e l

x a

E u

,(

Q i

i l

S 5 Cec- 'ber 1979 5

Fevisisn 2 Quality Assurance Officer Authority and responsibility to conduct periodic audit s is assigned by the Executive Vice President to the Qua;!ty Assura nce Officer.

He reports directly to the Exectulve Vice President in all matters involving quality assurance, and is Independent of the normal operation of the meteorological monitoring programs except for matter s involving quality assurance.

The Quality Assurance Officer is responsible for c onducting audits and inspections, detecting deficiencies in the pro cedures, and recommending improvements in the procedures if defici encies are discovered.

Vice President, Environmental Applications The Vice President, Environmental Applications is res ponsible for all environmental projects, including the meteorological mo i n toring programs.

The Vice President, Environmental Applications is also responsible fo the training of personnel involved -in the progr r

am, and for approving all procedures and manuals used in the program Project Manager The Project Manager has the overall direct respo nsibility for the monitoring program.

He is responsible for providing technical assista assigning time tables, setting priorities and the day t

nce, i

i o-day decisions required by the project.

He is also responsible for the preparation of procedures to assure data validity, I

i t

~~

L J

Murrayand TrettelInc.

N""- d " -

6 26 July 1976 Revision 0 Environmental Meteorologist The Environmental Meteorologist is responsible for the day-to-day operation of the project, and for providing technical assistance and training to the technicians. The duties also include inspection of charts and records of project documents for completeness, final editing of the data record and preparation of monthly, semi-annual and other miscellaneous related reports.

Data Processing Staff The Data Processing Staff maintains project records, reviews strip charts, reduces data and performs other tasks related to the day-to-day operation of the program.

Field Operations Staff (Field Staff)

The Field Staff maintains the fleid equipment, performs in-situ / instrument calibrations, provides documentation of the performance of each system, maintains a spare parts inventory and maintains service instrumen'tation in proper calib~ ration.

8_.

M U R R A Y 4 = o TR E T TE L.

.~c c e i.,. c c, cos..c o t c r, -..... u. s. s

I O

7 26 July 1976 Ruision 0 2.

Quality Assurance Program The Quality Assurance Program at Murray and Trettel is approved by management and assures effective implementation of program procedures.

These procedures or instructions assure the monitoring program is conducted in compliance with the appropriate codes and program sper,1 fi ca t ions.

In general, the Quality Assurance Program verifies (through audits) that activities have been correctly performed.

Audit personnel are independent of the activities being audited.

Quality Assurance personnel have sufficient authority and organizational freedom to identify problems, to initiate, recommend or provide solutions, and to verify implementation of the solutions. Any disagree-ments on procedures are resolved through a review of the situation by the president of Murray and Trettel.

Regular reviews of the status of adequacy of the monitoring program are provided through a series of Inspections and audits conducted by the QA personnel. A controlled distribution list is set up and recepients of controlled documents will recieve any alterations or revisions. Tr'aining is provided to all new personnel, and to all personnel when new procedures are incorporated into the program.

Instruments are maintained by qualified personnel and the equipment used for the calibration of the meteorological systems are themselves calibrated on a routine basis.

I i

l M U R R A Y a=o T R E T T E L,

i~c l

i e t..... c.

c o s u i.~ c.

iso-n. %. sis l

t

15 s' '

. < ?*

\\

  • 1 1

8 3.

Instructions, Procedures and Drawings A set of procedures for meteorological monitoring programs has been prepared for use by all personnel involved with the program 1 These procedures contain instructions, specifications, and check lints that i

i cover al.1 phases of the monitoring program from the censing of tfic meteorological data to its final verification, analysis and storage.

The procedures manual is maintained by the Project Manager.

All persons having registered copies of the manual receive revisions as they are approved and imple:aanted.

All revisions to the procedures manual are approved by CECO before being implemented by Murray and Trettel per sonnel, i

e.

I t

i t

4 l

l 1

.*oteorological ::enitoring Progrc.t.:

Equip unt Carv;eing and rv i Facovery Procedures. A controlled doctavnt I;o. 1C94 da ted 7/79.

t_.

s q,-

dd__

t.turray and Tretter inc.

corrified censur:ing Mercerorogists

i o

9 26 July 12/6 Revision 0 4.

Document Control A document control system is used to assure that documents such as procedures, specifications, maintenance forms and data handling forms are reviewed for accurracy and approved by authorized personnel.

Such documents are distributed to and used by the personnel responsible for their use.

Changes to these documents are handled similarly and are reviewed and approved by the same personnel that performed the criginal review and approval.

A master controlled distribution list is used to designate the recipients of the documents.

Each document recipient is responsible for insuring that only the latest authorized procedures are in use and void documents are so identified.

The Project Hanager is responsible for instituting the document control system for the project and the Environmental Meteorologist is responsible for assuring the necessary files, logs, and procedures are instituted and maintained in a neat and proper manner.

The Environmental Metdorologist is also respon'sible for assuring that those documents that are to be to the c,lient are prepared and transmitted in a timely manner.

sent Documents pertaining to the maintenance, calibration, and performance of equipnent are retained in a central filing system at Murray and Trettel.

i M U R R A Y 4 = o T R E T TE L,

inc cii.e.co co~susi.~c uciro.otoo. sis 1

10 26 July 1976 Revision 0 5

Inspection l

Inspections are carried out at all stages of the data acquisition, processing, and reporting to assure that all procedures are being followed in the correct manner.

The inspections are performed by personnel other than those who perform the task.

Documents that have been inspected are initiated or signed by the individual inspecting the document. An incomplete form is returned to the Individual responsible for it.

Corrections'are made before being initialed by the inspector.

Documents to be inspected are:

1) Weekly Visitation Logs
2) Bi-Monthly Routine Maintenance Forms
3) Emergency (Non-Routine) Maintenance Forms
4) Batches in-House
5) Batch Condition Sheets
6) Data Recovery and Equipment Status Report
7) Digiti'zer Tape Listing
8) Tape Explanation Sheet
9) Digitizing Record Sheet
10) Monthly Reports
11) Semi-Annual Reports d

M U R R A Y auo T R E T T E L,

.~c c i i... i t.

i. o u u t i.~c n i i s c - n i n,.. s r s

s 11 26 July 1976 Revision 0 6.

Equipment Calibration A testing program has been established to assure that the meteorological sensors, signal conditioners, and recorders are performing in the required manner.

Calibrations are conducted i

at specified Intervals by trained personnel.

In addition, calibra-tion of the equipment is performed whenever it has been repaired or whenever the quality assurance checks, made on the data, indir.ste that the system may not be performing up to specifications.

The test equipment used by Hurray and Trettel field personnel is calibrated at routine intervals.

Electronic test equipment is calibrated and certified by the manufacturer and thermometers calibrated in house by qualified technicians.

are To assure that all of the required tests and calibrations are performed, specific forms have been developed for each site.

These forms serve to remind the technician of the required tests, to document the results of the tests and to indicate any problems encountered in the procedure. The acceptable tolerances for each test are provided on the form to assure all calibrations are within acceptable limits.

The calibrated systems are affixed with a sticker indicating the date of calibration, the initials of the technician who performed the work, and the date of the forth-coming calibration.

M U R R A Y 4 ~ o T R E T T E L.

.*c Ct& -of840 C O N 5 u s i n te c t.it it O M O L O G s5 1 5

a I r, or.

r li t

"3 lu;n 12 t

7.

Control of 14easuring and_ Tc. sting Ecuipment The elctronic instruments and thermometerc used to calibrate the meteorological systems are themselves calibrated at routine intervals.

This assures that these itens are maintair.ed within weeptablo limits of accuracy.

Electronic instrumentation is calibrated once each year by the manufacturer in such a manner that the results can be traced to the Itational Bureau of Standards. T'1ese results are certified by the manufacturer and a calibration late 1 is affixed to the instrument.

The label states the date of the calibration and date the next calibration is due.

Thermometers are calibrated at I.!urray and Trettel by trained personnel.

A water bath and 'a precision thermometer, whose calibration is traceaMe to the riational Bureau of Standards, are used in the calibration procedure.

An eight point calibration is performed quarterly on each thermometer and the results are documented. 1:ew thermometers are calibrated before use in the field.

d s

(_3

}

t l

L J

i

_I-Murray and Trottel lac. Cerlified Consu!!ing Meteorologists

+

13 26 July 1376 Revision 0 8.

Inspection and Test Results The status of inspection and tests performed on items furnished as part of the program is indicated by means of labels affixed to the items. All instrumentation used in the calibration of the meteorological system have calibration labels Indicating when they were last calibrated, and the date their next calibration is due.

Each time the system is calibrated, a calibration label is affixed.

to the system by the field service personnel.

This label indicates-the date of the calibration, the personnel who performed the call-bration, and the date the next calibration is due.

i 4

t l

l 1

M U R R A Y a~o T R E TT E L,

..c CEmisF8(D CON:ut IeNG **fIfOmot04 elf 5

r 14 26 July 1976 Revision 0

9. Corrective Actior.

A series nf on-site visits, checks, and a weekly review of the strip charts provide several means of detecting problems at an early stage.

Procedures have been developed to identify.promptly any problems in the data base. When defective equipment is identified as the problem

~

~

source, field service personnel are notified and a site visit is scheduled to correct the problem.

It is not possible to eliminate all data loss from the meteorological systems, but it is possible to minimize the loss through quick detection of the problem.

The cause of each problem is identified and documented in the routine course of the project. When appilcable, recommendations of modifications to instrumentation or procedures are made in order to eliminate or minimize the loss of data.

M U R R A Y A N u T R E T T E L,

.9c c i a... e c, c o

.. i. u u t i i r.. < t.........

T e

15 26 July I' /6 Revision 0

10. Quality Assurance Records Records are maintained to furnish evidence of activities affecting the quality of the data collected by the monitoring programs. All records

'of site visits, routine maintenance, exceptional maintenance, data i

review, and progress reports are retained as part of the quality assurance program.

The timely submission of the reports required by the program specifi-cation is assured by the routine inspection and processing of the data within one month of the date collected.

All quality assurance records are identifiable and retrievable.

Notification will be given to CECO prior to disposing of these records and disposal will not be allowed until permission from CECO is j

obtained. All quality assurance records are maintained in accordance with applicable codes regarding record retention.

l

\\

i

(

M U R R A Y auo T R E T T E L.

.~c c

i.e.,o caso..c

...irc,

.s.5

16 26.!uly 1976 P.evision 0

11. Audits Audits are performed by Murray and Trettei personnel who are not involved in the day-to-day operation and management of the project.

The audits verify the Implementation and effectiveness of the monitoring program.

Audits cover maintenance and calibration of tower acquisition systems, data handling, and data reduction.

Procedures and inspections of records are included in the audit.

The audits are conducted twice each year by the Quality Assurance Officer using checklists or an agenda approved by the Executive Vice President.

A report is written af ter each audit and consists of the following:

a Su-ary Sheet, Check 1ists or agenda, and any additional pertinent details recorded on additional sheets necessary to support the findings.

This report is submitted to the Executive Vice President for review and is retained as a part of the quality assurance documentation.

A follow up review of deficient areas or adverse conditions and on corrective action commitments, is carried out to assure effective implementation.

Deficiencies in the execution or implementation of corrective action are brought to the attention of the person responsible for their recti-fication.

Continued deficiencies or failure to I. ale ent carrecti.e action are reported, in writing, to appropriate executives within Murray and Trettel.

M U R R A Y 4 co T R E T T E L.

. r. c c..vi..so c o s u..

c.

o r i,. - r.

.... s i s

Rsvision 1 July 1980 Commonwealth Edison Company Quality Articles for Meteorological Monitoring Section I - Quality Assurance 1.0 Quality Assurance Program:

1.1 The contractor shall be required to have an acceptable Quality Assurance Program which will be in effect for the duration of the contract.- The Quality Assurance Pregram shall include the quality assurance system, organization, policies, responsibilities, listing of procedures and/or requirements for processes necessary to control quality throughout all phases of the contract.

This program shall meet the applicable requirements of 10CFR50, Appendix B and must address the requirements delineated in Article 50, " Acceptance Criteria".

Acceptable guides for meeting the applicable requirements are ANSI N 45 2, " Quality Assurance Requirements for Nuclear Power Plants", and applicable associated ANSI N 45 2 daughter documents.

The program must be accepted by the purchaser prior to award of con-tract.

2.0 Quality Assurance Program Approval:

2.1 Before any contractor can be considered acceptable for an award of contract, he must have submitted an acceptable j

1 l

Quality Assurance Program.

In order to be considered as acceptable, the program must address, as applicable, the Page 1 of 16

R vision 1 July 1980 requirements delineated in Article 1.0 above.

2.2 If the contractor's program does not cover all of the requirements in detail, he must state when and how the requirements do not apply.

This statement of non-applicability must be substantiated.

23 Commitments accepted by the purchaser as a condition of award shall be implemented by the contractor immediately upon award of contract.

These commitments shall require the contractor to make written changes to the program in the form of revisions or supplements to the program.

The supplement shall be controlled in the same manner as the manual, and considered as a auditable part of the program.

2.4 The control of the accepted Quality Assurance Program is the responsibility of the contractor.

Contractor shall promptly notify the purchaser of all revisions to the Quality Assurance Program for the duration of the contract.

Nio, revisions to the accepted Quality Assurance Program shall be implemented on the purchaser's work by the con-tractor without the purchaser's written approval of the Program revision.

30 Quality Assurance Program Submittal with Proposal:

31 A contractor who has written acceptance by the purchaser and a controlled copy of the accepted Quality Assurance Program assigned to the Manager of Quality Assurance, Commonwealth Edison Company, need only submit documented Page 2 of 16

-Ravision 1 July 1980 verification that the controlled copy is applicable to the scope of work involved in the bid, and include information with the proposal covering the current effective date of the program manual, including all current revisions and supplements in effect.

32 A contractor who does not have an accepted and controlled copy of his Quality Assurance Program as described in Article 3 1 above shall submit to the purchaser with his bid two (2) controlled copies of his Quality Assurance Program for review and acceptance, one assigned to the Manager of Quality Assurance and the other assigned to the Nuclear Stations Division Manager.

4.0 Quality Assurance Program Submittal After Award:

4.1 After award, if the contractor meets the requirements of 3 2 above, he must submit three (3) uncontrolled copies of the accepted Quality Assurs

'e Program to the purchaser.

4.2 After award, if the contractor meets the requirements of 3 1 above, the contractor must submit four (4) copies of the accepted Quality Assurance Program.

One (1) copy must be controlled, and will be assigned to a designated individual in the Nuclear Stations Division; the three (3) remaining shall be uncontrolled.

4.3 After award, if contract is for more than one station, the contractor must submit two (2) additional uncontrolled copies for each additional station.

Page 3 of 16

Ravision 1 July 1980 4.4 After award, any revisions to the accepted quality assurance program which the purchaser approves, the contractor must submit copies of the accepted revisions for the uncontrolled and controlled manuals in the purchaser's possession for the duration of the contract.

50 Quality Assurance Program Acceptance Criteria:

51 organization:

A.

The contractor's Quality Assurance Program shall in-clude an organization chart identifying key positions and the reporting relationship between the Quality personnel and management (including field Q.A.

organization, if applicable).

All quality related activities which are referenced in the manual must be assigned to specific personnel.

The Quality Assurance personnel shall have:

1.

Written responsibilities for quality related job positions.

2.

Authority and organizational freedom to:

a.

identify and evaluate problems b.

require and implement approved corrective actions c.

control further activities where appropriate action such as "stop work" may be required.

3 Independence from groups involved in design and/

or operation of the system, computer programming, data processing system design / modification.

Page 4 of 16 4

Rsvision 1 July 1980 52 Quality Assurance Program:

A.

The contractor's Quality Assurance Program must be formally accepted by Company Management with a written policy statement.

This Program shall be implemented through written procedures and/or in-structions or they shall be established to ensure that the subject's work is accomplished in com-pliance with the appropriate code and procurement requirements.

B.

Provisions for training Quality Assurance personnel performing activities affecting quality shall be a part of the program.

These provisions must in-clude how this training is accomplished and who is responsible for its implementation.

C.

Provisions for a review of the status, adequacy, im-plementation and effectiveness of the total Quality Assurance Program on a specific time schedule shall be a part of the Program.

D.

Provisions shall be established in the Program for the controlled issuance of the latest revision to the quality assurance manual, procedures and in-structions.

E.

Includedin the Program is a commitment that the program complies with applicable portions of 10 CFR 50 Appendix B and/or ANSI N 45 2.

F.

The Program shall delegate responsible individual (s) to sign off on Certificates of Conformance and/or Page 5 of 16

Revision 1 July 1980 Compliance 53 Design Control:

A.

Measures to assure that the design basis for the systems and/or components are correctly translated into specifications, drawings, procedures, and instructions as appropriate, shall be described.

These measures shall include provisions to insure that appropriate quality standards are specified and included in design documents.

B.

The design control measures for independent veri-fication or check of the adequacy of design, such as by the performance of design reviews, by the use of alternate or simplified calculational methods, or by the performance of a suitable testing program shall be described.

C.

Means by which the contractor will insure that de-sign changes are subjected to design control measures commensurate with those applied to the original de-sign shall be described.

5.4 Procurement Document Control:

A.

Measures to assure that purchase docume':ts for procurement of material, equipment, and services, whether purchased by the contractor or by a sub-contractor performing a significant portion of the actual services, are reviewed for inclusion of quality requirements shall be described in the Program.

Page 6 of 16

Revision 1 July 1980 Subcontractors who perform a significant portion of the service shall be required to provide to the contractor a Quality Assurance Program consis-tant with the requirements of the contractor's Q.A.

program for review and acceptance by the contractor.

The contractor will be responsible for determining the Quality Assurance requirements to be applied to any subcontractor who performs a.significant portion of the actual services.

55 Instructions, Procedures and Drawings:

A.

Activities affecting quality shall be prescribed by documented work procedures or instructions, as appro-priate, and accomplished in accordance with these documents.

Procedures or instructions shall include appropriate acceptance criteria fbr work performance and quality c('.

Lance.

The above measures shall be described in t1 7 gram.

5.6 Document Control:

^

A.

Measures to control the issuance of the latest appli-cable documents such as instructions, procedures, drawings, purchase requirements and confirmatory docu-ments such as test reports, including changes thereto, which prescribe activities affecting quality shall be described.

These measures shall assure that documents including changes are reviewed for adequacy and appro-val for release by authorized personnel and are dis-tributed to and used at locations where the prescribed Page 7 of 16

r e

Revision 1 July 1980 activity is performed; and shall assure that obsolete drawings, specifications and instructions have been destroyed or isolated from use.

57 Control of Purchased Material, Equipment and Services:

A.

Measures to assure that purchased material, equip-ment and services, whether purchased directly or through subcontractors, conform to the procurement documents shall be described.

These mestares shall include provisions, as appropriate, for source evaluation and selection, objective evidence of quality furnished by contractor or subcontractor, inspection at the contractor or subcontractor source, and receiving inspection for compliance with pro-curement documents upon delivery.

The effectiveness of Quality Control by contractor, or by subcontractors who perform a significant portion of the actual services, may be assessed by purchaser or his de-signee at intervals appropriate to the importance, complexity, and quantity of the activities being performed.

58 Inspections:

A.

The inspection program for acti ities affecting quality that is established e.nd axecuted by or for the contractor and his subcontractors to verify conformance with documented instructions procedures, and drawings shall be described.

Such inspection shall be performed by qualified personnel, with Page 8 of 16

Rsvision 1 July 1980 certification as required, other than those who perform the activities being inspected.

The program shall identify the person responsible for the training, documentation of this training, and maintenance of the training records.

B.

There shall be provisions in the Program for es-tablishing, after award of contract, inspection, by the customer or by other as directed by Edison, of any activities or facilities utilized in the performance of these services by the contractor or significant subcontractors.

C.

The Program shall have provisions for documenting and retaining all inspection results:

59 Test control:

A.

A test program shall be established to insure that any bench or field testing required to demonstrate that the systems and/or components perform satis-factorily in service is performed by qualified

(

personnel, with certification as required, in accordance with written test procedures which in-corporate the requirement and acceptance criteria l

and limits contained in specifications.

Test procedures shall include provisions for assuring that all prerequisites for the given test have been met, that adequate and calibrated test instrumentation is available and used, and that the test is performed under appropriate environmental conditions.

Page 9 of 16

~

Rsvision 1 July 1980 B.

The Program shall have provisions for documenting, evaluating, and retaining all test results.

5 10 Control of Measuring and Test Equipment:

A.

Measures shall be established in the Program to assure that proper tools, gauges, instruments and other measuring and testing devices are used in activities affecting quality.

To assure accuracy the equipment shall be calibrated, adjusted and maintained at prescribed intervals or prior to use against certified equipment having known valid relationships to the National Bureau of Standards or other recognized applicable standards.

B.

Records shall be maintained and equipment suitably marked (such as tag, sticker, etching, etc.) to verify calibration status.

5 11 Handling, Storage and Shipping:

A.

Measures established to protect equipment being transported or in storage against damage or deterio-ration shall be described.

5 12 Nonconforming Materials, Parts or Components:

A.

Measures established to control materials, parts or components which do not conform to requirements in order to prevent their inadvertent use or installa-tion shall be described.

These measures shall in-clude procedures for identification, documentation, segregation and disposition.

5 13 Corrective Action:

A.

Measures shall be established to assure that conditions adverse to quality are promptly identified and Page 10 of 16

Revision 1 July 1980 corrscted.

The identification of the adversa con-ditions, the cause of such condition and the corrective action taken to prevent continuing recurrence of like conditions shall be documented and reported to appropriate levels of management and the customer.

5 14 Quality Assurance Records:

A.

Records shall be maintained to furnish evidence of activities affecting Quality.

The contractor shall establish measures that will assure prompt and com-plete delivery to the purchaser of any documents re-quired by the specification.

The contractor shall meet the requirements of applicable codes and ANSI Standards concerning record retention regarding identifiability and retrievability, duration of re-tention, location, and assigned responsibilities.

5 15 Audit:

A.

Measures established to provide a comprehensive program of planned and scheduled audits to be carried out to verify compliance with all aspects of the Program, and to determine the effectiveness of that Program, shall be described.

This plan shall in-clude both scheduled internal audits and, where appropriate, audits of subcontractors who perform a significant portion of actual services.

B.

The Program shall provide for audits to be conducted in accordance with written procedures and/or checklists by trained and certified audit personnel not having I

direct responsibilities in areas being audited.

A l

Page 11 of 16 l

Revision 1 July 1980 description shall be provided in the Program of Auditor training activities, with qualification and certification requirements.

This sh 11 include a description of training activities, a delegation of responsibilities for performance of these activities, and documentation of these activities.

C.

Audit results shall be documented with objective evidence, distributed, and an archival file shall be maintained.

The audit results shall be reviewed by management having responsibilities for the area being audited.

D.

Follow-up action, including re-audit of the deficient areas (s) to assure corrective action has been accom-plished, shall be described in Program.

Section II - Quality Control 1.0 Quality Control Document Submittal with Proposal A.

The contractor shall include with his proposal an index of Quality Control Procedures to be applied to the work.

B.

The contractor shall submit with his proposal for in-clusion into the contract awarded, a detailed list of the quality records and documentation regarding system operations and activities, other than those required by l

the specification, which will be furnished to, or avail-able for inspection by the purchaser.

Page 12 of 16 i

ggggmar i

~

^

R: vision 1 July 1980 2.0 Quality Control Document Submittal after Award:

2.1 Quality Control Procedures:

A.

Within six weeks after an award of contract, the con-tractor should submit the detailed procedures to be used or a schedule for submitting these procedures.

NOTE:

A contractor shall not start an'y work covered by these procedures until the appropriate procedures have been accepted in writing by the purchaser and/or the purchaser's consulting engineer as appropriate.

B.

The Quality Control Procedures shall contain those administrative procedures necessary to implement each l

Section- (5.1 through 515) of the Quality Assurance Program described above.

The procedures shall desig-nate who is responsible for the implementation by each of i

the departments stated in the Quality Assurance Program and define the authorities and duties of all personnel associated with quality control.

The procedures shall detail how all elements affecting the product quality will be processed and shall include the specification of the necessary documentation.

I C.

Quality Control Procedures shall also contain those design, testing, inspection, cleaning, etc., procedures necessary for the accomplishment of the work and to assure its proper quality.

Procedures shall be qualified as necessary to Code or Standard requirements.

These procedures shall detail what equipment is to be used, limiting conditions, acceptance criteria, techniques, etc., that will be used.

Page 13 of 16

N

_~

Revision 1 July 1980 2.2 Inspection Program:

A.

An inspection program shall be established by the contractor and shall include pertinent maintenance and inspection operations which will be of concern to the purchaser relative to Quality Control.

Contractor's recommend c&libration and maintenance program will be applied to the equipment, and documented in monthly reports.

Inspection programs shall be submitted to Nuclear Stations Division Manager or his designee.

NOTE:

1.

The contractor shall not start any work which requires an inspection program until the purchaser or the purchaser's consulting engineer has reviewed and accepted the program as appropriate.

B.

Purchaser and/or his designated representative shall have full access to contractor's and subcontractor's shops and field sites for reviewing progress and determining acceptability of Quality Control activities.

Nuclear Stations Division Manager or his designee shall be notified at least two (2) working days, excluding Saturdays and Sundays, prior to starting of specified installation, calibration, or test programs.

C.

Purchaser and/or his designated representative shall have full access to contractor's and subcontractor's shops for reviewing and auditing the implementation Page 14 of 16

o.

Revision 1 e

e July 1980 of its quality assurance program.

Any findings resulting from a contractor's/ subcontractor's audit shall be addressed and promptly corrected to the purchaser's satisfaction.

The audited organization shall provide a scheduled date for completion of corrective action.

f 2 3. Subcontractor Requirements:

A.

Contractor shall be responsible for the review, comment and acceptance of the Quality Assurance Program and Quality Control Procedures of the sub-contractor who performs a significant portion of actual services.

In addition, contractor shall be responsible for the subcontractor's work.

2.4 Nonconformance Report:

A.

Any nonconfonnance with purchase documents, approved drawings, procedures, or approved material selection shall be promptly reported in writing to the Purchaser.

25 Quality Control Records:

A.

Copies of all appropriate documentation as herein specified or as required by applicable Codes, Standards, or criteria, shall be submitted in monthly and semi-annual reports.

2.6 Certificate of Compliance /Conformance:

A.

Certificate of Compliance A Certificate of Compliance signed by a qualified party, attesting that the items or services are in Page 15 of 16

-3 RLvicion 1 7

July 1980 accordance with the customer's purchase order and specification, and accompanied kv all docu-mentation required by these articles to sub-stantiate that statement, is required upon commencement of the services contemplated by this contract.

27 Invoice Submittal:

A.

Invoices for equipment purchased for customer shall be sent to Nuclear Stations Division, Commonwealth Edison Company 2.8 Spare Parts:

A.

All requirements regarding Quality Control and docu-mentation that applied to the original parts of the specified equipment shall apply equally to the spare parts of the specified equipment.

Contractor shall identify those requirements in detail on spare parts quote.

m I

i l

Page 16 of 16 i

-