Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19309H570 + (ML19309H570)
- 05000366/LER-1980-070-03, /03L-0:on 800422,while Performing Surveillance Procedure HNP-2-3405,reactor Core Isolation Cooling Trip & Throttle Valve Closed When Turbine Speed Reached 2,000 Rpm. Cause Not Identified.Trip & Throttle Valve Reset + (ML19309H572)
- NUREG-0670, Discusses Comments on NUREG-0670, Study of Separation of Functions & Ex Parte Rules in NRC Adjudications for Domestic Licensing. Recommends Approval of Encl Draft Ltr to Senators Ribicoff & Culver + (ML19309H573)
- ML19309H574 + (ML19309H574)
- ML19309H575 + (ML19309H575)
- 05000366/LER-1980-071, Forwards LER 80-071/03L-0 + (ML19309H576)
- ML19309H577 + (ML19309H577)
- 05000346/LER-1980-033, Forwards LER 80-033/01T-0 + (ML19309H578)
- ML19309H579 + (ML19309H579)
- ML19309H580 + (ML19309H580)
- ML19309H581 + (ML19309H581)
- 05000366/LER-1980-052, Forwards LER 80-052/03L-0 + (ML19309H582)
- ML19309H583 + (ML19309H583)
- 05000346/LER-1980-033-01, /01T-0:on 800425,determined from Bechtel Study That Bleed Rate for 12 Hydraulic Snubbers Would Be Insufficient to Permit Thermal Growth of Piping During Transient Concurrent W/Locked Snubber + (ML19309H584)
- ML19309H585 + (ML19309H585)
- 05000366/LER-1980-071-03, /03L-0:on 800424,during Routine Reactor Startup Activities,Reactor Core Isolation Cooling Leak Detection Logic Power Failure Alarm Was Received.Caused by Component Failure.Inverter Supporting Power Was Replaced + (ML19309H586)
- ML19309H587 + (ML19309H587)
- ML19309H588 + (ML19309H588)
- 05000282/LER-1980-014, Forwards LER 80-014/03L-0 + (ML19309H589)
- ML19309H590 + (ML19309H590)
- 05000366/LER-1980-052-03, /03L-0:on 800408,during Maint of Standby Gas Treatment Sys,Power Cables to Heaters & Fans Found Undersized.Caused by Design Error.Cables Will Be Replaced by 800601 + (ML19309H591)
- ML19309H592 + (ML19309H592)
- 05000366/LER-1980-072, Forwards LER 80-072/03L-0 + (ML19309H593)
- ML19309H594 + (ML19309H594)
- 05000366/LER-1980-063, Forwards LER 80-063/03L-0 + (ML19309H595)
- ML19309H596 + (ML19309H596)
- 05000282/LER-1980-014-03, /03L-0:on 800410,during Surveillance Test,One Overpower Delta T Setpoint Was Found to Trip About 70% Above Desired Setpoint.Caused by Intermittent Capacitor.Capacitor Was Replaced + (ML19309H597)
- 05000366/LER-1980-063-03, /03L-0:on 800421,w/reactor in Startup/Hot Standby Mode,D/W Torus Temp Recorder Found Inoperable.Caused by Loose Wire on Common Terminal Block on Recorder.Connection Tightened + (ML19309H598)
- 05000295/LER-1980-020, Forwards LER 80-020/03L-0 + (ML19309H599)
- 05000366/LER-1980-072-03, /03L-0:on 800425,while Performing Surveillance Procedure HNP-2-3307,contact 2 Failed to Actuate at Set Point.Caused by Shorted Switch Inside Instrument Case.Switch Was Replaced + (ML19309H601)
- 05000306/LER-1980-013, Forwards LER 80-013/03L-0 + (ML19309H602)
- ML19309H603 + (ML19309H603)
- ML19309H604 + (ML19309H604)
- ML19309H605 + (ML19309H605)
- ML19309H606 + (ML19309H606)
- 05000295/LER-1980-020-03, /03L-0:on 800403,following Unit 2 Trip,Unit 1 Air Ejector Monitor 1RT PR26 Failed.Caused by Detector Tube Being Crushed During Routine Filter Change.Tube Replaced. Detector Functionally Tested & Returned to Svc + (ML19309H607)
- ML19309H608 + (ML19309H608)
- ML19309H609 + (ML19309H609)
- ML19309H610 + (ML19309H610)
- 05000306/LER-1980-013-03, /03L-0:on 800411,while Performing Maint,Workman Accidentally Tripped Overspeed Valve for turbine-driven Auxiliary Feedwater Pump 22.Valve Immediately Reset + (ML19309H611)
- 05000295/LER-1980-018, Forwards LER 80-018/03L-0 + (ML19309H612)
- ML19309H614 + (ML19309H614)
- ML19309H615 + (ML19309H615)
- 05000366/LER-1980-050, Forwards LER 80-050/03L-0 + (ML19309H616)
- ML19309H617 + (ML19309H617)
- ML19309H618 + (ML19309H618)
- ML19309H619 + (ML19309H619)
- ML19309H620 + (ML19309H620)
- 05000366/LER-1980-050-03, /03L-0:on 800407,during ISI Pump Operability Testing,While Shut Down for Surveillance/Vent Header Installation Outage,Determined That Standby Liquid Control Pump B Did Not Meet Acceptance Criteria + (ML19309H621)
- 05000295/LER-1980-018-03, /03L-0:on 800402,during Routine Surveillance,Both Svc Water Motor Operator Valves to Auxiliary Feedwater Pump 1C Backup Supply Failed to Stroke Properly.Caused by Limit Switch Rotors Out of Position.Rotors Readjusted + (ML19309H622)
- ML19309H623 + (ML19309H623)