- A800438, Forwards Rept of Change to Physical Security Plan,Revision 9.Plan Withheld (Ref 10CFR2.790) + (ML19340B537)
- ML19340B538 + (ML19340B538)
- ML19340B539 + (ML19340B539)
- 05000346/LER-1980-075-03, /03L-0:on 801008,steam Generator Level Instrument to Steam & Feedwater Rupture Control Sys Cabinet Channel 3 Maintained 15-inch Error Over Entire Scale.Caused by Zero Shift in Transmitter.Transmitter Being Monitored + (ML19340B540)
- ML19340B543 + (ML19340B543)
- 05000346/LER-1980-076, Forwards LER 80-076/03L-0 + (ML19340B544)
- ML19340B545 + (ML19340B545)
- ML19340B546 + (ML19340B546)
- 05000346/LER-1980-076-03, /03L-0:on 801008,gross Back Leakage Observed Through Core Flood Valve 30.Caused by Disengagement of Disc Unit from Body Block.New Bolt Plates & Locking Plate Properly Installed + (ML19340B547)
- ML19340B550 + (ML19340B550)
- 05000368/LER-1980-005, Forwards Revised LER 80-005/03X-1 + (ML19340B552)
- ML19340B556 + (ML19340B556)
- 05000368/LER-1980-070, Forwards LER 80-070/03L-0 + (ML19340B557)
- ML19340B558 + (ML19340B558)
- 05000368/LER-1980-070-03, /03L-0:on 801005,control Room Emergency Chiller, 2VE-1B,was Found to Be Inoperable.Caused by Improper Pressure Switch Setting (80 Psig Rather than 150 Psig). Pressure Switch Calibr + (ML19340B560)
- ML19340B561 + (ML19340B561)
- 05000346/LER-1980-074, Forwards LER 80-074/03L-0 + (ML19340B563)
- ML19340B564 + (ML19340B564)
- 05000368/LER-1980-071, Forwards LER 80-071/03L-0 + (ML19340B565)
- ML19340B566 + (ML19340B566)
- ML19340B567 + (ML19340B567)
- 05000368/LER-1980-071-03, /03L-0:on 801006,wind Speed Indicator (WDR-9300) Was Found to Be Inoperable Per Tech Spec 3.3.3.4.Caused by Faulty Amplifier on Recorder.Amplifier Replaced & WDR-9300 Recalibr + (ML19340B568)
- 05000346/LER-1980-074-03, /03L-0:on 801008,test Frequency for Containment Air Lock Test Exceeded.Caused by Procedural Deficiency.Mods to Plant Procedures Made to Provide Assurance of Completing Required Testing + (ML19340B569)
- 05000271/LER-1980-035, Forwards LER 80-035/03L-0 + (ML19340B570)
- ML19340B571 + (ML19340B571)
- 05000346/LER-1980-066, Forwards LER 80-066/03L-1 + (ML19340B572)
- ML19340B573 + (ML19340B573)
- ML19340B574 + (ML19340B574)
- 05000271/LER-1980-035-03, /03L-0:on 801007,main Steam Relief Valves Had as-found Setpoint of 1,093 Psig,Exceeding Max Setpoint. Deviation Caused by Setpoint Drift.Valve Disassembled & Rebuilt & Setpoint Readjusted + (ML19340B575)
- 05000346/LER-1980-073, Forwards LER 80-073/03L-0 + (ML19340B576)
- ML19340B577 + (ML19340B577)
- 05000346/LER-1980-066-03, /03L-1:between 800829 & 0921,doors to Spent Fuel Pool Area Blocked Open on Nine Occasions.Caused by Personnel Error on Part of Const Workers.Two Memos Issued to Reinforce Special Order 88-1 Previously Issued + (ML19340B578)
- 05000302/LER-1980-042, Forwards LER 80-042/03L-0 + (ML19340B581)
- ML19340B582 + (ML19340B582)
- 05000346/LER-1980-073-03, /03L-0:on 801008,inner Door of Containment Personnel Lock Could Not Be Latched.Caused by Two Broken Camrol Cam Follower Bearings in Door Operating Mechanism Control Linkage.Broken Bearings Replaced + (ML19340B583)
- 05000302/LER-1980-042-03, /03L-0:on 801008,dose Equivalent I-131 Exceeded 1.0 Uci/G Creating Event Contrary to Tech Spec 3.4.8.Caused by Leaking Fuel Pins & Anticipated Iodine Transient Following RCS Transient.Purification Flow Increased + (ML19340B584)
- 05000306/LER-1980-030, Forwards LER 80-030/03L-0 + (ML19340B585)
- ML19340B586 + (ML19340B586)
- ML19340B587 + (ML19340B587)
- 05000306/LER-1980-030-03, /03L-0:on 801008,diesel Generator D2 Tripped on High Crankcase Pressure When Eductor Hose Failed.Caused by Burst Eductor Hose.Hose Replaced on Both Diesel Engines + (ML19340B590)
- ML19340B591 + (ML19340B591)
- ML19340B592 + (ML19340B592)
- PNO-I-80-159, on 801031,during Full Power Operation,Target Rock Relief Valve Opened & Failed to Reseat.Manual Scram Was Initiated & Reactor Is Being Cooled Down Via Main Condenser. Valve Reclosed at 340 Psi W/Reactor Stable.Cause Unknown + (ML19340B593)
- ML19340B594 + (ML19340B594)
- ML19340B595 + (ML19340B595)
- ML19340B596 + (ML19340B596)
- ML19340B605 + (ML19340B605)
- ML19340B608 + (ML19340B608)
- B10118, Application to Amend License DPR-61,changing Tech Specs Re Monthly Manual Tests of ECCS Components.Class III Fee Encl + (ML19340B614)
- ML19340B616 + (ML19340B616)
- ML19340B617 + (ML19340B617)